Scope of use
FCGW series of composite insulation dry-type bushing for AC power system with rated voltage of 35KV, frequency of 50HZ outdoor substation, as the high-voltage conductor through walls or other grounding conductor, as high voltage electrical insulation box mechanical support, is so out of the line of vacuum circuit breaker 10KV high voltage insulation and support. It is especially used to prevent flashing accidents effectively, and it is a replacement product of porcelain through wall sleeving widely used at present.
Conditions of use:
Ambient temperature: -40 C ~+40 C
Altitude: 1000M
Stain grade: can be used in grade III heavy stains area
Model description
technical parameter
| Model | KV Rated voltage | A Rated current | Lmm Length of bushing | N Bending damaging load | power frequencywithstand(peak)not lessthan | full wave lighting impulsewithstand voltage KV(peak)not lessthan |
| FCGW-10/200/630 | 10 | 200-630 | 535 | 625 | 1250 | 30 | 75 |
| FCGW-35/630~1600A | 35 | 630-1600 | 1395 | 625 | 1250 | 95 | 200 |
Composite insulation dry-type bushing by copper conducting bar, new materials in the insulation sheath, composite insulating outer sheath core and grounding flange.