VCB stands for Vacuum Circuit Breaker. In VCB, the vacuum is used as the arc quenching media.Nowadays, VCB is widely used in high-voltage substationsor power transmission systems due to the advantages, such as strong interruption capacity, long service life, safety and reliability, and high cost performance.VS1 with rated voltage 12KV, as one type of vacuum circuit breaker, is widely applied to places where frequent operations are needed.According to the different installation forms in switchgear, it can be fixed type or handcart type.Handcart type vacuum circuit breakers are usually suitable for KYN28 series cabinets.The fixed type is applicable to XGN series.
WORKING PRINCIPLE
The VCB consists of fixed contact, moving contact and arc shield mounted inside a vacuum interrupter. The movable member is connected to the control mechanism by stainless steel bellows. This enables the permanent sealing of the vacuum chamber so as to eliminate the possibility of the leak.Under normal operating conditions, these contacts remain closed and will not open automatically until and unless the system becomes faulty.When a fault occurs on any part of the system, the trip coils of the breaker get energized. The moving contacts are pulled apart by some mechanism, thus opening the circuit.

TECHNICAL PARAMETERS OF VS1 -12KV INDOOR VCB
Rated voltage | KV | 12 | |||
Maximum working voltage | KV | 12 | |||
Rated Current | A | 630-1250 | 1250-2500 | 1250-3150 | |
Rated short circuit breaking current | KA | 20 | 31.5 | 40 | |
Rated short-circuit switching current | KA | 50 | 80 | 100 | |
Rated peak withstand current | KA | 50 | 80 | 100 | |
4S rated short-circuit withstand current | KA | 20 | 31.5 | 40 | |
Rated Insulation level | Power frequency withstand voltage | KV | 42(fracture 48) | ||
Impulse withstand voltage | KV | 75(fracture 85) | |||
Rated short-circuit current breaking times | Times | 50 | |||
Contact opening distance | mm | 11±1 | |||
Super stroke | mm | 3.5±0.5 | |||
Closing/Opening Time Difference Among Phases | ms | ≤2 | |||
Contact closing bounce time | ms | ≤2 | |||
Average opening speed | m/s | 0.9-1.2 | |||
Average closing speed | m/s | 0.5-0.8 | |||
Tripping Time | Maximum operating voltage | s | ≤0.05 | ||
Minimum operating voltage | s | ≤0.08 | |||