Specifications | Order No. |
| CTSC-200 CPU224I,24VDC Power Supply,14DI*10DO,Transistor output,0.75A,16KB Program Memory/108KB Data Memory,1*PPI,1*FPORT,1*Ethernet port. | CTS7 214-1AD41-0X24 |
Performnce Parameters:
Physical Features | ||
Dimension(W×H×D) | 137×80×62mm | |
Power dissipation | 7W | |
Memory Features | ||
Program memory | 12KB,can be expand to 16K | |
Data memory | 8KB,can be expand to 108KB | |
Power-off protection time(super capacitor ) | 112 hours(typical) | |
External battery (Optional) | 200 days(typical) | |
General Features | ||
| Counters total | 256(super capacitor backup) | |
Internal memory bits | 256(super capacitor backup) | |
Stored permanently on power down | 112 hours(typical) | |
Time Interrupts | 2 with 1ms resolution | |
Edge Interrupts | 4 rising edges and/ or 4 falling edges | |
Analog adjustment | 2 with 8 resolution | |
Boolean execution speed | 0.15µs | |
Float execution speed | 8µs | |
Clock | Embedded | |
Rated voltage | 220VAC | |
Power supply Native and extended bus+5V +5V +24V | 1A 10mA 300mA | |
Integrated Communication Function | ||
Communication port | 2 communication ports ,PORT0:PPI/Free port,RS485;FPORT1:PPI/freeport, RS485 PWL | |
PPI baud rates(baud) | 9.6k、19.2k and187.5k | |
Freeport baud rates (baud) | 1.2k ~ 115.2k | |
Maximum cable length per segment Isolated repeater applied Isolated repeater unapplied | When it is 1000 m, baud rate is 187.5k; when it is 1200 m, 38.4k. 50 m | |
Maximum number of stations | 32 stations per segment,126 stations per network | |
Maximum number of masters | 32 | |
Point to point (PPI Master Mode) | Yes(NWTR/NETW), 8 total, 2 reserved | |
Ethernet Function | ||
Communication port | 1 Ethernet port | |
Communication standard | IEEE802.3 standard | |
Communication speed | 10Mbps and 100Mbps self-adaption | |
Adaptive cross connection | Non support | |
Interface to industrial Ethernet(10/100Mbps) | RJ45 | |
Protocol type | UDP/TCP protocol Support MICO Ethernet programming, support Ethernet communication between PLC. | |
Collocation method | Support the upper computer through the Ethernet port search PLC, support the mouth download system configuration. | |
Max Connections | Each PLC supports up to 8 UDP connections and up to 4 TCP connections. | |
The maximum number of IT connections | 8 UDP_PPI connections, with 4 master stations and 4 slave stations. 4 ModBus_TCP connections, 2 master stations and 2 slave stations. | |
User data number | Up to 200 bytes are used for TCP/IP transmission. Up to 240 bytes are used for ModBus_TCP transport. | |
Port | local:1~65535 remote server:8888 | |
Boot time or restart time after reset | 3 seconds | |
Indicator lamp | Green RMC indicator: on: remote control in effect, off: remote control out Green Ethernet indicator: on: connection, flicker: transmission; out: not connected | |
Maximum cable length | 100m | |
Isolation | Communication port | |
I/O Feature | ||
Number of integrated digital inputs | 14 | |
Input type | Sink/Source | |
Number of integrated digital outputs | 10 | |
Output type | Solid-MOSFET | |
Digital I/O mapping domain | 128DI/128DQ | |
Analog I/O mapping domain | 32AI/32AQ | |
Maximum number of expandable I/O modules | 7 | |
Pulse catch inputs | 14 | |
High-speed counters Total Uniphase counters Bi-phase counters | 6 6×50KHz 4×30KHz | |
Digital Input Features | ||
Number of integrated digital input | 14 | |
Input type | Sink/ Source | |
Rated voltage | 24V DC | |
Input voltage range | 20.4~28.8V DC | |
Surge voltage | 35V DC,continuously 0.5s | |
Logical 1 Signal (minimum) Logical 0 Signal (Maximum ) | 15 VDC,2.5mA 5 VDC,1mA | |
Connect 2 wire proximity switch sensor (BERO) Allowable leakage current (maximum) |
1mA | |
Input filter | support 0.2ms,0.4ms,0.8ms,1.6ms,3.2ms,6.4ms,12.8ms,default 6.4ms | |
Isolation(field side to logical circuit) Isolation groups | 500V AC,1min | |
Simultaneous input | 36 | |
Maximum cable length Shielded Unshielded | 500 M(standard input) 50 M(high-speed counters input) 300 M(standard input) | |
Digital Output Features | |
Number of integrated digital output | 10 |
Output type | Solid-MOSFET,source |
Rated voltage | 24VDC |
Output voltage range | 20.4~28.8VDC |
Logical 1 Signal (minimum) | 20VDC,max current |
Logical 0 Signal (Maximum) | 0.1V DC,10KΩ load |
Rated current per point | 0.75A |
Rated current for each common point | 6A |
Leakage current (maximum) | 10uA |
Surge current(Maximum) | 8A,100ms |
Lamp load (maximum) | 5W |
On resistance (contact) | Typical 0.3Ω,max 0.6Ω |
Isolation(field side to logical circuit) | 500VAC,1mins |
Delay | Off to on:2us(Q0.0, Q0.1),---15us on to off:10us(Q0.0, Q0.1),---130u |
High speed pulse output Maximum frequency | Motion control library instruction: 2* 50KHz Pulse (Q0.0,Q0.1),Dir (Q0.2,Q0.3) PTO/PWM: 2 *20KHz (Q0.0,Q0.1) |
Simultaneous input | 10 |
Parallel output | Only when the outputs are in the same group |
Maximum cable length Shielded Unshielded | 500m 150m |
Wiring diagram

RS485 communication port definition
Connector | Pin | PORT1(RS485) | PORT0(RS485) |
| 1 | Shell Grounded | Shell Grounded |
2 | +24V Grounded | +24V Grounded | |
3 | RS485+signal B | RS485+signal B | |
4 | Send the application | Send the application | |
5 | +5V Grounded | +5V Grounded | |
6 | +5V,100Ω | +5V,100Ω | |
7 | +24V | +24V | |
8 | RS485-signal A | RS485-signal A | |
9 | NC | NC | |
Shell | Shell Grounded | Shell Grounded |
Ethernet port definition
RJ45 port | PIN | Signal | Signal definition |
| 1 | TX+ | Data sending to the positive end |
2 | TX- | Data sending to the negative end | |
3 | RX+ | Data receiving from the positive end | |
4 | TERM | -- | |
5 | TERM | -- | |
6 | RX- | Data receiving from the negative end | |
7 | TERM | -- | |
8 | TERM | -- |