| Environmental temperature | -20℃~+55℃ |
| Environmental relative humidity | ≤95% |
| Basic design dosage of fire extinguishing agent | ≥0.15kg/m³ |
| Extinguishing time | ≤30s |
| Release time | ≤120s |
| Outlet temperature at 5 mm of nozzle | landing≤180℃、hanging≤200℃ |
| Maximum temperature of box body | landing≤100℃、hanging≤200℃ |
| DC resistance | 1~5Ω |
| Starting condition | DC24V/1~2A(minimum starting current 700 mA) |
| Safe current | 150mA/5min |
| Multi-station linkage mode | series connection |
| Term of validity | 7years |
| Insulation property of resultant | >105MΩ(Non-corrosive: No obvious change in color of brass plate.) |
| Chemical Components of Fire Extinguishing Agents | Strontium nitrate and potassium nitrate 45%~70%(W/W) |
| Toxicity test | The mice did not lose the ability to escape after the experiment, and did not die within 3 days after the experiment. |