application | Large and medium-sized rotating machinery and equipment such as steam turbines, water turbines, generator sets, gear boxes, water pumps, and fans. |
Overview | The system adopts the form of a frame structure, which can be connected to a variety of sensors (acceleration, speed, displacement, eddy current, etc.) and process sensors (flow, pressure, temperature, analog, etc.) to provide real-time status monitoring and It is protected, has strong expansion capability and compatibility, and is easy to install. It has a variety of performances and functions that other systems do not have. The device is an intelligent system with supporting configuration software, which can configure the monitoring parameters, and adopts a redundant power supply design to make the system more stable and more stable. |
VMS8000B/05 frame module |
Dimensions | 420mm×225mm×370mm (L×H×D) |
Hole Size | 387mm×200mm (l×h) |
Installation method | Disc |
VMS8000B/90 power module |
Input power | (1) 90~264VAC/47~63Hz; (2) 120~370VDC |
power | ≤100W |
display | OK: Green (power module backplane) |
description | Provide power for the entire system and modules |
VMS8000B/02A, VMS8000B/02B system modules |
power supply | Powered by VMS8000B/90 power module |
Key phase signal input | (1) Input impedance: >20KΩ; (2) Input frequency: <99999 rpm; (3) 1~255 pulses/period |
Adaptation sensor | (1) Eddy current sensor; (2) Magnetic sensor |
Buffered output | With original signal buffer output interface |
Output impedance | 100Ω |
Eddy current sensor power supply | -24VDC, current limit; current per channel is less than 50mA |
Modbus communication | RS485: 1, located on the back panel |
USB storage port | 1 USB port, located on the back panel |
VMS8000B/xxxx Eddy Current Displacement Function Module |
power supply | Powered by the power module, power consumption 8.0W |
input signal | Receive eddy current sensor signal |
input resistance | >20KΩ |
Sensitivity | (1) 8mm/5mm probe: 8.0mv/µm (200mV/mil) (3) 18mm probe: 1.5mv/µm (37.6mV/mil) (2) 11mm probe: 4.0mv/µm (100mV/mil) (4) 25mm probe: 0.8mv/µm (20mV/mil) |
Precision | <±1%FS@25℃ |
4~20mA current | Large load 750Ω, ±0.1%FS@25℃ |
Sensor power supply | -24VDC, current limit; current per channel is less than 50mA |
Call the | Each channel has two alarm points (two channels can be used for alarm and calculation), which can be adjusted from 0 to 99% of full scale |
Alarm delay | (1) Alarm 1 delay is set at 1~60s, and the time step is 1s (2) Alarm 2 delay is set at 1~60s, and the time step is 1s |
Relay load | 3A/30VDC, 3A/250VAC SPST dry node |
display | (1) Value: current engineering value, histogram; (2) Status display: disconnection, normal, alarm, danger, bypass |
VMS8000B/xxxx watt vibration function module |
power supply | Powered by the power module, power consumption 8.0W |
input signal | (1) Receive piezoelectric accelerometer signal (2) Receive piezoelectric speed sensor signal (3) Receive magnetoelectric sensor signal |
input resistance | >20KΩ |
Sensitivity/frequency response | (1) Piezoelectric acceleration sensor: sensitivity 100mv/g; frequency response: 10Hz~4.0KHz (2) Piezoelectric speed sensor: 4.0mv/mm/s; frequency response: 10 Hz~4.0KHz (3) Magnetoelectric speed sensor: 31.5mv/mm/s; frequency response: 10 Hz~300Hz |
Precision | <±1%FS@25℃ |
Range | Amplitude (0-500μm user-defined), intensity (0-50.0mm/s user-defined) |
4~20mA current | Large load 750Ω, ±0.1%FS@25℃ |
Buffered output | With original signal buffer output interface |
Output impedance | 100Ω |
Sensor power supply | (1) Piezoelectric sensor 4mA±10%, +24Vdc isolation (2) Passive magnetoelectric sensor |
Call the | Alarm point setting: each channel has two alarm points, which can be adjusted from 0 to 99% of full scale |
Alarm delay | (1) Alarm 1 delay is set at 1~60s, and the time step is 1s (2) Alarm 2 delay is set at 1~60s, and the time step is 1s |
Relay load | 3A/30VDC, 3A/250VAC SPST dry node |
display | (1) Numerical value: current engineering value, histogram (2) Status display: normal, alarm, dangerous, bypass |
VMS8000B/xxxx axis vibration function module |
power supply | Powered by the power module, power consumption 8.0W |
input signal | Receive eddy current sensor signal |
input resistance | >20KΩ |
Sensitivity | 8mm probe: 8.0mv/µm(200mV/mil) |
Frequency response | 2-500Hz±3dB |
Precision | <±1%FS@25℃ |
Range | Amplitude (0-500μm user defined) |
4~20mA current | Large load 750Ω, ±0.1%FS@25℃ |
Buffered output | With original signal buffer output interface |
Output impedance | 100Ω |
Sensor power supply | -24VDC, current limit; current per channel is less than 50mA |
Call the | Alarm point setting: each channel has two alarm points, which can be adjusted from 0 to 99% of full scale |
Alarm delay | (1) Alarm 1 delay is set at 1~60s, and the time step is 1s (2) Alarm 2 delay is set at 1~60s, and the time step is 1s |
Relay load | 3A/30VDC, 3A/250VAC SPST dry node |
display | (1) Numerical value: current engineering value, histogram (2) Status display: disconnection, normal, alarm, danger, bypass |
VMS8000B/xxxx speed function module |
power supply | Powered by the power module, power consumption 8.0W |
input signal | Magnetoresistive sensor, AC voltage signal, Hall sensor, pulse voltage signal |
input resistance | >20KΩ |
Precision | <±1%FS@25℃ |
Range | 0-9999rpm user defined |
4~20mA current | Large load 750Ω, ±0.1%FS@25℃ |
Buffered output | With original signal buffer output interface |
Sensor power supply | Hall sensor +12VDC; eddy current sensor -24VDC |
Call the | Alarm point setting: each channel has two alarm points; set the set value within 0~99% of full scale; |
Alarm delay | (1) Alarm 1 delay is set at 1~60s, and the time step is 1s (2) Alarm 2 delay is set at 1~60s, and the time step is 1s |
Relay load | 3A/30VDC, 3A/250VAC SPST dry node |
display | (1) Numerical value: current engineering value, histogram (2) Status display: normal, alarm, dangerous, bypass |
VMS8000B/xxxx stroke function module |
power supply | Powered by the power module, power consumption 8.0W |
input signal | Stroke sensor |
input resistance | >20KΩ |
Sensitivity | Any specific sensitivity |
Precision | <±2%FS@25℃ |
4~20mA current | Large load 750Ω, ±0.1%FS@25℃ |
Call the | Alarm point setting: each channel has two alarm points; set within 0~99% of full scale |
Alarm delay | (1) Alarm 1 delay is set at 1~60s, and the time step is 1s (2) Alarm 2 delay is set at 1~60s, and the time step is 1s |
display | (1) Numerical value: current engineering value, histogram (2) Status display: normal, alarm, dangerous, bypass |
Environmental indicators |
Operating temperature | -30℃~+65℃ |
Storage temperature | -40℃~+85℃ |
Relative humidity | ≤90%, non-condensing |
Order information |
Order number | Options |
System module |
VMS8000B/05 | Frame/LCD screen | Chassis frame with LCD display |
VMS8000B/90 | Power module | 90~264VAC/47~63Hz/120~370VDC |
VMS8000B/02A | System Module A | System mandatory module (including 1 key phase monitoring module) |
VMS8000B/02B | System Module B | Required modules for the system |
VMS8000B/00 | Expansion module | Blank expansion module |
functional module |
Function module model selection | Codename | function name | Matching sensor |
VMS8000B/□□□□ 1 signal code 2 signal code 3 way signal code 4 signal code | A | Wall Zhen monitoring point | Magnetoelectric sensor |
B | Wall Zhen monitoring point | Piezoelectric speed sensor |
C | Wall Zhen monitoring point | Piezoelectric acceleration sensor |
D | Shaft vibration monitoring point | φ8 eddy current sensor |
E | Swing monitoring point | φ8 eddy current sensor |
F | Axial displacement monitoring point | φ8, φ11 eddy current sensor |
G | Differential expansion monitoring point | φ18, φ25 eddy current sensor |
H | Eccentric monitoring point | φ8 eddy current sensor |
I | Oil film monitoring point | φ8 eddy current sensor |
J | Speed monitoring point | Magnetoresistive sensor, Hall sensor, Eddy current sensor |
L | Zero speed monitoring point | Hall sensor, eddy current sensor |
M | Bond phase monitoring point | φ8 eddy current sensor |
N | Oil motive monitoring point | Oil motive sensor |
W | Thermal expansion monitoring point | Thermal expansion sensor |
P | Valve position monitoring point | Valve position sensor |
Q | Fuel tank oil level monitoring point | Fuel tank oil level sensor |
R | Synchronizer monitoring point | Synchronizer sensor |
S | Power limiter monitoring point | Power limiter sensor |
T | Start valve monitoring point | Start valve sensor |
U | Temperature monitoring point | Platinum resistance PT100 |
V | Process quantity monitoring point | Current sensor |
0 | Expand | Expand |
Remarks: (1) Each instrument is equipped with a chassis frame/LCD display, at least one power module (up to 2 power modules can be configured to form dual power redundancy), 2 system modules, and 5 functional monitoring modules at most ; (2) A total of 1 monitoring point can be selected for the speed/zero speed module, and the system module A has a built-in key phase measurement function; (3) Each functional monitoring module can be equipped with 4 functional monitoring points. Please put together modules with the same or similar measurement functions to form the corresponding monitoring module; (4) Vibration function monitoring module CHA, CHB or CHC, CHD 2 function monitoring points as a group; Example: It is necessary to select a VMS8000B instrument to monitor 4 bearing vibration signals (using magnetoelectric sensors), 8 axis vibration signals (using eddy current sensors), 2 axis displacement signals, 1 differential expansion signal, and 1 eccentricity Module, 1 way fuel tank oil level signal, 1 way thermal expansion signal, 1 way key phase signal. |
Instrument model |
Function module number | model | description |
Instrument model | VMS8000B | Total model |
Frame model | VMS8000B/05 | required |
Power module 1 model | VMS8000B/90 | required |
Power module 2 model | VMS8000B/00 | Single power supply blank expansion, optional power supply module to form dual power supply redundancy |
System module A model | VMS8000B/02A | Required (including 1 key phase monitoring point) |
System module B model | VMS8000B/02B | required |
Function monitoring module 1 | VMS8000B/AAAA | 4 road vibration monitoring points |
Function monitoring module 2 | VMS8000B/DDDD | 4-way axis vibration monitoring point |
Function monitoring module 3 | VMS8000B/DDDD | 4-way axis vibration monitoring point |
Function monitoring module 4 | VMS8000B/FFGH | 2 monitoring points for axial displacement, 1 monitoring point for differential expansion, 1 monitoring point for eccentricity |
Function monitoring module 5 | VMS8000B/WQ00 | 1 thermal expansion monitoring point, 1 fuel tank oil level monitoring point |