Membership
Help
CEEG Nanjing Transmission & Distribution Equipment Co., Ltd.
CEEG Nanjing Transmission & Distribution Equipment Co., Ltd.
Product overview
XGN15-12 Box type AC metal enclosed ring network switchgear (hereinafter referred to as ring network cabinet) has reached the standard of IEC298 AC Metal Enclosed Switchgear through type test and long-term trial operation, met the reliable anti misoperation function, and the protection grade has reached IP3X.
XGN15-12 Box type AC metal enclosed ring network switchgear is suitable for AC 50hz.10kv network as power receiving and distribution.
Environmental Conditions Requirements:
1. Altitude not exceeding 2000 m
2. The upper limit of ambient air temperature is + 40 ° and the lower limit is - 25 °
3. Relative humidity: the daily average value shall not be greater than 95%, and the monthly average value shall not be greater than 90%;
4. The surrounding air is not obviously polluted by corrosive gas or combustible gas, water vapor, etc
5. No frequent violent vibration
Technical Parameter
ITEM | NAME | UNIT | DATA | |
1 | Rated Voltage | kV | 12 | 17.5 |
2 | Power frequency voltage (Phase to phase and to ground) (50HZ, 1min) | kV | 42 | 38 |
3 | Impulse withstand voltage (Phase to phase and to ground) | kV | 75 | 95 |
4 | Rated Current | A | 400 | 400 |
630 | 630 | |||
5 | Closed loop breaking current | A | 400 | 400 |
630 | 630 | |||
6 | Breaking current of no-load transformer | A | 25 | 25 |
7 | Cable charging breaking current | A | 25 | 25 |
8 | Rated thermal stability current (1 second) | kV | 12.5 25 | 12.5 25 |
9 | Rated thermal stability current (2 second) | kV | 12.5 20 | 12.5 20 |
10 | Rated thermal stability current (3 second) | kV | 12.5 16 | 12.5 16 |
11 | Rated short circuit making current | kV | 31.5 62.5 | 31.5 62.5 |
12 | Transfer current | A | 1200 | 800 |