15kV PowerGlide MV Primary UD Cable

People's Cable Group Co., Ltd.

Model
Nature of the Manufacturer
Manufacturer
Product Category
Power Cable
Place of Origin
HeNan, ZhengZhou
15kV PowerGlide MV Primary UD Cable

APPLICATIONS

Predominantly used for primary underground distribution in conduit systems; suitable for use in wet or dry locations, direct burial, underground duct, and where exposed to sunlight. The engineered PowerGlide polyethylene jacket allows the cable to slide through duct with less friction, resulting in longer pulls or longer pushes with less lubricant, or in some cases, no lubricant at all. To be used at 15,000 volts or less and at conductor temperatures not to exceed 90°C for normal operation.


SPECIFICATIONS

15kV PowerGlide MV Primary UD Cable meets or exceeds the following ASTM specifications:

• B-8 Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard or Soft.

• B-230 Aluminum, 1350-H19 Wire for Electrical Purposes.

• B-231 Aluminum 1350 Conductors, Concentric-Lay-Stranded.

• B-609 Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes.

15kV PowerGlide MV Primary UD Cable is manufactured to the latest edition of the following specifications, and in case of specification conflicts, in the order listed:

• ANSI/ICEA S-94-649

• AEIC CS-8


CONSTRUCTION

The phase conductor is concentrically stranded, compressed soft copper or 1350-H16/26 aluminum alloy. The cable is composed of the conductor, covered by a semi-conducting cross-linked polyethylene strand shield, a tree-retardant cross-linked polyethylene primary insulation, and a semi-conducting cross-linked polyethylene insulation shield. Conductors are available with either 99% or 133% insulation levels. A concentric neutral of bare copper wires and an insulating engineered PowerGlide polyethylene jacket are applied over the insulation shield. The cable is identified by surface print on the jacket and with the lightning bolt symbol for supply cables indented in the jacket. A semi-conducting engineered PowerGlide polyethylene jacket is available upon request.


Phase

Conductor


Neutral


Thickness

Per Cond. (mils)



Diameter (mils)




Weight

1000 feet

(lbs.)

Allowable

Ampacities+


Size

(AWG or

kcmil)

Strand-

ing

No.

of

Wires

Size

(AWG)

Approx.

Insul.

Insul.

Shield

Min.

Point

Approx.

Jkt.

Bare

Phase

Cond.

Over

Insul.

Over

Insul.

Shield

Comp.

Cable

Comp.

Cable

Direct

Burial

In

Ducts

ALUMINUM CONDUCTOR - 0.175" INSULATION -99% INSULATION LEVEL














2

7

10

14*

175

30

50

283

678

758

986

470

168*

119*

1/0

19

16

14*

175

30

50

362

758

838

1066

616

218*

155*

2/0

19

20

14*

175

30

50

406

803

883

1111

711

248*

177*

3/0

19

25

14*

175

30

50

456

865

945

1173

840

284*

201*

4/0

19

20

12*

175

30

50

512

908

988

1249

1005

324*

230*

250

37

16

10*

175

30

50

558

963

1043

1346

1213

360*

257*

350

37

18

14**

175

40

50

661

1068

1168

1396

1054

389**

319**

500

37

25

14**

175

40

50

790

1193

1293

1521

1345

468**

384**

750

61

24

12**

175

40

80

968

1383

1483

1798

1940

569**

468**

1000

61

20

10**

175

40

80

1117

1530

1630

1988

2463

642**

542**















COPPER CONDUCTOR - 0.175" INSULATION -99% INSULATION LEVEL














2

7

16

14*

175

30

50

283

678

758

986

684

210*

150*

1

19

20

14*

175

30

50

322

718

798

1026

803

240*

171*

1/0

19

25

14*

175

30

50

362

758

838

1066

951

273*

194*

2/0

19

20

12*

175

30

50

405

800

880

1142

1160

313*

224*

3/0

19

25

12*

175

30

50

456

853

933

1194

1389

358*

255*

4/0

19

20

10*

175

30

50

512

908

988

1291

1716

410*

293*

250

37

24

10*

175

30

50

558

963

1043

1346

2052

446*

322*

350

37

18

12**

175

40

50

661

1068

1168

1429

1963

489**

400**

500

37

26

12**

175

40

50

790

1193

1293

1554

2648

577**

472**

750

61

25

10**

175

40

80

968

1383

1483

1840

3900

649**

532**

+ Ampacities shown assume use of 99% load factor, 60 Hz current, 36" burial depth, 20°C ambient temperature, 90°C conductor temperature, earth RHO 90,

insulation and shield RHO 400.

* Full neutral construction (Ampacities assume- single phase circuit, one cable)

** 1/3 neutral cable (Ampacities assume - three phase circuit, 3 cables triplexed, multi-point grounding per ICEA methods)















Phase

Conductor


Neutral


Thickness

Per Cond. (mils)



Diameter (mils)




Weight

1000 feet

(lbs.)

Allowable

Ampacities+


Size

(AWG or

kcmil)

Strand-

ing

No.

of

Wires

Size

(AWG)

Approx.

Insul.

Insul.

Shield

Min.

Point

Approx.

Jkt.

Bare

Phase

Cond.

Over

Insul.

Over

Insul.

Shield

Comp.

Cable

Comp.

Cable

Direct

Burial

In

Ducts

ALUMINUM CONDUCTOR - 0.220" INSULATION -133% INSULATION LEVEL














2

7

10

14*

220

30

50

283

770

850

1078

530

168*

119*

1/0

19

16

14*

220

30

50

362

850

930

1158

680

218*

155*

2/0

19

20

14*

220

30

50

406

893

973

1201

777

248*

177*

3/0

19

9

14*

220

30

50

456

943

1023

1251

705

284*

201*

4/0

19

20

12*

220

30

50

512

1000

1080

1342

1080

324*

230*

250

37

16

10*

220

40

50

558

1055

1155

1459

1316

360*

257*

350

37

18

14**

220

40

50

661

1158

1258

1486

1136

389**

319**

500

37

25

14**

220

40

50

790

1285

1385

1613

1438

468**

384**

750

61

24

12**

220

40

80

968

1475

1575

1891

2050

569**

468**

1000

61

20

10**

220

55

80

1117

1623

1753

2110

2636

642**

542**















COPPER CONDUCTOR - 0.220" INSULATION -133% INSULATION LEVEL














2

7

16

14*

220

30

50

283

770

850

1078

744

210*

150*

+ Ampacities shown assume use of 99% load factor, 60 Hz current, 36" burial depth, 20°C ambient temperature, 90°C conductor temperature, earth RHO 90,

insulation and shield RHO 400.

* Full neutral construction (Ampacities assume- single phase circuit, one cable)

** 1/3 neutral cable (Ampacities assume - three phase circuit, 3 cables triplexed, multi-point grounding per ICEA methods)















  People’s Cable Group is the developer, manufacturer, sales provider of wires and cables. Established in 1987,the company has five core subsidiaries under the jurisdiction, more than 80 cooperative enterprises, and 1,000 sales branches in China. The company is located in 3 Yongding Road of Zhengzhou Industrial Park, covering a total area of 160,000 square meters. The registered capital is 100 million yuan and the total assets are 350million. People’s cable has the first-class production equipment and the improved detection system domestically, with a total of 305 staff members, 65 of whom are professional and technical experts. As one of the top cable suppliers in China, we are dedicated to the production of high, medium and low voltage wire and cable series. The main products are PVC building wires, PVC and XLPE insulation power cables, rubber, mining and welding cables, ABC cable, bare conductors such as: AAC, AAAC, ACSR, ACSR/AW, AACSR, ACAR and power cable up to 35KV. All our products meet the standards of GB,JB,IEC,BS,DIN,ASTM,JIS,NF,AS/NZS,CSA,GOST etc.We have obtained ISO9001, ISO14001, OHSAS8001,CCC and CE certificates and more than 3000 product specifications have been exported to Southeast Asia, Middle East, Africa, South America and other countries and regions. Through many years of ongoing effort and endeavors, we have gained cooperation and widespread compliments from clients all over the world because of our superior quality, reasonable price and attentive services. We look forward to your contact and visit.