Welcome Customer !

Membership

Yantai Land Air-Conditioning Industry Co., Ltd.
Free Member ·1YRS
,
Other

Main Products: 高温水源热泵

Xwboo>Products
Product Categories

Yantai Land Air-Conditioning Industry Co., Ltd.Free·1YRS

  • E-mail

  • Phone

    0535-6726582,6726583

  • Address

    3 Lande Road, Laishan District, Yantai

Contact Now

Energy Tower Heat Pump System

Model
Nature of the Manufacturer
Other
Product Category
Place of Origin
City, Province
Overview
Standard Heat Pump SystemRefrigerating capacity: 266kW~4188kWHeating capacity: 213kW~3232kWHigh temperature Heat Pump SystemRefrigerating capacity: 220kW~1226kWHeating capacity: 251kW~1408kW
Product Details
- Under heating conditions, for standard heat pump system, the highest temperature of outlet water is up to 55℃; for high temperature heat pump system, the highest temperature of outlet water is up to 68℃.
- Take outdoor air as the cold and heat source. The ambient temperature range for standard heat pump system is -15℃~43℃; and that for the high temperature heat pump system is -9℃~43℃.
- Meet the requirements for refrigeration, heating and sanitation hot water for large buildings such as residential area, supermarkets, office buildings, schools, hospitals, hotels, stations, airports, etc.
- Excellent Bitzer semi-hermetic screw compressor.
- Independently developed flooded evaporator improves the heat exchange efficiency by 15% compared with dry type evaporator.
- Independently developed special control device for heat pump features integrated design, powerful functions and stable performance.
- High quality electronic expansion valve and independently developed and manufactured actuator provides high precision control and quick response.
- Color touchscreen interface of humanized design.
- GSM remote monitoring patented technology enables unattended operation through remote control by phone SMS. 
- Ambient temperature and sunlight compensation patented technology enables automatic adjustment of operations according to outdoor weather conditions, which greatly reduces system operation cost.
- Coordinated control of ancillary equipment ensures safe operation of the heat source water system and air conditioner water system.
- All-round protection functions ensure safe and stable system operation.
- The temperature of ambient wet bulb is 7℃ higher than the temperature of outlet water under heating conditions; when the temperature of ambient wet bulb is lower than -6℃, the highest temperature of outlet water is up to 50℃. 
- It is suggested to choose ancillary electric facility with power equal to 1.3 times of the heating input power of the system.
- For special requirements, please inform us before placing the order.