2 Wire 20mA Differential Pressure Transducers 800Ω External Load

Changsha Taihe Electronic Equipment Co., Ltd.

Model
Nature of the Manufacturer
Manufacturer
Product Category
UHF RFID Reader
Place of Origin
HuNan, ChangSha

Changsha Taihe Electronic Equipment Co., Ltd.

Contact

Mr. William

Phone

Fax

86-731-85665625
2 Wire 20mA Differential Pressure Transducers 800Ω External Load

2 Wire 20mA Differential Pressure Transducers 800Ω External Load

Description
Operating:-18 ~ +65°CStorage:-54 ~ +82°C
Electrical Connection:PG-9 Cable Locking DevicePressure Fitting:3/16” O.D.Barbed Brass Pressure Fitting For 1/4” Push-on Tubing
Zero And Span Adjustments:Accessible Inside Of Case
High Light:

20mA Differential Pressure Transducers

,

800Ω Differential Pressure Transducers

,

20mA Differential Pressure Device

PPM-WCY61-P050A Infectious Disease Room Differential Pressure Transducer

Product Introduction:
It is consisted of stainless steel diaphragm and gilt ceramic fixed electrode. When pressure changes, the space between two electrode pad also changes, which result in the change in capacitance value. And then the unique detective circuit will transfer the change of capacitance value into linear DC signal.
inherit the consistent characteristics of high-precision, rapid-response and low range. Considering the requirement of pharmaceutical plant and clean room for low differential pressure transducer, on-site LCD is developed and accessories with non-dust accumulation surface are added to meet the industrial applying requirement; so it is a desire choice for pharmaceutical plant, clean rooms of electronic factory and no-dust laboratory. low differential pressure transducer can measures pressure difference or gauge pressure (static pressure) and can choose the output signal in 4-20mA, 0-5VDC or 0-10VDC. transducer has conducted temperature compensation with an exciting voltage of 24VDC and can choose 24VAC as power supply for voltage signal product. The minimum measurement of Model 261C range is at 0 ~ 25Pa with an accuracy of ±1%FS at room temperature; The unit are temperature compensated to ±0.06%FS/°C thermal error over the temperature range +5 to +65°C.

Applications :
Pharmaceutical Plant
Clean Room
Bio-Safety Labs
Infectious Disease Room
Stairwell Fire and Smoke Protection

Technical Parameters :

Parameter

Accuracy RSS* (constant temperature)

Standard

±1.0%FS

Option

±0.4%FS

Option

±0.25%FS

Non-Linearity, BFSL±0.98%FS±0.33%FS±0.20%FS
Non-Repeatability±0.05%FS±0.05%FS±0.05%FS
Hysteresis±0.1%FS±0.1%FS±0.1%FS
Compensation range-5 ~ +65°C (no LCD display)
Zero/ Span shift<0.06%FS/°C
Max. linear pressure70KPa
OverpressureUp to 70KPa in positive or negative direction
Warm up drif±0.1% FS

Error caused by installing position

(the nominal position in factory is in vertical position)

RangeZero Drift (%FS/G)
0-25Pa2.1
0-250Pa0.22
0-1250Pa0.14
0-7500Pa0.06

* RSS of non-linear, hysteresis and non-repeatability


Environmental and Physical Data

Operating-18 ~ +65°C
Storage-54 ~ +82°C
Electrical connectionPG-9 cable locking device
Pressure Fitting

3/16” O.D.Barbed Brass pressure fitting for

1/4” push-on tubing

Zero and Span adjustmentsAccessible Inside of Case
Pressure mediumAir or similar non-conducting gas
EnclosureCast aluminum
Weight347.5g
Mountingφ3mm bolt or countersunk head bolt (option)


Electrical Data (Voltage)

Circuit3-Wire (Com, Exc, Out)
Exciting

9 ~ 30VAC/12 ~ 42VDC (0 ~ 5VDC output);

12 ~ 30VAC/13 ~ 42VDC (0 ~ 10VDC output)

Output*0-5VDC/0-10VDC**
Bidirectional Output at Zero2.5VDC(0-5VDC) / 5VDC(0-10VDC)
Output Impedance100Ω

*Calibrated into a 50KΩ load, operable into a 5KΩor greater.
** Zero output factory set to within ±50mV (± 25mV for option accuracy)
** Span(Full scale) output factory set to within ±50mV (± 25mV for option accuracy)

Electrical Data (Current)

Circuit2-Wire Protected from Miswiring
Full scale output*20mA±0.16mA
Zero point output*4mA±0.16mA
Bidirectional Output at Zero12mA
External load0-800Ω
Min. supply voltage9+0.02×(Resistance of receiver plus line)VDC
Max. supply voltage30+0.004 × (Resistance of receiver plus line)VDC

* Calibrated with a 24VDC loop supply voltage and a 250 ohm load

Definition of wiring:
2 Wire 20mA Differential Pressure Transducers 800Ω External Load 0
Dimensions in mm :
2 Wire 20mA Differential Pressure Transducers 800Ω External Load 1