Fire Pump

Model
Nature of the Manufacturer
Other
Product Category
Centrifugal Pump
Place of Origin
City, Province
Overview
A fire pump is a part of a fire sprinkler system's water supply and powered by electric, diesel or steam. The pump intake is either connected to the public underground water supply piping, or a static water source (e.g., tank, reservoir, lake).
Product Details

Fire Pump

Summary
A fire pump is a part of a fire sprinkler system's water supply and powered by electric, diesel or steam. The pump intake is either connected to the public underground water supply piping, or a static water source (e.g., tank, reservoir, lake). The pump provides water flow at a higher pressure to the sprinkler system risers and hose standpipes.
Yonjou can make the fire pump with NFPA20 standard.
Fire pumps function either by an electric motor or a diesel engine, or, occasionally a steam turbine. If the local building code requires power independent of the local electric power grid, a pump using an electric motor may utilize, when connected via a listed transfer switch, the installation of an emergency generator.




Service condition:


Atmosphere

>90kpa

In abnormal condition, engine rated power may lower then normal.
Ensure working safe, a bigger engine required at work is better.
Note: Measurement of engine rated power is tested in following condition.

Atmosphere

=100kPa

Ambient temperature

5-40℃

Ambient temperature

=25℃

Relative air humidity

=30%

Relative air humidity

≤80%

Every 100m altitude higher the rated power of engine drop 3%.

Applicable diesel engine

Engine rated power 10% more then pump absorbed power

Every 5.6'C ambient temperature higher the rated power of engine drop 1%.

Engine real power output=(CA+CT-1)x Rated power




Standard configuration
Water pump: Single stage end-suction centrifugal fire pump, multistage fire pump, single stage double-suction fire pump, submerged fire pump, rotor fire pump, according with GB6245-2006《 Fire pump testing demand and testing method》 and NFPA20(National fire protection association).
Engine: Water cooling engine
1. Single cylinder engine: battery; air, fuel, lubricant filter system; exhaust system with muffler assembly; engine water cooling system; fuel tank; auto start control box(no protection system, manual stop).
2. Multicylinder engine: battery; air、 fuel、 lubricant filter system; exhaust system with muffler assembly; engine water cooling system; fuel tank; engine monitor; PLC editor, auto start control box(normal standard protection system or NFPA20 type).




Specification data:


Type

Size

Flow

Head

Power

End Suction Fire pump

50-200 mm

36.3-400m3/h

5-125 m

0.22-110kW

Multistage Fire Pump

40~300 mm

3.75~850 m3/h

19~816 m

3-1600 kW

Split Case Fire Pump

80-450 mm

14.5~2500m3/h

6.1~200 m

2.2-1800 kW

Submerged fire pump

150-1000 mm

50-8400 m3/h

15-150 m

5.5-2000 kW



29

30

Hot Tags: fire pump, China, manufacturers, suppliers, factory, price, for sale, Mono Screw Pump, double diaphragm pump, Acid Transfer Pump, Horizontal Split Case Pump, Air Driven Diaphragm Pump, Sulfuric Acid Pump