Product Name | Addressable Fire Alarm Control Panel | Product number | GS690 |
Certificate | UL | Standard | UL864 |
Power Supply | | | |
Operating voltage | AC(110~220)V,50/60Hz | Mains supply Current Limit | 2.1A |
Mains supply fuse | 4A/AC 250V slow blow(20mm) | Power supply | 3.5A@28.5V |
Standby battery maximum capacity (2xDC 12V) | 12Ah | Maximum battery current draw | 1.2A@maximum operating temperature |
Charging Circuit | 28V,±2% Nominal | Battery fuse | 1A resettable(electronic fuse) |
Battery fault threshold voltage | < DC 20V | Quiescent current | 100mA @ DC28.5V |
Addressable Loops | | | |
Addressable loops | 2 | Number of connected devices per loop | 127 |
Loop current(max) | 100mA @40ohms(max) @24V DC per loop | Loop monitoring | Open, short-circuit and Ground |
Power Limited | | | |
Audio Alarms | | | |
Configurable audio alarm groups(max) | 7 | Non-addressable audio alarm device driver | 220mA (Line Drop: 2.4V) (Total) |
Non-addressable audio alarm end-of-line resistor | 10KΩ | Alarm zone monitoring | Open , Ground, and short-circuit |
Power Limited | | | |
Alarm zone voltage(max) | DC 24V | Current Rating for Regulated,mA | 22 |
Current Rating for Special Applications,mA | 220 | Alarm zone fuse | 1A resettable(electronic fuse) |
24-Aux Output (Use to power Strobes/Horns Only) | | | |
Nominal output voltage, Vdc | 24 | Recorded Voltage range for compatibility, V | 17.2-27.7 |
Maximum circuit output current,A | 1.35 | Current Rating for Regulated, A | 0.135 (max 1 NAC device) |
Current Rating for Special Applications,A | 1.35 (max 10 NAC devices) | Max line Impedance (ohms) | 2 (per loop) |
Ancillary Outputs | | | |
Number of programmable output relays | 3(Power factor 1) | Ancillary fire C/O relay | 2x(1.0A@DC30V) |
Ancillary Inputs | | | |
Evacuation start/stop | Non-latching, voltage-free | | |
Miscellaneous | | | |
Terminal Wiring | 28 -14AWG (0.5~+1.6)mm2 | Operating temperature | (0~+49)℃ |
Operating humidity | (0~93)%RH, Non-condensing | Storage temperature | (-25~+80)℃ |
Storage humidity | (0~98)%RH, Non-condensing | Dimensions(LxWxH) | 440mm*354mm*140.5mm |
Weight (excluding batteries) | ≤9.0kg | Ground Fault Impedance value | 0 ohm |