The vacuum interrupter for load break switch is used for breaking load current, i.e. rated working current. It is often combined with fuse, which is used for short circuit protection.
This type of product adopts the ceramic shell made by once sealed exhaust technology, which has the advantages of high insulation level, strong arc extinguishing ability, long service life, simple maintenance, no explosion risk, no pollution, low noise, etc.
The LBS assembled with the vacuum interrupter is suitable for the control and protection of the power transmission and distribution system of the electric power, machinery, chemical industry, metallurgy, mining and railway departments.
STRUCTURE
The vacuum interrupter has a shell made of ceramic and metal sealing. The sectional view of the shell is usually a T-shaped structure with three terminals. One end of the three ceramic insulators is gastight welded with a metal end cover respectively. The first end is equipped with a fixed conductor, which is opposite to the second end surface equipped with a transmission device component. The second fixed conductor is placed on the third end, which is transversely opposite to the axis of the first fixed conductor. The first conductor has a fixed contact mounted at its end.
TECHNICAL SPECIFICATION
No. | Items | Unit | Value |
1 | Rated current | A | 630 |
2 | Rated frequency | Hz | 50 |
3 | Rated short-time power frequency withstand voltage (1min) | kV | 42 |
4 | Rated lighting impulse withstand voltage | kV | 75 |
5 | Rated peak withstand current | kA | 50 |
6 | Rated short-circuit making current (peak) | kA | 50 |
7 | Rated operations of short-circuit breaking current | times | 20 |
8 | Rated operation sequence | O-0.3(0.5)s-CO-180s-CO | |
9 | Rated short-time withstand current | kA | 20 |
10 | Rated duration of short-circuit | s | 4 |
11 | Mechanical endurance | times | 10000 |
12 | Contact closing force | N | 80±30 |
13 | Contact reaction force at rated opening distance | N | 140±40 |
14 | Circuit resistance at lowest rated contact force | μΩ | ≤45 |
15 | Contact erosion limit | mm | 3 |
16 | Average opening speed | m/s | 1.0±0.2 |
17 | Average closing speed | m/s | 0.6±0.25 |
18 | Added contact force | N | 900±500 |
19 | Contact bouncing duration at closing operation | ms | ≤2 |