Membership
Help
COTRUST TECHNOLOGIES CO., LTD.
COTRUST TECHNOLOGIES CO., LTD.
Order Data
Product Name | Specifications | Order No. |
C35-00 | CTH300-C motion control CPU, 32MB PM, 32KB data stored when power down, 55M expansion bus;1 Free port, 2 EtherCAT port, 1 EtherNET port, 1 USB port. | CTH3 C35-000S1 |
C36-00 | CTH300-C motion control CPU, 32MB PM, 32KB data stored when power down, 55M expansion bus;1 Free port, 2 EtherCAT port, 1 EtherNET port, 1 USB port. Support SoftMotion | CTH3 C36-000S1 |
C37-00 | CTH300-C motion control CPU,32MB PM, 32KB data stored when power down,, 55M expansion bus;1 Free port, 2 EtherCAT port, 1 EtherNET port, 1 USB port, Support SoftMotion, CNC. | CTH3 C37-000S1 |
C35-01 | CTH300-C motion control CPU, 32MB PM, 64KB data stored when power down, 55M expansion bus;1 Free port, 1 EtherCAT port, 1 EtherNET port, 1 CAN port,1 USB port.(Recommend) | CTH3 C35-001S2 |
C36-01 | CTH300-C motion control CPU, 32MB PM, 64KB data stored when power down, 55M expansion bus;1 Free port, 1 EtherCAT port, 1 EtherNET port, 1 CAN port,1 USB port.Support SoftMotion.(Recommend) | CTH3 C36-001S2 |
C37-01 | CTH300-C motion control CPU, 32MB PM, 64KB data stored when power down, 55M expansion bus;1 Free port, 1 EtherCAT port, 1 EtherNET port, 1 CAN port,1 USB port.Support SoftMotion,CNC.(Recommend) | CTH3 C37-001S2 |
| C37-02 | CTH300-C motion control CPU, 32MB PM, 120KB data stored when power down, 55M expansion bus;1 RS485 port(Modbus), 1 EtherCAT port, 1 EtherNET port, 1 CAN port,1 USB port.Support single axis motion control, interpolation, electronic gear and electronic CAM and other SoftMotion command set functions and CNC functions, support CODESYS programming platform SP11 version | CTH3 C37-002S2 |
Performance Parameters
Model No. | C35-00 | C36-00 | C37-00 | C35-01 | C36-01 | C37-01 | C37-02 | ||
Physical Features | |||||||||
Dimension(W×H×D) | 34×115×101.6 mm | ||||||||
Power consumption | 19.2W | ||||||||
Memory | |||||||||
User program memory | 32MB | 32MB | 32MB | 32MB | 32MB | 32MB | 32MB | ||
Power down to maintain space | 32KB | 64KB | 120KB | ||||||
Power supply features | |||||||||
Rated input voltage | 24V DC | ||||||||
Input voltage range | 20.4V~28.8V DC | ||||||||
Input current | 0.8A | ||||||||
Reverse polarity protection | Yes | ||||||||
Bus power supply voltage | +5V DC | ||||||||
Bus supply current | 1.6A | ||||||||
Isolation | Isolation between external power and system power | ||||||||
LED indicator features | |||||||||
24V power indicator (green) | On: 24VDC power supply is normal, off: no 24VDC power supply | ||||||||
SF indicator (red) | On: system failure, off: no error | ||||||||
BF indicator (red) | On: bus failure, off: no error | ||||||||
Run indicator (green) | On: system runs, off: the system stops | ||||||||
STOP indicator (orange) | On: system stops; off: system runs | ||||||||
RJ45 network port indicator | Green | Blink: connected, off: unconnected | |||||||
Yellow | On: 100Mbps, off: 10Mbps | ||||||||
CAN port indicator | Green | -- | Data receiving indicator | ||||||
Yellow | -- | Data transmission indicator | |||||||
Real time clock | |||||||||
Power down of maintain time | Power down retention time approx. 112 hours (typical value) | ||||||||
Precision | Monthly deviation <60 seconds | ||||||||
Read/set the real-time clock | Read/set via the SETRTC directive | ||||||||
Protection function | |||||||||
Power protection | Power supply end provides reverse connection protection function and surge absorption function | ||||||||
Interface protection | Communication port lightning protection | ||||||||
Extend I/O capabilities | |||||||||
Supports INT-00 rack count of 1 CPU | 4 | ||||||||
Maximum number of modules supported per rack | Support up to 8 modules, power, CPU, relay module is not including | ||||||||
Supports ETC-00 rack count of 1 CPU | Supports up to 128 | ||||||||
Number of modules supported per ECT-00 | Supports up to 8 modules | ||||||||
Isolation | |||||||||
Power supply isolation | Isolation between external power and system power | ||||||||
Communication isolation | Ethernet, RS485 isolation, CAN isolation | ||||||||
Model No. | C35-00 | C36-00 | C37-00 | C35-01 | C36-01 | C37-01 | C37-02 | ||||||
Supports SP4 version of Codesys platform | Supports Codesys platform SP11 version | ||||||||||||
EtherNET port | |||||||||||||
Communication port | 1*EtherNET port | ||||||||||||
Baud rate | 10/100Mbps adaptive | ||||||||||||
Protocol type | Codesys custom protocol, based on UDP and TCP, support Ethernet programming and Ethernet communication between CPU, support Socket free communication. | ||||||||||||
Maximum cable length per segment | 100m directly connected | ||||||||||||
Maximum number of connections to a site | UDP supports up to 16 connections and TCP supports up to 32 connections. | ||||||||||||
| DHCP feature | Support | ||||||||||||
| Remote monitoring/programming | Support | ||||||||||||
| Isolation | Communication port isolation | ||||||||||||
EtherCAT port | |||||||||||||
Communication port | 1*EtherCAT port | ||||||||||||
Maximum number of site |
Each master supports up to 128 EtherCAT slave stations per master | ||||||||||||
Protocol type | EtherCAT | ||||||||||||
Support functions | Supports distributed clock configuration | ||||||||||||
Support startup parameter configuration | |||||||||||||
Support for configuring PDO parameters and mappings | |||||||||||||
Support for configuring bus cycle cycle, configuring startup check vendor ID and product ID | |||||||||||||
Maximum cable length per segment | 100m | ||||||||||||
Baud rate | 10/100Mbps adaptive | ||||||||||||
Isolation | Communication port isolation | ||||||||||||
RS485 port | |||||||||||||
Communication port | 1*RS485 port | ||||||||||||
Maximum number of site | Each network with a maximum of 1 master station and 31 slave stations | ||||||||||||
Protocol type | Modbus master/slave protocol | ||||||||||||
Modbus Baud rate | 1200/4800/9600/19200/38400/57600/115200bps | ||||||||||||
Isolation | Communication port isolation | ||||||||||||
CANopen port | |||||||||||||
Communication port | -- | 1*CAN communication master station port | |||||||||||
Maximum number of slave sites | Up to 32 slave stations can be connected behind one master station | ||||||||||||
Protocol type | CANopen DS301 standard protocol | ||||||||||||
Support functions | Support for automatically starting CANOpen Manager | ||||||||||||
Support optional slave polling | |||||||||||||
Support to start slave stations | |||||||||||||
Support to start slave stations | |||||||||||||
Support synchronous production | |||||||||||||
Support synchronous consumption | |||||||||||||
Support heartbeat generation | |||||||||||||
Support activation time creation | |||||||||||||
Transmission rate(kbit/s) | 1000 | 800 | 500 | 250 | 125 | 50 | 20 | ||||||
Maximum length(m) | 25 | 50 | 100 | 250 | 500 | 1000 | 2500 | ||||||
Isolation | Communication port isolation | ||||||||||||
Power interface definition
4pin terminals spaced at 3.81mm apart | Symbol | Signal definition |
| L+ | +24V power |
M | +24V power ground | |
| Ground | |
-- | -- |
USB interface definition
USB port | No. | Signal | Signal definition |
![]() | 1 | V_BUS | +5V power |
2 | Data- | Data- | |
3 | Data+ | Data+ | |
4 | GND | Ground |
EtherNET interface definition
RJ45 port | No. | Signal | Signal definition |
| 1 | TX+ | Positive end of data transmission |
2 | TX- | Negative end of data transmission | |
3 | RX+ | Positive end of data transmission | |
4 | TERM | -- | |
5 | TERM | -- | |
6 | RX- | Negative end of data transmission | |
7 | TERM | -- | |
8 | TERM | -- | |
Shell | PE | Shell ground | |
Green indicator | As an indication of EtherNET connection status | ||
Yellow indicator | As an indication of EtherNET connection status | ||
CAN interface definition
RJ45 port | No. | Signal | Signal definition |
![]() | 1 | CAN_H | Positive end of data transmission |
2 | CAN_L | Negative end of data transmission | |
3 | -- | -- | |
4 | -- | -- | |
5 | -- | -- | |
6 | -- | -- | |
7 | CAN_GND | CAN Gound | |
8 | -- | -- | |
| Shell | PE | Shell ground | |
| Green indicator | As an indication of CAN connection status | ||
| Yellow indicator | As an indication of CAN connection status | ||
RS485 interface definition
Port0,use 2pcs of 3pin terminals spaced at 3.81mm apart | ||
6pin terminals | Signal | Signal definition |
| A0 | PORT0 RS485 signal A |
B0 | PORT0 RS485 signal B | |
SG | PORT0 RS485 signal ground | |
A0 | PORT0 RS485 signal A | |
B0 | PORT0 RS485 signal B | |
SG | PORT0 RS485 signal ground | |
Dial switch definition
Dial switch | Symbol | Dial direction | Signal definition |
| RUN | Up | System operation |
STOP | Down | System halt | |
Swivel 5 times in 3 seconds | Reset the IP configuration (once from run-> STOP and once from stop-> RUN) |
DIP | No. | Symbol | Signal definition |
| 1 | Term-PORT0 | Terminal resistance switch 1(PORT0) ON:with terminal resistance OFF:without terminal resistance |
2 | NC | Reserve | |
3 | NC | Reserve |