Welcome Customer !

Membership

Guangzhou Zhengneng Eetronic Technology Co. Ltd.
Free Member ·1YRS
,
Other

Main Products: 电力检测设备

Xwboo>Products

Guangzhou Zhengneng Eetronic Technology Co. Ltd.Free·1YRS

  • E-mail

    hsh@znele.com

  • Phone

  • Address

    Address, 4F, No.771 Guangcong 8th Road, ZhongLuoTan, Baiyun District, Guangzhou, Guangdong, China

Contact Now

Double clamp multi-function groun

Model
ES3002
Nature of the Manufacturer
Other
Product Category
Earth Resistance Series
Place of Origin
City, Province
Overview
Double clamp multi-function groun
Product Details
ES3002 Double clamp multi-function grounding resistance tester is also called double clamp grounding resistance tester, The advanced grounding resistance tester integrates a variety of measurement methods. In addition to the traditional function of ancillary grounding resistance, it also has the unique function of measuring without auxiliary ground. It uses a large LCD gray screen backlight display and microprocessor technology, through the microprocessor-controlled 2-wire, 3-wire, 4-wire, selection method, double clamp method to test ground resistance. Large-diameter current clamp design, using double jaw measurement technology, without the need to hit the auxiliary ground, without the need to isolate the grounding body and equipment to achieve on-line measurement. Widely used in telecommunications, electricity, meteorology, computer rooms, oil fields, power distribution lines, iron tower transmission lines, gas stations, factory grounding networks, lightning rods and so on.The instrument has the characteristics of precise, fast, simple, stable and reliable.
ES3002 Double clamp multi-function grounding resistance tester is controlled by a microprocessor and can accurately detect ground resistance, soil resistivity, ground voltage, DC voltage and AC current. It uses a fast filtering technique to minimize interference. Displaying the resistance value of the auxiliary electrode in the same screen, which is convenient for judging the measurement error caused by environmental factors, facilitating more accurate measurement of the grounding true resistance value, and storing 500 sets of data at the same time.The online monitoring data can be monitored by the monitoring software. USB data can be uploaded to the PC and has unique functions such as numerical maintenance and intelligent alarm prompting.
ES3002 Double clamp multi-function grounding resistance tester consists of host computer, monitoring software, test line, USB cable, and grounding pin. It has the functions of reading, checking, saving, reporting and printing of historical data.
1.Rang and Accuracy
Test FunctionRangeAccuracyResolution
2、3、4 wire method for measuring ground resistance (Re)0.00Ω~29.99Ω±2%rdg±5dgt(remark 1)0.01Ω
30.0Ω~299.9Ω±2%rdg±3dgt0.1Ω
300Ω~2999Ω±2%rdg±3dgt1Ω
3.00kΩ~30.00kΩ±2%rdg±3dgt10Ω
DC resistance(Re)0.0Ω~299.9Ω±2%rdg±3dgt0.1Ω
300Ω~2999Ω±2%rdg±3dgt1Ω
3.00kΩ~30.00kΩ±2%rdg±3dgt10Ω
Selection method for measuring ground resistance(Re)0.00Ω~29.99Ω±2%rdg±5dgt(remark 1)0.01Ω
30.0Ω~299.9Ω±2%rdg±3dgt0.1Ω
300Ω~3000Ω±2%rdg±3dgt1Ω
Double clamp method for measuring ground resistance (Re)0.01Ω~0.99Ω±10%rdg±10dgt0.01Ω
1.0Ω~9.9Ω0.1Ω
10Ω~100Ω1Ω
Soil resistivity(ρ)0.00Ωm~99.99Ωmρ=2πaR (remark 2)0.01Ωm
100.0Ωm~999.9Ωm0.1Ωm
1000Ωm~9999Ωm1Ωm
10.00kΩm~99.99kΩm10Ωm
100.0kΩm~999.9kΩm100Ωm
1000kΩm~9999kΩm1kΩm
Ground voltageAC 0.00~100.0V±2%rdg±3dgt0.01V
AC currentAC 0.0mA~1000A±2%rdg±3dgt0.1mA
Remark:
1. Reference conditions: accuracy with Rh Rs < 100Ω。
Working conditions:Rh max=3kΩ+100R<50kΩ;Rs max=3kΩ+100R<50kΩ
2.Depends on the measurement accuracy of R,π=3.14, a:1 m~100m;

2.General specification
FunctionGround resistance、Soil resistivity、DC resistance、Ground voltage、AC current
Ambient temperature and humidity23℃±5℃,below 75%rh
Interference voltage<20V (should be avoided)
Interference current<2A (should be avoided)
Measure R electrode spacinga>5d
Measured ρelectrode spacinga>20h
PowerDC 6V 4.5Ah lead-acid battery lasts more than 100 hours standby
BacklightControllable backlight, suitable for use in dim places
measurement modePrecise four-wire、 three-wire measurement, simple two-wire measurement、Selection method, double clamp method for measuring grounding resistance
Measurement methods2.3.4-wire method measurement: Polarization method, measuring current 20mA Max
Soil resistivity: four-pole method
Selectivity Measurement: Polarization Method, Measuring Current 20mA Max
Double clamp method: non-contact mutual inductance measurement method, test current 1mA Max
DC resistance: polarization method
AC current: average rectification (clamp)
Ground Voltage: Average Rectification(between S-ES interface)
Test voltage waveformSine wave
Test frequency128Hz
Short circuit test currentAC 20mA max
Open circuit test voltageAC 28V max
Electrode spacing range1m~100m
Display mode4-bit large LCD display, with backlight
Measurement instructionsLED flashing indicator during measurement
LCD size111mm×68mm
LCD display field108mm×65mm
Instrument sizeL/W/H:277.2mm×227.5mm×153mm
Clamp sizeL/T/H:101mm×27mm×214mm
Test line4 strips:red 15m,black 15m, yellow 10m,green 10m each one
Simple test line2strips:yellow 1.5m,green 1.5m each one
Auxiliary Grounding rod4PCS:φ10mm×200mm
Current clamp2PCS:φ4 mm Banana plug
Current clamp diameterφ50mm
Current clamp lead Length 2m
Measure timeAC current:about 2 times/sec;
Ground voltage:about 2 times/sec;
grounding resistance、soil resistivity: about 7 seconds/time
Line voltageMeasurement below AC100V (ground voltage measurement function cannot be used to measure commercial power)
USB interfaceWith USB interface, storage data can be uploaded to the computer, save and print
Communication LineOne USB communication line, 1.5m long
Data storage500 groups, "MEM" storage indicates, flashing "FULL" symbol indicates that the memory is full
Data reviewData review function: "MR" symbol display
Overflow displayOver-range overflow function: "OL" symbol display
Current clamp low current indicationWhen measuring by the selection method or the double-clamp method, when the current signal received by the current clamp A is lower than 0.5 mA, the symbol “ ” is displayed, and at this time, the clamping direction of the current clamp A should be checked.
Interference testAutomatic identification of interference signals, "NOISE" symbol indication when the interference voltage is higher than 5V
Auxiliary grounding testWith auxiliary ground resistance test function, 0.00KΩ ~ 30kΩ (Rh max = 3kΩ +100R <50kΩ; Rs max = 3kΩ +100R <50kΩ)
Alarm functionAlarm when the measured value exceeds the alarm setting value
Battery voltageReal-time display of battery power, reminding timely charging when battery voltage is low
Automatic Shutdown“APO” Indicates, automatic Shutdown After 15 Minutes
Power consumptionStandby: 40mA Max(Backlight off)
Turn on backlight: 43mA Max
measuring:120mA Max(Backlight off)
WeightInstrument: 2450g(including battery)
Current clamp:940g(2PCS)
Test lines:1300g(including simple test line)
Auxiliary grounding rod: 850g(4PCS)
Working temperature and humidity-10℃~40℃;below 80%rh
Storage temperature and humidity-20℃~60℃;below 70%rh
Overload protectionGrounding resistance:AC 280V/3 seconds between H-E and S-ES ports
Insulation resistance20MΩ以上(500V between circuit and housing)
Pressure resistanceAC 3700V/rms(between circuit and housing)
Electromagnetic propertiesIEC61326(EMC)
Suitable for safety regulationsIEC61010-1(CAT Ⅲ 300V、CAT IV 150V、pollution level 2);
IEC61010-031;
IEC61557-1(grounding resistance);
IEC61557-5(soil resistivity);
JJG 366-2004.
JJG 366-2004(ground resistance meter);
JJG 1054-2009(Clamp grounding resistance meter).

Instrument1PC
Instrument bag1PC
Auxiliary grounding rod4PCS
Current clamp2PCS
Monitoring software CD1PC
USB communication line1PC
Test line4PCS
Simple test line2PCS
6V Battery (built-in)1PC
charger1PC
Manual, certificate1SET