DC low resistance tester

Model
FR3060
Nature of the Manufacturer
Other
Product Category
DC Low resistance Series
Place of Origin
City, Province
Overview
DC low resistance tester
Product Details
FR3060 digital DC low resistance meter, also known as micro-ohmmeter, ohmmeter, equipotential tester, uses microprocessor technology, four-wire method test, safe, precise and reliable. Mainly used to measure the cable resistance, contact resistance of switches, connectors, relays, resistances of coils, motors, transformer windings, and equipment enclosures, lightning protection belts, ground beams, structures, cabinets, steel bars, water pipes, windows, guardrails, heat dissipation Device, assembly line, and other objects between the metal components of the connection resistance test. Widely used in telecommunications, electric power, meteorology, machine rooms, oil fields, power distribution lines, transmission lines of iron towers, gas stations, factory grounding networks, lightning rods, etc.
FR3060 digital DC low resistance meter is composed of host, monitoring software, test line, communication line, etc. The large-screen LCD display of the host makes it easy to see at a glance, and the port has an anti-overload function to avoid accidental operation and burnout of the instrument. Can store 500 sets of data, resistance measurement range: 0.001mΩ ~ 300.0KΩ. The host computer software has the functions of reading, viewing, saving, and reporting historical data.
I. Model Contrast
ModelFR3060AFR3060
Resistance range0.01mΩ~30.00KΩ0.001mΩ~300.0KΩ
Resolution10uΩ1uΩ
Accuracy±0.1%FS ±0.1%FS
Data storage500 groups500 groups
USB connect computernohave
Rechargeable functionhavehave

II. Technical Parameters
FunctionMainly used to measure the wire resistance of the cable, the contact resistance of the switch, the connector, the relay, the resistance of the coil, the motor, the transformer winding, the metal riveting resistance, the connection resistance test between the metal components, the low value resistance test, the ground floor ground Resistance test of connecting conductor, contact resistance test, etc.
Test methodFour-wire test
Short circuit test current≥1A
Open circuit voltage≤4.2V
Over load protectionhave
Capacity factorMeasure capacity factor≤8W
PowerDC 3.7V 2000mAh Large-capacity lithium battery
BacklightControllable gray-white screen backlight, suitable for use in dim places
Display modeLCD display, gray screen backlight
LCD sizeL/W: 72 mm×55mm
Instrument sizeL/W/H:187 mm*119 mm*50mm
Test line lengthAbout 60cm,red、black each 1PC
Measurement timeabout 2 times/sec
USB interfaceWith micro USB interface
Communication linemicro usb communication line 1PC
Data storage500 groups, "MEM" storage instructions, display "FULL" symbol indicates that the storage is full
Data reviewData review function: "READ" symbol display
Overflow DisplayExceed measurement range overflow function: “OL ” symbol display
battery voltageThe battery power is displayed in real time, suggesting needs to be charged in time when the battery voltage is low.
Automatic shut-downThe instrument automatically shuts down after about 15 minutes without operation.
Power consumptionStandby: about 100mA (backlight off)
Boot on backlight: about 105mA
Measurement:2A max
WeightInstrument: 480g(with battery)
Test line:250g
Working temperature and humidity-10℃~50℃;below 70%rh
Storage temperature and humidity-20℃~60℃;below 70%rh
Overload protection AC 220V / 0.0001 seconds between C1-C2 P1-P2 port, after overload protection, the meter needs to be restarted for normal testing
Insulation resistancecAbove 10MΩ (500V between circuit and enclosure)
Pressure ResistanceAC 3700V/rms(Between the circuit and the housing)
Electromagnetic characteristicIEC61010-4-3,adio frequency electromagnetic field≤1V/m
Suitable for Safety RegulationsIEC61010-1, CAT Ⅲ 600V, pollution level 2, JJG724-1991 "Verification Regulations for DC Digital Ohmmeter", JJG166-1993 "Verification Regulations for DC Resistors", "DL / T967-2005 Loop Resistance Tester and DC Resistance Fast Tester Verification Regulations"
Instrument1PC
Bag1PC
Monitoring Software CD1PC( FR3060 only)
USB communication line1PC
Test line2PCS(red, black each 1)
charger1PC
Manual, certificate1SET