It is used for return circuit of class 1E category K3 outside security housing of nuclear reactor in nuclear power station.
Executive Standard:
As the enterprise’s enterprise ( with reference to “Design & Manufacturing Regulation on Electric Devices of Nuclear Island of RCC-E Reactor in Nuclear Power Station” of France & “ technical Specification of 0.6/1kV Control Cable” by No.2 Research & Design Institute of Nuclear Industry)
Main Features:
Main Technical Parameters:
| Nominal cross section areas (mm2) | Pieces/ Diameter of Single Piec | D.C. Conductor Resistance (20℃)≤W/km | ||
| Category 1 | Category 2 | Non-plated | Plated | |
| 1.0 | 1/1.13 | 7/0.43 | 18.1 | 18.2 |
| 1.5 | 1/1.38 | 7/0.52 | 12.1 | 12.2 |
| 2.5 | 1/1.78 | 7/0.68 | 7.41 | 7.56 |
| Conductor Diameter (mm) | D.C. Conductor Resistance(20℃) ≤W/km | |
| Non-plated | plated | |
| 0.8 | 36.0 | 36.7 |
| 1.0 | 23.5 | 23.8 |
| Nominal cross section area(mm2) | D.C. Conductor Resistance (20℃) ≤W/km | |
| Single Strand | Multi strand | |
| 1.0 | 1/1.13 | 7/0.43 |
| 1.5 | 1/1.37 | 7/0.52 |
| 2.5 | 1/1.76 | 19/0.41 |
(1). Power Cable, Control Cable: 3.5kV/5min
(2) Instrument Cable, Compensational Cable: between insulated cores:2.5kV/5min between insulated core and shielding: 1.5kV/5min
4. Long-term Thermal Cycle Test:
(1). Test Time 5000h
(2). Test Voltage 2kV
5. Flame-retardant Performance:
5.1 Vertical Firing Test of Single Insulated Core Flame Supply Time: 15 S Flame-free Time: 15 S The damaged area should be less than 25% after 5 mins of repetition
5.2 Cable Firing Test in Bundle (Category B): damaged Cable length≤2.5m
5.3 Smoke Density Test (Light Penetration Rate):
5.4 The emitted gas corrosion in firing of sheath material: PH value≥4.3; Electric Conductivity≤10ms/mm
Working conditions: