Welcome Customer !

Membership

Dongguan Tuancheng automation equipment Co., Ltd
Free Member ·1YRS
,
Other

Main Products: 发电机

Xwboo>Products

Dongguan Tuancheng automation equipment Co., LtdFree·1YRS

  • E-mail

  • Phone

    +86-769-23836636,+86-769-22768286

  • Address

    Wentang Road,Chashang industrial zone #18,Dongcheng,Dongguan,Guangdong,China

Contact Now

EA16(400Hz) Generator AVR

Model
Nature of the Manufacturer
Other
Product Category
Generator AVR
Place of Origin
City, Province
Overview
EA16(400Hz) Generator AVR
Product Details
Introduce
Product:
User manual:
Software Download:

Product description

 This EA16 is for 400 Hz system.It is similar to the original EA15A in power and voltage sensing capabilities but with new enhanced paralleling functions; the user can now select the CT inputs either 1 & 5 Amp or use new A1 & A2 analogue signal inputs terminals for use with PLC paralleling controls. It has new over-voltage excitation safety circuits to prevent damage caused by the accidental detachment of the sensing wires or irregularities on the generator’s excitation circuits.


Main features:

1、KUTAI EA16 Can Used In Parallel Operation.

2、Soft Start Voltage Ramping  

3、Load CT Current Compensation, Analogue Voltage Input 

4、Suitable for brushless style generator sensing Input 170~510VAC

5、Two types: 400HZ  and 50-60HZ

    
Specifications:
 

Sensing Input

Voltage 170~510 VAC single phase 2 wire

Frequency 50/60 Hz
*EA16-400Hz : Frequency 400 Hz

Power Input

Voltage 60~300 VAC single phase 2 wire

Output

Voltage Max. 90 VDC @ 240 VAC input
Current Continuous 16A, Max. Intermittent 20A for 10 sec.
Resistance Min. 6 Ohm @ 35 VDC

Voltage Regulation

< ±0.5% (with 4% engine governing)

Voltage Build-up

Residual volts at AVR terminal > 5 VAC

External Volts Adjustment

±5% with 2 K Ohm 1 watt trimmer

Unit Power Dissipation

Max. 10 watt

Thermal Drift

0.03% per °C change in AVR ambient

Under Frequency Protection

55 Hz @ 60 Hz / 45 Hz @ 55 Hz (Adjustable)
*EA16-400Hz : 360 Hz (Adjustable)

CT Current Compensation Input

1A or 5A (Selectable)

Analogue Input

±5 VDC ±10% AC @ ±3 VDC

Environment

Operating Temperature : -40~70 °C
Storage Temperature : -40~85 °C
Relative Humidity : Maximum 95%
Vibration : 3.3G @ 100~2 KHz

AVR Controls Functions

VOLT : Voltage Adjustment
STAB : Stability Adjustment
U/F*: To Set the U/F Knee Point
DROOP : To Adjust Droop
TRIM : Analogue Input Adjustment
(*U/F: Under Frequency Protection)

Dimensions

156.0 (L) x 106.0 (W) x 43.0 (H) mm

Weight

450g ±2%