Structure
FN18 load break switch offers switchgear owners and assemblers the advantages of an assemblers the advantages of an advanced interrupting technology and proven,dependable performance ina a compact design.The switch is available to switchgear assemblers as a building block for metal-enclosed and pad-mounted switchgear application in ratings from 12 upto 24kv.
The standard VACF18 switch includes a steel frame with stand-off insulator,aunique puffe-type arc extinguishing system,an operating mechanism and current-carrying components,including blade-type interrupters with cast hinges and jaw connectors.
Optional accessories and features include avariety of operating handles,a motor operator,auxiliary switches,a shunt trip device,fuse bases,mechanical fuse tripping,grounding switches,mechanical door interlocking and key interlocking.

![]()
MODEL DESCRIPTION

Technical Specifications
| Item | Data |
| Rated voltage | 12/24kV |
| Rated current | 630A |
| Rated power frequency | 50/60Hz |
| Rated short-circuit making current | 50kA Peak. |
| Rated peak withstand current | 50kA Peak. |
| Short time withstand current | kAeff. |
| 1 Sec. | 31.5/25 |
| 2 Sec. | 25 |
| 3 Sec. | 16/20 |
| IEC 62271-105(IEC 420 1990-11)Max.breaking current in co-operation with fuses IEC 62271-105(IEC 420 1990-11) | 900/1600A |
| Max.fuse current(XRNT Fuse) | 200A |
| Rated power frequency withstand voltage (50Hz 1min) | |
| -To earth and between phase | 42/65kV |
| -Between fracture | 48/79kV |
| Impulse withstand voltage (1.2/50μs) | |
| -To earth and between poles | 75/125kV |
| -Between fracture | 85/145kV |
| Mechanical life | 200s0cycle |