S MOULDED CASE CIRCUIT BREAKER
| |
| APPLICATIONS: | Moulded case circuit breaker is suitable for circuit AC 50/60Hz, rated voltage up to AC 660V, rated operating current to 630V. It features normal structure, reliable performance, complete accessories & high breaking capacity, used for power distribution and protecting the circuit and electrical equipment against overload short circuit. It complies with standard of IEC947-2.DD. | | TRIPPING CHARACTERISTICS OF MCCB: | Rated current of release (A) | Thermodynamic release (ambient temp +40℃) | Operational current of magnetic release (A) | 1.05In (cold state) inoperative time(h) | 1.30In (heat state) inoperative time (h) | In≤63 | ≥1 | <1 | 10-50In±20% | 63<In≤250 | ≥2 | <2 | 10In±20% | 25<In≤800 | ≥2 | <2 | 5-10In±20% |
| | | Type | Rated current (A) | Rated insulating voltage | Pole number | Rated operating voltage | Untimate short circuit breaking capacity 1cu KA | -Service short circuit breaking capacity 1cu KA | AC380V (400) | AC660V (690) | DC250V | AC380V (400) | AC660V (690) | 125E | 12.5,16,20, 25,32,40,50, 63,80,100 | 600V | Two three four | 380V 660V | 15 | - | - | 7.5 | - | 125S | 25 | - | 20 | 16 | - | 160S | 16,20,25,32, 40,50,63,80, 100,125,160 | 35 | 8 | 20 | 18 | - | 160H | 50 | 10 | 40 | 25 | - | 250S | 100,125,160, 180,200,225,250 | 35 | 10 | 40 | 18 | - | 250M | 50 | 16 | 40 | 30 | - | 250H | 65 | 18 | 40 | 48 | - | 400S | 200,225,250, 315,350,400 | 35 | 16 | 40 | 18 | - | 400M | 50 | 20 | 40 | 30 | - | 400H | 65 | 25 | 40 | 48 | - | 630S | 400,500,630 | 50 | 20 | 40 | 30 | - | 630M | 65 | 25 | 40 | 48 | - | 630H | 80 | 30 | 40 | 60 | - | 800S | 500,630,700,800 | 50 | 20 | 40 | 30 | - | 800M | 65 | 25 | 40 | 48 | - | 800H | 80 | 30 | 40 | 60 | - |
|
|
| |
 |