Overview
LV250 (R250) Generator AVR
Product Details
Introduce
Product:
User manual:
Software Download:

Product description:


This R250 is a high-quality version of the original potentiometer and other well-known brand components. The SHUNT excitation alternator is auto-excited with a R250 voltage regulator.The regulator controls the excitation current according to the alternator’s output voltage. With a very simple conception, the SHUNT excitation alternator does not have a short circuit capacity.This product has now created a myth of zero complaints.

1.Leroy Somer Automatic Voltage Regulator R250
2. Suits leroy somer brushless alternator
3.Analogic Automatic Voltage Regulator with transistor

4.Applications Alternators LSA 42.2, 43.2, 44.2, 46.2, 47.2. Compatible with the SHUNT excitation system. The R250 is in Compliance with: IEC, VDE, NEMA, BS, CSA, UL508 CE low voltage.

 

 Voltage regulation Around ± 0.5 %
 Supply range 85 to 139 V
 Potentiometer for voltage setting 1000Ω /0.5W min. setting range ±5%
 Operating at 50 Hz Threshold at 48 Hz without LAM forimpactsbetween 30 and 40% of the rated
 Load
 Threshold at 48 Hz with LAM 13% forimpacts between 40 and 70% of the rated
 Load.
 Threshold at 48 Hz with LAM 25% for impacts > 70% of the rated load
 Operating at 60 Hz Threshold at 58 Hz without LAM forimpacts between 30 and 40% of the
 Rated load
 Threshold at 58Hz with LAM 13% for impacts 40 and 70% of the rated load
 Threshold at 58Hz with LAM 25% for impacts > 70% of the rated load
 Specific operating Threshold at 57Hz without LAM for speed variations at a steady state > 2 Hz
 Threshold at 65Hz without LAM for speed and tractelec / gearlec (U/F gradient)
 Special: the factory setting 48Hz 2U/F gradient; a special programme is
 Possible on request.
 Threshold at 47.5 Hz without LAM for speed variations at a steady state > 2 Hz