6-36kv XLPE Insulated Armored

HENAN BAIFA ELECTRIC POWER CO., Ltd.

Model
Nature of the Manufacturer
Other
Product Category
Power Cable
Place of Origin
,
6-36kv XLPE Insulated Armored

Standard
Cables will be produced as per Chinese National Standard GB/T12706.2-12706.3 equivalent to IEC 60502

Application
This product is suitable for using in rated voltage from 6/6kV to 26/35kV system transmission and distribution lines. Based on different sheath structures,

 it can be used for laying in the air and underground

Description and Installation Place

Description

Installation Place

XLPE Insulated, PVC Sheathed Power Cable

Laid in indoor, outdoor, tunnels, cable canals, 

reinforced concrete pipelines and loose soil. 

Cable should not bear outer mechanic force, 

but can bear a certain tractional force.

XLPE Insulated, Steel Tape Armored and PVC Sheathed Power Cable.

Laid underground. Cable can bear outer mechanic force, 

but should not bear large tractional force.

XLPE Insulated ,fine Steel Wire Armored and PVC Sheathed Power Cable

Laid in indoor, tunnels and mines. Cable can bear outer mechanic force 

and fairly large tractional force.

XLPE Insulated, thick Steel Wire Armored and PVC Sheathed Power Cable.

Laid in vertical section, indoor, tunnels and mines. 

Cable can bear outer mechanic force and very large tractional force.

1)3.6/6(7.2)kV, 3.6/6.6(7.2)kV Single Core Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable

Normal 

Cross Section 

of Conductor

Normal 

Diameter of 

Conductor

Normal 

Thickness of 

Insulation

Normal 

Thickness of

Copper Tape

Normal 

Thickness of 

Outer Sheath

Approx.

Overall Dia.

Approx. Net Weight

Max. D.C. 

Resistance of 

Conductor at 20℃

Al 

Conductor

Cu 

Conductor

Al

Conductor

Cu 

Conductor

mm2

mm

mm

mm

mm

mm

kg/m

kg/m

Ω/km

Ω/km

25

6.0

2.5

0.12

1.5

17.6

0.34

0.49

1.2000

0.7270

35

7.0

2.5

0.12

1.5

18.5

0.39

0.60

0.8680

0.5240

50

8.3

2.5

0.12

1.6

20.0

0.46

0.74

0.6410

0.3870

70

9.7

2.5

0.12

1.6

21.5

0.55

0.96

0.4430

0.2680

95

11.3

2.5

0.12

1.7

23.3

0.66

1.23

0.3200

0.1930

120

13

2.5

0.12

1.7

24.8

0.77

1.48

0.2530

0.1530

150

14.6

2.5

0.12

1.8

26.4

0.87

1.77

0.2060

0.1240

185

15.9

2.5

0.12

1.8

28.1

1.01

2.13

0.1640

0.0991

240

18.3

2.6

0.12

1.9

30.9

1.23

2.71

0.1250

0.0754

300

20.4

2.8

0.12

2.0

33.6

1.48

3.32

0.1000

0.0601

400

23.2

3.0

0.12

2.1

37.0

1.81

4.16

0.0778

0.0470

500

26.4

3.2

0.12

2.2

41.1

2.24

5.27

0.0605

0.0366

630

30.1

3.2

0.12

2.3

45.0

2.73

6.62

0.0469

0.0283


2)6/10(12)kV,6.35/11(12)kV Single Core Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable

Normal 

Cross Section 

of Conductor

Normal 

Diameter of 

Conductor

Normal 

Thickness of 

Insulation

Normal 

Thickness of

Copper Tape

Normal 

Thickness of 

Outer Sheath

Approx.

Overall Dia.

Approx. Net Weight

Max. D.C. 

Resistance of 

Conductor at 20℃

Al 

Conductor

Cu 

Conductor

Al 

Conductor

Cu 

Conductor

mm2

mm

mm

mm

mm

mm

kg/m

kg/m

Ω/km

Ω/km

25

6.0

3.4

0.12

1.5

19.4

0.40

0.55

1.2000

0.7270

35

6.9

3.4

0.12

1.6

20.5

0.45

0.66

0.8680

0.5240

50

8.2

3.4

0.12

1.6

21.8

0.52

0.80

0.6410

0.3870

70

9.7

3.4

0.12

1.7

23.5

0.62

1.03

0.4430

0.2680

95

11.3

3.4

0.12

1.7

25.1

0.73

1.30

0.3200

0.1930

120

12.8

3.4

0.12

1.8

26.8

0.85

1.56

0.2530

0.1530

150

14.2

3.4

0.12

1.8

28.2

0.95

1.85

0.2060

0.1240

185

15.9

3.4

0.12

1.9

30.1

1.10

2.22

0.1640

0.0991

240

18.3

3.4

0.12

2.0

32.7

1.33

2.80

0.1250

0.0754

300

20.4

3.4

0.12

2.0

34.8

1.54

3.39

0.1000

0.0601

400

23.2

3.4

0.12

2.2

38.0

1.87

4.22

0.0778

0.0470

500

26.4

3.4

0.12

2.2

41.5

2.26

5.29

0.0605

0.0366

630

30.1

3.4

0.12

2.4

45.6

2.78

6.67

0.0469

0.0283


3)8.7/10(15)kV Single Core Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable

Normal 

Cross Section of 

Conductor

Normal 

Diameter of 

Conductor

Normal 

Thickness of 

Insulation

Normal 

Thickness of

Copper Tape

Normal 

Thickness of 

Outer Sheath

Approx.

Overall Dia.

Approx. Net Weight

Max. D.C. 

Resistance of 

Conductor at 20℃

Al 

Conductor

Cu 

Conductor

Al

Conductor

Cu

Conductor

mm2

mm

mm

mm

mm

mm

kg/m

kg/m

Ω/km

Ω/km

25

6.0

4.5

0.12

1.6

21.8

0.48

0.63

1.2000

0.7270

35

6.9

4.5

0.12

1.7

22.9

0.54

0.75

0.8680

0.5240

50

8.2

4.5

0.12

1.7

24.2

0.61

0.89

0.6410

0.3870

70

9.7

4.5

0.12

1.8

25.9

0.72

1.13

0.4430

0.2680

95

11.3

4.5

0.12

1.8

27.5

0.84

1.40

0.3200

0.1930

120

12.8

4.5

0.12

1.9

29.2

0.96

1.67

0.2530

0.1530

150

14.2

4.5

0.12

1.9

30.6

1.06

1.96

0.2060

0.1240

185

15.9

4.5

0.12

2.0

32.5

1.22

2.34

0.1640

0.0991

240

18.3

4.5

0.12

2.1

35.1

1.46

2.93

0.1250

0.0754

300

20.4

4.5

0.12

2.1

37.2

1.68

3.52

0.1000

0.0601

400

23.2

4.5

0.12

2.2

40.2

2.00

4.35

0.0778

0.0470

500

26.4

4.5

0.12

2.3

43.9

2.43

5.45

0.0605

0.0366

630

30.1

4.5

0.12

2.4

47.8

2.93

6.83

0.0469

0.0283


4)12/20(24)kV, 12.7/22(24)kV Single Core Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable

Normal 

Cross Section 

of Conductor

Normal 

Diameter of 

Conductor

Normal 

Thickness of 

Insulation

Normal 

Thickness of

Copper Tape

Normal 

Thickness of 

Outer Sheath

Approx.

Overall Dia.

Approx. Net Weight

Max. D.C. 

Resistance of 

Conductor at 20℃

Al 

Conductor

Cu 

Conductor

Al

Conductor

Cu

Conductor

mm2

mm

mm

mm

mm

mm

kg/m

kg/m

Ω/km

Ω/km

25

 

 

 

 

 

 

 

 

 

35

6.9

5.5

0.12

1.7

24.9

0.62

0.83

0.8680

0.5240

50

8.2

5.5

0.12

1.8

26.4

0.70

0.98

0.6410

0.3870

70

9.7

5.5

0.12

1.8

27.9

0.80

1.21

0.4430

0.2680

95

11.3

5.5

0.12

1.9

29.7

0.94

1.50

0.3200

0.1930

120

12.8

5.5

0.12

1.9

31.2

1.05

1.77

0.2530

0.1530

150

14.2

5.5

0.12

2.0

32.8

1.17

2.07

0.2060

0.1240

185

15.9

5.5

0.12

2.0

34.5

1.33

2.45

0.1640

0.0991

240

18.3

5.5

0.12

2.1

37.1

1.57

3.04

0.1250

0.0754

300

20.4

5.5

0.12

2.2

39.4

1.81

3.66

0.1000

0.0601

400

23.2

5.5

0.12

2.3

42.4

2.14

4.49

0.0778

0.0470

500

26.4

5.5

0.12

2.4

46.1

2.58

5.61

0.0605

0.0366

630

30.1

5.5

0.12

2.4

49.8

3.10

6.99

0.0469

0.0283


5)18/30(36)kV,19/33(36)kV Single Core Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable

Normal 

Cross Section 

of Conductor

Normal 

Diameter of 

Conductor

Normal 

Thickness of 

Insulation

Normal 

Thickness of

Copper Tape

Normal 

Thickness of 

Outer Sheath

Approx.

Overall Dia.

Approx. Net Weight

Max. D.C. 

Resistance of 

Conductor at 20℃

Al 

Conductor

Cu 

Conductor

Al

Conductor

Cu

Conductor

mm2

mm

mm

mm

mm

mm

kg/m

kg/m

Ω/km

Ω/km

25

 

 

 

 

 

 

 

 

 

35

 

 

 

 

 

 

 

 

 

50

8.2

8.0

0.12

2.0

31.8

0.95

1.23

0.6410

0.3870

70

9.7

8.0

0.12

2.0

33.3

1.07

1.47

0.4430

0.2680

95

11.3

8.0

0.12

2.1

35.1

1.21

1.78

0.3200

0.1930

120

12.8

8.0

0.12

2.1

36.6

1.34

2.05

0.2530

0.1530

150

14.2

8.0

0.12

2.2

38.2

1.47

2.37

0.2060

0.1240

185

15.9

8.0

0.12

2.2

39.9

1.64

2.76

0.1640

0.0991

240

18.3

8.0

0.12

2.3

42.5

1.90

3.37

0.1250

0.0754

300

20.4

8.0

0.12

2.4

44.8

2.16

4.01

0.1000

0.0601

400

23.2

8.0

0.12

2.4

47.6

2.52

4.87

0.0778

0.0470

500

26.4

8.0

0.12

2.5

51.3

2.98

6.01

0.0605

0.0366

630

30.1

8.0

0.12

2.6

55.2

3.54

7.43

0.0469

0.0283


6)3.6/6(7.2)kV,3.6/6.6(7.2)kV Three Cores Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable

Normal 

Cross Section 

of Conductor

Normal 

Diameter of 

Conductor

Normal 

Thickness of 

Insulation

Normal 

Thickness of

Copper Tape

Normal 

Thickness of 

Outer Sheath

Approx.

Overall Dia.

Approx. Net Weight

Max. D.C. 

Resistance of 

Conductor at 20℃

Al 

Conductor

Cu 

Conductor

Al

Conductor

Cu

Conductor

mm2

mm

mm

mm

mm

mm

kg/m

kg/m

Ω/km

Ω/km

25

6.0

2.5

0.1

2.0

34.6

1.13

1.58

1.2000

0.7270

35

6.9

2.5

0.1

2.1

36.8

1.29

1.92

0.8680

0.5240

50

8.2

2.5

0.1

2.2

39.8

1.51

2.36

0.6410

0.3870

70

9.7

2.5

0.1

2.3

43.2

1.81

3.04

0.4430

0.2680

95

11.3

2.5

0.1

2.4

46.9

2.17

3.87

0.3200

0.1930

120

12.8

2.5

0.1

2.4

50.1

2.53

4.69

0.2530

0.1530

150

14.2

2.5

0.1

2.5

53.3

2.90

5.60

0.2060

0.1240

185

15.9

2.5

0.1

2.6

57.2

3.40

6.77

0.1640

0.0991

240

18.3

2.6

0.1

2.8

63.2

4.12

8.55

0.1250

0.0754

300

20.4

2.8

0.1

3.0

69.0

4.89

10.46

0.1000

0.0601

400

23.2

3.0

0.1

3.4

76.7

6.10

13.18

0.0778

0.0470

500

26.4

3.2

0.1

3.6

85.7

8.10

16.55

0.0605

0.0366


7) 6/10(12)kV,6.35/11(12)kV Three Cores Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable

Normal 

Cross Section of 

Conductor

Normal 

Diameter of 

Conductor

Normal 

Thickness of 

Insulation

Normal 

Thickness of

Copper Tape

Normal 

Thickness of 

Outer Sheath

Approx.
Overall Dia.

Approx. Net Weight

Max. D.C. 

Resistance of 

Conductor at 20℃

Al 

Conductor

Cu 

Conductor

Al

Conductor

Cu

Conductor

mm2

mm

mm

mm

mm

mm

kg/m

kg/m

Ω/km

Ω/km

25

6.0

3.4

0.1

2.1

38.7

1.30

1.75

1.2000

0.7270

35

6.9

3.4

0.1

2.2

40.9

1.47

2.22

0.8680

0.5240

50

8.2

3.4

0.1

2.3

43.9

1.70

2.50

0.6410

0.3870

70

9.7

3.4

0.1

2.4

47.3

2.02

3.25

0.4430

0.2680

95

11.3

3.4

0.1

2.5

51.0

2.42

4.12

0.3200

0.1930

120

12.8

3.4

0.1

2.6

54.4

2.79

4.95

0.2530

0.1530

150

14.2

3.4

0.1

2.7

57.6

3.17

5.87

0.2060

0.1240

185

15.9

3.4

0.1

2.8

61.5

3.69

7.06

0.1640

0.0991

240

18.3

3.4

0.1

2.9

66.9

4.38

8.82

0.1250

0.0754

300

20.4

3.4

0.1

3.1

71.8

5.11

10.68

0.1000

0.0601

400

23.2

3.4

0.1

3.3

78.3

6.24

13.32

0.0778

0.0470

500

26.4

3.4

0.1

3.5

86.4

7.63

16.50

0.0605

0.0366


8)8.7/10(15)kV Three Cores Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable

Normal 

Cross Section 

of Conductor

Normal 

Diameter of 

Conductor

Normal 

Thickness of 

Insulation

Normal 

Thickness of

Copper Tape

Normal 

Thickness of 

Outer Sheath

Approx.

Overall Dia.

Approx. Net Weight

Max. D.C. 

Resistance of 

Conductor at 20℃

Al 

Conductor

Cu 

Conductor

Al

Conductor

 

Cu

Conductor

mm2

mm

mm

mm

mm

mm

kg/m

kg/m

Ω/km

Ω/km

25

6.0

4.5

0.1

2.3

43.9

1.57

2.02

0.9270

0.7270

35

6.9

4.5

0.1

2.4

46.0

1.75

2.38

0.6680

0.5240

50

8.2

4.5

0.1

2.4

48.8

2.00

2.85

0.4936

0.3870

70

9.7

4.5

0.1

2.5

52.3

2.34

3.57

0.3420

0.2680

95

11.3

4.5

0.1

2.6

55.9

2.75

4.45

0.2464

0.1930

120

12.8

4.5

0.1

2.7

59.4

3.16

5.32

0.1955

0.1530

150

14.2

4.5

0.1

2.8

62.6

3.57

6.27

0.1587

0.1240

185

15.9

4.5

0.1

2.9

66.4

4.07

7.45

0.1271

0.0991

240

18.3

4.5

0.1

3.1

72.0

4.82

9.25

0.0976

0.0754

300

20.4

4.5

0.1

3.3

77.0

5.71

11.28

0.0778

0.0601

400

23.2

4.5

0.1

3.4

83.2

6.78

13.86

0.0615

0.0470

500

26.4

4.5

0.1

3.5

91.1

8.20

17.32

0.0487

0.0366


9)12/20(24)kV, 12.7/22(24)kV Three Cores Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable

Normal 

Cross Section 

of Conductor

Normal 

Diameter of 

Conductor

Normal 

Thickness of 

Insulation

Normal 

Thickness of

Copper Tape

Normal 

Thickness of 

Outer Sheath

Approx.

Overall Dia.

Approx. Net Weight

Max. D.C. 

Resistance of 

Conductor at 20℃

Al 

Conductor

Cu 

Conductor

Al

Conductor

 

Cu

Conductor

mm2

mm

mm

mm2

mm

mm

kg/m

kg/m

Ω/km

Ω/km

25

 -

 

 

 

 

 

 

 

 

35

6.9

5.5

0.1

2.4

50.3

2.00

2.63

0.8680

0.6680

50

8.2

5.5

0.1

2.5

53.3

2.26

3.11

0.6410

0.4936

70

9.7

5.5

0.1

2.6

56.8

2.62

3.85

0.4430

0.3420

95

11.3

5.5

0.1

2.8

60.6

3.07

4.77

0.3200

0.2464

120

12.8

5.5

0.1

2.9

64.1

3.49

5.65

0.2530

0.1955

150

14.2

5.5

0.1

3.0

67.3

3.91

6.61

0.2060

0.1587

185

15.9

5.5

0.1

3.1

71.2

4.44

7.81

0.1640

0.1271

240

18.3

5.5

0.1

3.3

76.8

5.21

9.64

0.1250

0.0976

300

20.4

5.5

0.1

3.3

81.3

6.10

11.66

0.1000

0.0778

400

23.2

5.5

0.1

3.5

87.7

7.20

14.28

0.0778

0.0615

500

26.4

5.5

0.1

3.8

96.0

9.15

17.80

0.0605

0.0487


10)18/30(36)kV,19/33(36)kV Three Cores Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable

Normal 

Cross Section 

of Conductor

Normal 

Diameter of 

Conductor

Normal 

Thickness of 

Insulation

Normal 

Thickness of

Copper Tape

Normal 

Thickness of 

Outer Sheath

Approx.

Overall Dia.

Approx. Net Weight

Max. D.C. 

Resistance of 

Conductor at 20℃

Al 

Conductor

Cu 

Conductor

Al

Conductor

Cu

Conductor

mm2

mm

mm

mm

mm

mm

kg/m

kg/m

Ω/km

Ω/km

25

 

 

 

 

 

 

 

 

 

35

 

 

 

 

 

 

 

 

 

50

8.2

8.0

0.1

2.9

64.9

3.02

3.87

0.6410

0.4936

70

9.7

8.0

0.1

3.0

68.4

3.42

4.65

0.4430

0.3420

95

11.3

8.0

0.1

3.1

72.0

3.89

5.59

0.3200

0.2464

120

12.8

8.0

0.1

3.3

75.7

4.39

6.54

0.2530

0.1955

150

14.2

8.0

0.1

3.3

78.7

4.85

7.55

0.2060

0.1587

185

15.9

8.0

0.1

3.4

82.6

5.42

8.79

0.1640

0.1271

240

18.3

8.0

0.1

3.5

88.0

6.22

10.66

0.1250

0.0976

300

20.4

8.0

0.1

3.7

92.9

7.20

12.77

0.1000

0.0778

400

23.2

8.0

0.1

3.9

99.3

8.38

15.46

0.0778

0.0615

500

26.4

8.0

0.1

4.2

107.6

10.15

18.85

0.0605

0.0487


11)3.6/6(7.2)kV,3.6/6.6(7.2)kV Three Cores Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable

No.X Nominal 

Cross Section 

of Conductor

Nominal 

Diameter of 

Conductor

Nominal 

Thickness of 

Insulation

Nominal 

Thickness of 

Copper Tape 

Screen

Nominal 

Thickness of 

Inner Sheath

Nominal 

Thickness of 

Steel Tape 

Armouring

Nominal 

Thickness of 

PVC Sheath

Approx. 

Overall 

Diameter

Approx. Weight

Al

Conductor

Cu

Conductor

No. X mm2

mm

mm

mm

mm

mm

mm

mm

kg/m

kg/m

3 X 25

6.0

2.5

0.1

1.2

0.2

1.9

37.9

1.87

2.32

3 X 35

6.9

2.5

0.1

1.3

0.5

2.0

41.5

2.10

2.73

3 X50

8.2

2.5

0.1

1.3

0.5

2.0

44.3

2.37

3.22

3 X 70

9.7

2.5

0.1

1.4

0.5

2.1

47.9

2.77

4.00

3 X 95

11.3

2.5

0.1

1.4

0.5

2.2

51.6

3.21

4.91

3 X 120

12.8

2.5

0.1

1.5

0.5

2.4

55.4

3.69

5.84

3 X 150

14.2

2.5

0.1

1.5

0.5

2.5

58.6

4.15

6.85

3 X 185

15.9

2.5

0.1

1.5

0.5

2.6

62.5

4.73

8.11

3 X 240

18.3

2.6

0.1

1.6

0.5

2.7

68.5

5.62

10.05

3 X 300

20.4

2.8

0.1

1.7

0.5

2.9

74.5

6.55

12.11

3 X 400

23.2

3.0

0.1

1.9

0.8

3.2

83.6

8.78

15.86

3 X 500

26.4

3.2

0.1

2.1

0.8

3.4

93.0

10.52

18.85


12)6/10(12)kV,6.35/11(12)kV Three Cores Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable

No.X Nominal 

Cross Section 

of Conductor

Nominal 

Diameter of 

Conductor

Nominal 

Thickness of 

Insulation

Nominal 

Thickness of 

Copper Tape 

Screen

Nominal 

Thickness of 

Inner Sheath

Nominal 

Thickness of 

Steel Tape 

Armouring

Nominal 

Thickness of 

PVC Sheath

Approx. 

Overall 

Diameter

Approx. Weight

Al

Conductor

Cu

Conductor

No. X mm2

mm

mm

mm

mm

mm

mm

mm

kg/m

kg/m

3 X 25

6.0

3.4

0.1

1.3

0.5

2.0

43.4

2.16

2.61

3 X 35

6.9

3.4

0.1

1.3

0.5

2.0

45.4

2.36

2.99

3 X50

8.2

3.4

0.1

1.4

0.5

2.2

48.8

2.69

3.54

3 X 70

9.7

3.4

0.1

1.5

0.5

2.3

52.4

3.10

4.33

3 X 95

11.3

3.4

0.1

1.5

0.5

2.4

56.1

3.56

5.26

3 X 120

12.8

3.4

0.1

1.5

0.5

2.5

59.5

4.04

6.19

3 X 150

14.2

3.4

0.1

1.5

0.5

2.6

62.7

4.49

7.19

3 X 185

15.9

3.4

0.1

1.6

0.5

2.6

66.6

5.12

8.49

3 X 240

18.3

3.4

0.1

1.7

0.5

2.8

72.4

5.99

10.42

3 X 300

20.4

3.4

0.1

1.8

0.5

3.0

77.5

6.86

12.42

3 X 400

23.2

3.4

0.1

1.9

0.8

3.2

85.4

8.97

16.05

3 X 500

26.4

3.4

0.1

2.0

0.8

3.4

93.7

10.65

19.50


13)8.7/10(15)kV Three Cores Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable

No.X Nominal 

Cross Section 

of Conductor

Nominal 

Diameter of 

Conductor

Nominal 

Thickness of 

Insulation

Nominal 

Thickness of 

Copper Tape 

Screen

Nominal 

Thickness of 

Inner Sheath

Nominal 

Thickness of 

Steel Tape 

Armouring

Nominal 

Thickness of 

PVC Sheath

Approx.

 Overall 

Diameter

Approx. Weight

Al

Conductor

Cu

Conductor

No. X mm2

mm

mm

mm

mm

mm

mm

mm

kg/m

kg/m

3 X 25

6.0

4.5

0.1

1.4

0.5

2.1

48.6

2.53

2.98

3 X 35

6.9

4.5

0.1

1.4

0.5

2.2

50.7

2.76

3.39

3 X50

8.2

4.5

0.1

1.5

0.5

2.3

53.9

3.10

3.95

3 X 70

9.7

4.5

0.1

1.5

0.5

2.4

57.4

3.51

4.74

3 X 95

11.3

4.5

0.1

1.5

0.5

2.6

61.2

4.05

5.75

3 X 120

12.8

4.5

0.1

1.6

0.5

2.6

64.7

4.56

6.72

3 X 150

14.2

4.5

0.1

1.6

0.5

2.7

67.9

5.04

7.74

3 X 185

15.9

4.5

0.1

1.7

0.5

2.8

71.9

5.66

9.04

3 X 240

18.3

4.5

0.1

1.8

0.5

3.0

77.7

6.56

11.00

3 X 300

20.4

4.5

0.1

1.9

0.8

3.2

84.1

8.39

13.96

3 X 400

23.2

4.5

0.1

2.0

0.8

3.3

90.5

9.71

16.79

3 X 500

26.4

4.5

0.1

2.1

0.8

3.5

98.8

11.45

20.57


14)12/20(24)kV, 12.7/22(24)kV Three Cores Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable

No.X Nominal 

Cross Section 

of Conductor

Nominal 

Diameter of 

Conductor

Nominal 

Thickness of 

Insulation

Nominal 

Thickness of 

Copper Tape 

Screen

Nominal 

Thickness of 

Inner Sheath

Nominal 

Thickness of 

Steel Tape 

Armouring

Nominal 

Thickness of 

PVC Sheath

Approx. 

Overall 

Diameter

Approx. Weight

Al

Conductor

Cu

Conductor

No. X mm2

mm

mm

mm

mm

mm

mm

mm

kg/m

kg/m

3 X 25

 

 

 

 

 

 

 

 

 

3 X 35

6.9

5.5

0.1

1.5

0.5

2.4

55.6

3.14

3.77

3 X50

8.2

5.5

0.1

1.5

0.5

2.5

58.6

3.49

4.34

3 X 70

9.7

5.5

0.1

1.5

0.5

2.6

62.1

3.93

5.16

3 X 95

11.3

5.5

0.1

1.6

0.5

2.6

65.7

4.46

6.16

3 X 120

12.8

5.5

0.1

1.7

0.5

2.7

69.4

5.00

7.15

3 X 150

14.2

5.5

0.1

1.7

0.5

2.8

72.6

5.49

8.19

3 X 185

15.9

5.5

0.1

1.8

0.5

3.0

76.9

6.16

9.53

3 X 240

18.3

5.5

0.1

1.9

0.8

3.2

83.9

7.87

12.31

3 X 300

20.4

5.5

0.1

2.0

0.8

3.2

88.6

8.96

14.52

3 X 400

23.2

5.5

0.1

2.1

0.8

3.5

95.4

10.35

17.43

3 X 500

26.4

5.5

0.1

2.2

0.8

3.7

103.7

12.45

20.23


15)18/30(36)kV,19/33(36)kV Three Cores Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable

No.X Nominal 

Cross Section 

of Conductor

Nominal 

Diameter of 

Conductor

Nominal 

Thickness of 

Insulation

Nominal 

Thickness of 

Copper Tape 

Screen

Nominal 

Thickness of 

Inner Sheath

Nominal 

Thickness of 

Steel Tape 

Armouring

Nominal 

Thickness of 

PVC Sheath

Approx. 

Overall 

Diameter

Approx. Weight

Al

Conductor

Cu

Conductor

No. X mm2

mm

mm

mm

mm

mm

mm

mm

kg/m

kg/m

3 X 25

 

 

 

 

 

 

 

 

 

3 X 35

 

 

 

 

 

 

 

 

 

3 X50

8.2

8.0

0.1

1.7

0.5

2.8

70.4

4.56

5.41

3 X 70

9.7

8.0

0.1

1.7

0.5

2.9

73.9

5.04

6.26

3 X 95

11.3

8.0

0.1

1.8

0.5

3.0

77.7

5.62

7.32

3 X 120

12.8

8.0

0.1

1.9

0.8

3.2

82.8

6.99

9.15

3 X 150

14.2

8.0

0.1

1.9

0.8

3.2

85.8

7.56

10.26

3 X 185

15.9

8.0

0.1

2.0

0.8

3.3

89.9

8.30

11.67

3 X 240

18.3

8.0

0.1

2.1

0.8

3.5

95.7

9.36

13.79

3 X 300

20.4

8.0

0.1

2.2

0.8

3.6

100.6

10.51

16.07

3 X 400

23.2

8.0

0.1

2.3

0.8

3.8

107.2

11.99

19.07

3 X 500

26.4

8.0

0.1

2.4

0.8

4.0

120.1

14.15

23.85

Henan Baifa Electric Power Co., Ltd. is a professional cable & wire manufacturer which integrates R&D, production and sales together. It’s factory Henan Xunda Cable Co., Ltd was established in 2001, and is located in the Science & Technology Industrial Park of Gongyi, Zhengzhou City, Henan Province. The traffic & transportation are extremely convenient with beautiful environment there.Our corporation has passed the ISO9001 quality management system certification, ISO14001 environmental management system certification and GB / T28001-2001 occupational health and safety management system certification, CE European Union Product Certification, CCC China Compulsory Certification, PCCC Power Product Certification, and Flame and Fire Retardant Cable Certification, Coal Safety Certification, High-tech New Enterprise in Henan Province and China Famous Brand.We have the advanced production and testing equipment made from China and abroad countries, completed scientific management system, and mature production technology with strict controlling of raw materials, to provide qualified and reputed products and services for customers. The annual production capacity is 2,600,000.00 km cables and wires. In our factory, there are above 200 staffs totally including workers and supervisors, besides, we also have our own rights for importation and exportation. With strong technical forces indeed, we have many technical and production workers to make sure the production demand. The main products we can produce are Aerial Bundled Cables (ABC), bare conductors (AAC, AAAC, ACSR, ACAR, ACS, CCS, GUY WIRE, STAY WIRE, STEEL WIRE etc.) , power cables and special cables including all the four series products.Our products sales network has covered more than 20 provinces and municipalities in China. Most of products are sold to many countries for overseas marketing including the following areas like Philippines, Indonesia, Bangladesh, UK, Congo, Iran, Australia, Tanzania, USA, Canada, Madagascar, Pakistan, South Africa, Tunis, Dominica, Honduras, Guatemala, Iraq, Chile, Brazil, Peru etc. Our principle is quality first, customer is God, to make them satisfied. Our goal is Baifa Power, Powering Strongly, to make the worldwide power grid operating orderly.