LF55 Series pressure switches is usually used with fluorinated refrigerants to control the pressure of compressor in refrigeration system. It can also used in air and water. Internal Micro-swith ensures reliable switching. It is provided standard Mounting Bracket.
Model Specification
| Model | Adjustable range (Bar) | Differential (Bar) | Factory setting (Bar) | Max working pressure (Bar) | ||||
| Min. | Max. | Min. | Max. | OFF | ON | |||
| LF5502 | -0.5 | 2 | 0.2 | 0.7 | 1 | 0.5 | 16.5 | |
| LF5503 | -0.5 | 3 | 0.35 | 1.5 | 2 | 1 | 16.5 | |
| LF5506 | -0.5 | 6 | 0.6 | 4 | 3 | 2 | 16.5 | |
| LF5506M | -0.5 | 6 | Reset Differential | 3 | Manual Reset | 16.5 | ||
| LF5510 | 1 | 10 | 1 | 3 | 6 | 5 | 16.5 | |
| LF5516 | 5 | 16 | 1 | 4 | 10 | 8 | 33 | |
| LF5520 | 5 | 20 | 2 | 5 | 16 | 14 | 33 | |
| LF5530D | 5 | 30 | 5 | 10 | 20 | 15 | 33 | |
| LF5530 | 8 | 30 | Fixed at 3 to 5 | 20 | 15~17 | 33 | ||
| LF5530M | 8 | 30 | Reset Differential | 20 | Manual Reset | 33 | ||
| Medium | Refrigerant, Air, Water, Oil | |||||||
| Media Temperature | -10°C - 120°C | |||||||
| Connection | M12X1.25, 7/16-20UNF other connection is available on request | |||||||
| Contact Arrangement | SPDT | |||||||
| Electrical Rating: | Non-Inductive: 20A@125VAC,10A@ 250 VAC | |||||||
| Inductive: FLA:15A@ 125VAC,8A@250VAC LRA:72A@ 125VAC,64A@250VAC | ||||||||