T MOULED CASE CIRCUIT BREAKER
| |
| APPLICATION | Moulded case circuit breaker is suitable for circuit AC 50/60Hz, rated voltage up to AC 660V, rated operating current to 630V. It features normal structure, reliable performance, complete accessories & high breaking capacity, used for power distribution and protecting the circuit and electrical equipment against overload and short circuit. It complies with standard of IEC947-2. Equipment against overloads and short circuit. It complies with standard of IEC947-2. | | TRIPPING CHARACTERISTICS OF MCCB | Rated current of release (A) | Termodynamic release (ambient temp +40℃) | Operational current of magnetic release (A) | 1.05In(cold state) inoperative time (h) | 1.30In(heat state) inoperative time(h) | In≤ 63 | ≥1 | <1 | 10-50In±20% | 63 <In≤ 250 | ≥2 | <2 | 10In±20% | 25 <In ≤800 | ≥2 | <2 | 5-10In±20% |
|
|
| |
 |