Boiler control

Model
Nature of the Manufacturer
Other
Product Category
PLC Control System
Place of Origin
City, Province
Overview
The temperature detection part includes: system backwater temperature, system water supply temperature, system water supply temperature, outdoor temperature, boiler water intake temperature, boiler water discharge temperature, air preheater outlet air temperature, air preheater import smoke temperature, furnace export smoke temperature, Before the coal saving device smoke temperature, After the coal economizer smoke temperature, air preheater export smoke temperature, dust collector export smoke temperature.
Product Details

Product details:

The pressure inspection part includes: system backwater pressure, system water supply pressure, system water supply pressure, cycle water pump pressure, boiler water intake pressure, boiler water discharge pressure, blower outlet air pressure, coal economizer post-pressure, air preheater outlet air pressure, furnace exit pressure, air preheater Exporting flue gas pressure, air preheater inlet flue gas pressure.
The flow detection part includes: system backwater flow, system water supply flow, system water supply flow, boiler water flow, blower exit flow.
The liquid level inspection part includes: water level of water supply tank, water level of dust collector.
Other inspection parts include: flue gas oxygen content, furnace speed, fan speed and current, fan speed and current, cycle pump speed and current, filling pump speed and current, various related equipment start and stop state indication.
Control adjustment
Water boiler combustion system adjustment
Adjustment of boiler combustion system according to required heat
According to the actual situation, combined with the data and experience of the outdoor ambient temperature of the local winter calendar year, we can formulate a curve of the temperature of the boiler outlet with the outdoor temperature, so that the automatic control system automatically adjusts the water temperature of the boiler outlet according to the changes in the outdoor temperature. Real-time adjustment is achieved, while avoiding the major disturbance caused by human modification to the system, and at the same time saving energy. In addition, taking into account the different heat(loads) required during the early and deep cold periods of winter, during the day and night, allowing the automated system to automatically track changes in outdoor temperature and 24-hour undisturbed changes in the boiler outlet water temperature, The heat provided by the boiler is consistent with the heat required.