ApplicationscopeTNR-XseriessurgeprotectivedeviceissuitableforprotectingallkindsofelectronicandelectricalequipmentsinbuildingsofT1classlightningprotectionarea
Application scope
TNR-X series surge protective device issuitable for protecting all kinds of electronic and electrical equipments inbuildings of T1 class lightning protection area, where it’s easy caused lightningovervoltages. Mainly used for main distribution system and installed on thefront end of power distribution cabinet as First tier protection
IEC61643-11 Standards
A surge protective device of T1 should be installed at the general distributionbox connected with the power supply. The voltage level of surge protective deviceshould be less than or equal to 2.5KV. When the impulse current value is notdetermined, the impulse current should be equal to or larger than 12.5KA
Technical parameter
| Model | TNR-X(100) | TNR-X(50) | TNR-X(25) | TNR-X(15) |
| Maximum sustained operating voltage Uc(V~) | 255,385,440 | 255,385,440 | 320,385,440 | 320,385,440 |
| Nominal discharge current ln(ka) | 50 | 50 | 50 | 30 |
| Maximum impact current limp(ka) | 100 | 50 | 25 | 15 |
| Protection level Up(kv) | <2.5~4.5 | <2.5~4.0 | <2.5~3.5 | <2.5 |
| Protection mode | L/N-PE L-N | L-N-PE L-N | L-N-PE L-N | L-N-PE L-N |
| response time (ns) | <100 | <100 | <25 | <25 |
| Working temperature range(℃) | -40~+70 |
| Intercepting area of access wire(mm²) | 16-35(Multi strand copper cored line) |
| Power supply system | TN TT IT |
Product connection and size
Installation matters
This product is installed in parallel in front of the protected equipment, and is installed with fusing circuit protection. This product is installed around the guide rail as a combustible material, and should keep the 10cm distance from each part.