Specification parameter | Order number |
32MB program data space, 64KB power down hold data, 55M expansion bus, 24VDC power supply, 10 channels digital input,6*500KHZ high-speed counter,1*RS485 port,1*EtherNET port,1*USB port,,1*CAN port,1 *EtherCAT port; support visual WebVisu, support OPC UA slave station, support EtherNet/IP master station, support MODBUS(RTU/TCP) master/slave, support single axis motion, interpolation, electronic gear and electronic CAM and other softmotion instruction set functions, Maximum number of racks :4 (including local racks) Support up to 128 EtherCAT slave stations and support CODESYS programming platform SP18 version. | CTH3 C57-103S2 |
| Product model | C57-A3 | ||||||||
| Order number | CTH3 C57-103S2 | ||||||||
| Physical characteristics | |||||||||
| Size (WxHxD) | 34×115×101.6 mm | ||||||||
| Power loss | 19.2W | ||||||||
| Power supply characteristic | |||||||||
| Rated input voltage | 24V DC | ||||||||
| Input voltage range | 20.4V~28.8V DC | ||||||||
| Input current | 0.8A | ||||||||
| Polarity reverse protection | Yes | ||||||||
| Bus power voltage | +5V DC | ||||||||
| Bus power current | 1.6A | ||||||||
| LED indicator characteristics | |||||||||
| 24V Power indicator (green) | On: 24VDC power supply is normal; Off: No 24VDC power supply. | ||||||||
| SF Indicator (red) | On: The system is faulty. Off: no error. | ||||||||
| BF indicator (red) | On: The bus is faulty. Off: no error. | ||||||||
| RUN indicator (green) | On: The system is running. OFF: The system stops. | ||||||||
| STOP indicator (yellow) | On: The system stops. Off: The system is running | ||||||||
| Ethernet indicator | Link 1 indicator(Green) | On: Connect; Off: No connection | |||||||
| SPEED 1 indicator(Yellow) | On: 100Mbps; Off: 10Mbps | ||||||||
| EtherCAT indicator | LINK 2 indicator(Green) | On: Connected; Off: Not connected | |||||||
| SPEED 2 indicator(Yellow) | On: 100Mbps; Off: 10Mbps | ||||||||
| IO indicator | 10.0~11.1(Green) | ON: Signal input; Off: No signal input | |||||||
| Instruction performance | |||||||||
| Bit instruction execution speed | 15ns | ||||||||
| Floating point instruction execution speed | 45ns | ||||||||
| Data storage specification | Zone I 32K,Zone Q 32K,Zone M 512K | ||||||||
| Internal memory | |||||||||
| User program space | 32M | ||||||||
| Power off hold space | 64KB | ||||||||
| Integrated communication function | |||||||||
| Bus interface | Support | ||||||||
| USB port | 1 | ||||||||
| EtherNET port | 1 | ||||||||
| RS485 port | 1 | ||||||||
| EtherCAT port | 1 | ||||||||
| CAN port | 1 | ||||||||
| EtherCAT port | |||||||||
| Communication interface | 1*EtherCAT port | ||||||||
| Baud rate | 100Mbps adaptive | ||||||||
| Protocol type | EtherCAT Interface protocol | ||||||||
| Maximum cable length per section | 100m | ||||||||
| Maximum number of sites | Each master supports a maximum of 128 EtherCAT slave stations | ||||||||
| Support function | Support distributed clock configuration, redundancy Settings | ||||||||
| Support startup parameter configuration | |||||||||
| Support PDO parameter configuration and mapping | |||||||||
| Support for bus cycle configuration, configure startup check vendor ID and product ID | |||||||||
| Isolate | Yes | ||||||||
| RS485 communication port | |||||||||
| Number of communication interfaces | 1,PORT0 | ||||||||
| Communication protocol | Free port protocol (built-in MODbus-RTU protocol) | ||||||||
| Free port baud rate | Ranges from 1.2Kbps to 115.2Kbps | ||||||||
| Maximum cable length per section | Use isolation repeater: 1000m(115.2Kbps) 1200m(38.4 kbps) Isolation repeater not used: 50m | ||||||||
| Maximum number of sites | 32 stations per segment, 126 stations per network. | ||||||||
| Isolate | Communication port isolation | ||||||||
| CANopen port | |||||||||
| Communication interface | CANopen | ||||||||
| Protocol type | 32 | ||||||||
| Protocol type | CANopen DS301 standard protocol | ||||||||
| Support function | Support automatic start CANopen Manager | ||||||||
| Support Optional slave polling | |||||||||
| Support starting the slave station | |||||||||
| Support NMT | |||||||||
| Support synchronous production | |||||||||
| Support synchronous consumption | |||||||||
| Support heartbeat generation | |||||||||
| Support activation time creation | |||||||||
| Transmission rate (kbit/s) | 1000 | 800 | 500 | 250 | 125 | 50 | 20 | ||
| Maximum length (m) | 25 | 50 | 100 | 250 | 500 | 1000 | 2500 | ||
| Isolate | Communication port isolation | ||||||||
| EtherNET communication port | |||||||||
| Communication interface | 1*EtherNET port | ||||||||
| Baud rate | 10/100Mbps adaptive | ||||||||
| Protocol type | CODESYS custom protocol, based on UDP and TCP(Ethernet programming and CPU support | ||||||||
| Maximum cable length per section | 100m | ||||||||
| Maximum number of connections for a site | UDP supports a maximum of 16 connections | ||||||||
| Isolate | Communication port isolation | ||||||||
| Programming Software | |||||||||
| Programming package | CODESYS V3.5 (SP18 version) | ||||||||
| Programming language | Programming language according to IEC61131-3: CFC/FBD/LD/IL/ST/SFC | ||||||||
| Protection function | |||||||||
| Power supply protection | The power supply terminal provides reverse protection and surge absorption functions | ||||||||
| Interface protection | Lightning protection for communication ports | ||||||||
| Local I/O scalability | |||||||||
| Maximum number of racks | 4 | ||||||||
| Maximum number of modules | Host rack: 11 (power module, CPU, trunk module, 8 signal modules) Slave rack: 10 (power module, trunk module, 8 signal modules) | ||||||||
| Remote I/O expansion capability | |||||||||
| CAN extended maximum number of master stations | 1 | ||||||||
| CAN maximum number of slave stations | Each master station connects to a maximum of 32 CAN slave stations. | ||||||||
| EtherCAT maximum number of extended slaves | Up to 128 EtherCAT slave modules , each EtherCAT slave module has a maximum of 8 signal modules | ||||||||
| Supports motion control function | |||||||||
| Motion control function | Do not support SoftMotion and CNC | ||||||||
| Real-time clock | |||||||||
| Power off hold space | The power failure holding time is about 112 hours (typical value), and the power failure holding time can reach at least 1 year after the external battery is connected | ||||||||
| Precision | Monthly deviation <60 seconds | ||||||||
| Digital input characteristics | |||||||||
| Native integrated IO points | 10 | ||||||||
| Input type | Drain type/source type | ||||||||
| Rated voltage | 24V DC | ||||||||
| Input voltage range | 20.4~28.8V DC | ||||||||
| Surge voltage | 35V DC for 0.5s | ||||||||
| Logic 1 Signal (min) | 15 VDC,2.5mA | ||||||||
| Logical 0 signal (Max) | 5 VDC,1mA | ||||||||
| Connect 2-wire Proximity Switch Sensor (BERO) | 1mA (maximum allowable leakage current) | ||||||||
| Input filtering | Configurable, supporting 0.2us, 0.4us, 0.8us, 1.6us, 3.2us, 6.4us, 12.8us, 0.2ms, 0.4ms,0.8ms, 1.6ms, 3.2ms, 6.4ms, 12.8ms, default is 6.4ms | ||||||||
| Isolation (field vs. logic) | 500V AC,1minute | ||||||||
| Simultaneous connected input | 10 | ||||||||
| Maximum cable length per section | 500 m (standard input) | ||||||||
| Shield | 50m (high speed counter input) | ||||||||
| Unshielded | 300 m (standard input) | ||||||||
| Pulse capture input | 10 | ||||||||
| High count counter | Total | 6 | |||||||
| Single-phase | 6×500KHz | ||||||||
| Two-phase | 4×250KHz | ||||||||

Power interface definition
4 detachable terminals (spacing 3.50mm) | Symbol | Signal definition |
| L+ | 24V power supply positive |
M | 24V power supply negative | |
| 24V power supply GND | |
-- | -- |
USB interface definition
USB interface | Bit number | Signal | Signal definition |
| 1 | V_BUS | +5V power supply |
2 | Data- | Data negative | |
3 | Data+ | Data positive | |
4 | GND | GND |
EtherNET/EtherCAT interface definition
Dual network-port interface | Bit number | Signal | Signal definition |
| 1 | TX+ | Data sending end |
2 | TX- | Data sending negative end | |
3 | RX+ | Data receiving terminal | |
4 | TERM | -- | |
5 | TERM | -- | |
6 | RX- | Data receiving negative end | |
7 | TERM | -- | |
8 | TERM | -- | |
Connector housing | PE | Casing grounding |
RS485/CAN Communication interface definition
Single port interface | Bit number | Signal | Signal definition |
| 1 | CAN_H | Data sending positive end |
2 | CAN_L | Data sending negative end | |
3 | -- | -- | |
4 | A0 | RS485 signal A | |
5 | B0 | RS485 signal B | |
6 | -- | -- | |
7 | CAN_GND | CAN/RS485 signal GND | |
8 | -- | -- | |
Connector housing | PE | Casing grounding |
System running DIP switch definition
System run switch | Symbol | Dip direction | Signal definition |
| RUN | UP | System operation |
STOP | Down | System stop |
Installation specification
1. Use DIN35 standard guide rail.
2. Installation size diagram:

Figure C5X-10 motion controller and installation dimensions