5" LCD Touch screen lithium battery smart charger
Functional details
1. Hot plug
Plug technology is applied to thecharging module to provide convenience for installation and maintenance. Theaccess of the charging module to the system shall not disturb the outputvoltage of the system.
2. Advanced current sharing technology
Under constant voltage working mode,the charging modules can share current automatically within 10S, with degree ofunbalance less than ±0.5A.
3. Control of input limited power
Refer to Fig. 1-8 for the relation betweenthe output power and input voltage of the charging module. When the inputvoltage is within 220 Vac ~ 280 Vac (return difference is less than 5V), the module can output themaximum power of 7 KW; when the input voltage is within 90 Vac ~ 220 Vac, themodule can still work normally under limited power mode.
4. Control of output constantpower
When there is a rated input voltage, the output power of the module is 7KW
The charging moduleadopts two working modes:
1) The module receives monitoringinstructions and works in 32A mode or 16A mode (with different power limits).
2) Outputs 50-500V and 500-750V. Whenthere is no required voltage, the power-on defaults to work in the low-voltagesection. When the actual output of the module is higher than 525V, the moduleautomatically switches to the high-voltage section. When the demand is lowerthan 500V, it will automatically switch back to the low-voltage section towork. When the output of the module changes from high voltage to low voltage,the output of the module will drop briefly across the switching point; when theoutput of the module changes from low voltage to high voltage, there is no dropin the output of the module when it crosses the switching point. When the switchingpoint is crossed, the power output is as above Graph curve way.
5. Temperature limited power
Under 55°C ambient temperature, themodule can output full power of 7 kW;
Over 55°C ambient temperature, themodule shall be used by derating with the power Linearly .
Under 65°C ambient temperature, theallowable output power of the module is 3,500 W.
Under 75°C ambient temperature, theoutput power of the module is reduced to 0.
7. Regulation of output current limiting point
The module has stepless currentlimiting function. Through the external monitoring module, the current limitingpoint of the module is adjustable in the range of 0~20A. When the outputvoltage is between 50Vdc~750Vdc
When, the current limiting accuracy ofthe module is ±0.3A.
8. Regulation of output voltage
The output voltage of the module can beregulated constantly through the external monitoring module, with regulationrange of 50Vdc ~ 750Vdc and minimum regulationstep of 0.1 Vdc.
9. Fan control
The built-in processor of the modulecan regulate the speed of the fan according to the internal temperature andoutput current of the module.
10. Protection of input overvoltage/ voltageshortage
The input of the module is asingle-phase AC voltage. When the input voltage is lower than 90Vac or greaterthan 280Vac, the module will stop working and no output.
When an overvoltage or undervoltagealarm occurs, the module will report the alarm information to the monitoringmodule; when the input voltage returns to the normal range, the alarmdisappears and the module recovers
Return to normal working condition.
11. Output overvoltage protection
Manualintervention is required after overvoltage protection to boot.
The softwareovervoltage protection point can be set through the monitoring module, thesetting range is 76Vdc~778Vdc, and the factory default value is 778Vdc.
Manualintervention method: The module can be reset through the monitoring module, orthe module can be reset by re-powering after the AC power failure.
12. Over-temperature protection
The environmental over-temperatureprotection point is 80°C. When the DC panel has a temperature over 85°C, themodule will stop working; when the DC panel has a temperature below 75°C, themodule will automatically work again.
13. Protection of internal bus fault
When the internal bus voltage of themodule is beyond the overvoltage/ voltage shortage protection point, the modulewill be powered off automatically. At this time, there is no output from themodule and the fault indicator light is on.
14. Short circuit protection
In case of short circuit of the module,it will be subjected to protective shutdown and the red indicator light of thepanel is on, and this condition will be transmitted to the monitor of the“module fault".
15. Interruption of background communication
After module communication interruption,the protection indicator light will flash and the module will be subject toshutdown protection. When the communication is recovered, the protectionindicator light recovers to normal state and the module works again.
16. Protection against fan fault
In case of module communicationinterruption over 8S, the module will be subject to shutdown protection,without voltage output and the protection indicator light will flash. Afterfault removal, the module will work automatically again.
17. Monitoring performance
The charging module is equipped withCAN bus. It can also be converted to RS232 via the protocol converter, and theRS485 protocol communicates with the external monitoring module.

Category | Name | Parameter |
Environmental conditions | Operating temperature | -40°C ~ +75°C, derating is required when the temperature is above 55°C. |
Storage temperature | -40℃ ~ +70℃ | |
Relative humidity | ≤95%RH, No condensation | |
Cooling way | Forced air cooling | |
Altitude | 2000m, derating is required when the altitude is above 2000 m | |
Atmospheric pressure | 79kPa ~ 106kPa | |
AC input | Input phase | Single phase L/N or L1/L2 + PE |
Voltage rage | 90-280Vac | |
The maximum static voltage borne under no operation | 300Vac | |
Rated voltage | 220Vac | |
Maximum current | 32A | |
Grid frequency | 45Hz~65Hz | |
Rated frequency | 50Hz/60Hz | |
DC output | Voltage range | 50Vdc ~ 750Vdc |
Current range | 0 ~ 20A | |
Rated current | 9.33A@750V(Set current limit point, current limit point 1.0 is 9A, converted into current limit point according to actual current demand) | |
Steady voltage precision | <±0.5% | |
Steady current precision | ≤±1%(rated range of 20% ~ 99% for output load) | |
Load regulation rate | ≤±0.5% | |
Grid regulation rate | ≤±0.1% (testing range is 320V ~ 530V) | |
Startup overshoot | ≤±3% | |
Power factor and THD | Power factor | ≥0.95 Full-load output power of @20%~50% |
≥0.98 Full-load output power of @50%~99% | ||
≥0.99 Full-load output power, input nominal voltage and frequency of @99% | ||
THD | ≤5% Full-load output power of @50%~99% | |
Noise index | Peak-to-peak value noise | ≤1% (150~750V, 0~20MHz) |
Others | Safety requirements | C lassA , Meet the requiremnt of NB/T 33001-1-2010,NB/T 33008-1-2013 |
Efficiency | ≥94.5%, @750V, 50%~99% load current, under rated input voltage | |
Instant impulse current upon startup | <20A | |
Temperature Coefficient(1/℃) | ≤±0.01% | |
Startup duration (select the startup mode through the monitoring module) | Normal startup mode: the time delay from AC power-on to module output is ≤ 8s. | |
Output delayed startup: The startup duration can be set through the monitoring module, with default output startup duration of 3~8s. | ||
Noise | ≤65dB(A) (1m away) | |
Earthing resistance | Earthing resistance ≤ 0.1Ω, bearable current ≥ 25A | |
Leakage current | Leakage current≤3.5mA | |
Surge protection | Meets IEEE C62 41-1991 Class B3 rating, 6kV/3kA (1.2/50μs impulse voltage and 8/20μs inrush current mixed wave) | |
Insulation resistor | The insulation resistance of DC part and AC part to housing and the AC part to the DC part shall be ≥ 10MΩ. | |
Insulation strength | AC input terminal to the housing 3535V DC voltage 20S clock, no breakdown, no arcing phenomenon, steady state leakage current is less than 1mA; AC input terminal to DC output terminal 3535V DC voltage 20S clock, no breakdown, no arcing phenomenon, steady-state leakage current is less than 1mA; DC output terminal to the housing 3535V DC voltage 20S clock, no breakdown, no arcing phenomenon, steady state leakage current is less than 1mA; | |
ROHS | R5 | |
Mechanical parameters | Size | 87Mm (H) ×177.5mm (W) ×385mm (D) |
Weight | ≤15kg |