AVR 300/300V Copper-core PVC Insulated Soft Cable for Installation Use
Standards
Standard:JB/T8734.4-2012
Rated voltage: 300/300V
Applications
Applicable to AC rated voltage U ○ / U for 300 / 300V and below electrical appliance, instrumentation panel, electronic equipment and automation device.
Characteristics
1.Max. Operating Temp of Conductor. 70℃(AVR)or 90℃(AVR-90)
2.Min. Ambient Temperature during installation: 0℃
3.Min. Bending Radius: 6 x cable O.D if diameter above 16mm
4 x cable O.D if diameter below 16mm
4. Insulated material for high-quality PVC, moisture-proof, anti-oil, anti-chemical corrosion and other characteristics
5.100m / 200m / 500m per roll or custom length
| |
| AVR,AVR-90 300/300V Copper-core PVC insulated soft cable for installation use |
| Conductor Cross Section Area(mm2) | Conductor (NO./mm) | Insulation Thickness(mm) | Average O.D.(mm)Upper Limit | Max. Resistance of Conductor at 20 ℃(Ω/KM) | Min. Resistance of Insulation at 70 ℃ or 90℃(MΩ/KM) |
| Copper | Tinned Copper |
| 0.08 | 7/0.12 | 0.4 | 1.3 | 247 | 254 | 0.018 |
| 0.12 | 7/0.15 | 0.4 | 1.5 | 158 | 163 | 0.016 |
| 0.2 | 12/0.15 | 0.4 | 1.6 | 92.3 | 95.0 | 0.014 |
| 0.3 | 16/0.15 | 0.5 | 2.0 | 69.2 | 71.2 | 0.014 |
| 0.4 | 23/0.15 | 0.5 | 2.1 | 48.2 | 49.6 | 0.012 |
| | | | | | | |