Welcome Customer !

Membership

Henan Senyuan Electric Co., Ltd.
Free Member ·1YRS
,
Other

Main Products: 电气设备

Xwboo>Products

YBM(Y)-12/0.4 (TBM) Prefabricated Substation

Model
Nature of the Manufacturer
Other
Product Category
Pre-installed Transformer Substation And Switching Station
Place of Origin
City, Province
Overview
YBM(Y)-12/0.4 (TBM) Prefabricated Substation
Product Details

Product Introduction

YBM(Y)-12/0.4 (TBM) high/low voltage prefabricated substation is applied to TBM power supply and distribution system and provides safe and reliable power for TBM. It is the dedicated power distribution for TBM, which integrates power distribution unit, power transformer and reactive compensator, and possess the features of strong completeness, small size, compact structure, reliable operation, easy maintenance and removable. The product meets the standard requirements of GB/T 17467-2010 high-voltage/low-voltage prefabricated substation and DL/T 537-2002 high-voltage/low-voltage prefabricated cubical substation.

Product Features

YBM(Y)-12/0.4 (TBM) high/low voltage prefabricated substation adopts metal-closed box type, the protection level is not less than IP55 with high sealing performance;

The structure of substation is arranged according to the Chinese character “目",which can be divided into four compartments, namely, HV compartment, transformer compartment I, transformer compartment II, LV compartment. Each compartment is separated from other by steel plate.

Each transformer is placed in separate compartment, each compartment has separate temperature and humidity control system, which is not only conducive to transformer heat dissipation, but also conducive to energy saving.

The enclosure and internal components of substation are all equipped with anti-shock precautions with high insulation performance and heat dissipation performance.

Technical Parameters

No.

Item

Unit

Parameter

1

High Voltage Side Rated Voltage

kV

12

2

Low Voltage Side Rated Voltage

kV

0.4

3

Rated Frequency

Hz

50

4

Transformer Rated Capacity

kW

≤3000

5

High Voltage Side Rated Current

A

Note 1

6

Low Voltage Side Rated Current

A

≤6300

7

High Voltage Side Rated Short-time Withstand Current

kA

20

8

High Voltage Side Rated Short-circuit Making Current (Peak)

kA

Note 2

9

High Voltage Side Rated Short-circuit Breaking Current

kA

Note 2

10

Low Voltage Side Rated Limit Short-circuit Breaking Capacity

kA

≥35

11

High Voltage Side Rated Current

A

Note 1

12

High Voltage Side Rated Short-time(1min)Power Frequency Withstand Voltage

Phase to Phase

Phase to Earth

kA

42

Clearance

kA

48

13

High Voltage Side Rated Lightning Impulse Withstand Voltage

Phase to Phase

Phase to Earth

kA

75

Clearance

kA

85

Note 1: depends on the rated current value of fuse

Note 2: limited to high voltage fuse

Similar Product Recommend