Membership
Help
COTRUST TECHNOLOGIES CO., LTD.
COTRUST TECHNOLOGIES CO., LTD.
Order Data
Specifications | Order No. |
CPU122,24VDC Power supply,8DI/6DO×24VDC,uni-channel communication | CTS7 112-1AD200X14 |
CPU122,220VAC power supply, | CTS7 112-1BD20-0X14 |
Performance Parameters
Physical Features | |
Dimension(W×H×D) | 90×80×62mm |
Power Dissipation | 5W |
Memory Features | |
Program Memory | 6KB,4K for common users,2K for encrypted users |
Data Memory | 2KB |
Power-failure retention power | button battery |
General Features | |
Timers in total 1ms 10ms 100ms | 128(T0-T127) 4 16 108 |
Counters in total | 128(button battery) |
Internal Memory Bits | 128(button battery) |
Power-failure retention of internal memory | 112 |
Time interrupts | 2×1ms Resolution |
Edge interrupts | 4 rising edges/ falling edges |
Boolean execution speed | 0.5µs |
Float execution speed | 16µs |
Runtime clock | √ |
Integrated Communication Function | |
Communication Port | PORT0:RS485 |
PPI Baud Rate | 9.6, 19.2kbps |
Maximum cable length per segment Isolated repeater applied Isolated repeater unapplied | When it is 1200 m, 38.4k. 50 m |
Maximum number of stations | 4 stations per segment,32 stations per network |
Maximum number of masters | 16 |
Point to point (PPI Mater Mode) | × |
Power Function | |
Input Voltage | 20.4 to 28.8 VDC , with anti- reverse connection protection |
+5V power for the extended bus | × |
24 VDC Sensor Power supply | × |
I/O Features | |
Number of integrated Digital inputs | 8 |
Input type | Sink/Source |
Number of integrated Digital outputs | 6 |
Output type | Solid-MOSFET(Source) |
Digital I/O mapping area | 128(64 inputs/64 outputs) |
Analog I/O mapping area | 32(16 inputs/16 outputs) |
Maximum number of expandable I/O modules | 0 |
Maximum number of digital I/O | 14 |
Maximum number of analog I/O | 0 |
Pulse catch inputs | 8 |
High-speed counters Single phase counters | 4×50KHz,support HSC0、HSC3、HSC4、HSC5,do not support HSC1and HSC2 |
Digital Input Features | |
Number of integrated digital input | 8 |
Input type | Sink/Source |
Rated voltage | 24V DC |
Maximum continuous permissible voltage | 30V DC |
Logical 1 Signal (minimum) Logical 0 Signal (Maximum ) | 14 VDC,2.5mA 5 VDC,1mA |
Isolation( field side and logical circuit) Optical isolation(Galvanic) Isolation group | √ 500V AC,1 minute refer to the Terminal Identification |
Simultaneous Inputs | 8 |
Maximum cable length Shielded Unshielded | 500 m(standard input)、50m(high-speed counter input) 300 m( standard input) |
Digital Output Features | |
Number of integrated digital output | 6 |
Output type | Solid-MOSFET(Source) |
Maximum rated current of each output Surge Current | 0.75A 8A,100 millisecond |
Lamp load(Max) | 5W |
On- state resistance | 0.3 ohm , (Max :0.6 ohm ) |
High-speed pulse output | 2×50KHz,Q0.0 and Q0.1, directionless output; Support MC_PTP_R/MC_SPEED_CTRL etc. of CPU, do not support PTO/PWM of programming software |
Simultaneous output | 6 |
Two parallel outputs | only when the two outputs are in the same group |
Maximum cable length Shielded Unshielded | 500m(standard output) 150m(standard output) |
Performance Parameters
Physical Features | ||
Dimension(W×H×D) | 90×80×62mm | |
Power dissipation | 7W | |
Memory Features | ||
Program memory | 6KB,4K for common users,2K for encrypted users | |
Data memory | 2KB | |
Power-failure retention power | button battery | |
General Features | ||
Timers in total 1ms 10ms 100ms | 128(T0-T127) 4 16 108 | |
Counters in Total | 128(button battery) | |
Internal memory bit | 128( button battery) | |
Power-failure retention of internal memory | 112 | |
Time interrupts | 2×1ms resolution | |
Edge interrupts | 4 rising edges/ falling edges | |
Boolean execution speed | 0.5µs | |
Float execution speed | 16µs | |
Runtime clock | √ | |
Integrated Communication Function | ||
Communication port | PORT0:RS485 | |
PPI Baud Rate | 9.6, 19.2kbps | |
Maximum cable length per segment Isolated repeater applied Isolated repeater unapplied | When it is 1200 m, 38.4k. 50m | |
Maximum number of stations | 4 stations per segment,32 stations per network | |
Maximum number of masters | 16 | |
Point to point (PPI Mater Mode) | × | |
Power Function | ||
Input Voltage | 85-264VAC(47-63HZ) | |
+5V power for the extended bus | × | |
24 VDC Sensor Power supply | 240 mA | |
I/O Features | ||
Number of integrated Digital inputs | 8 | |
Input type | Sink/Source | |
Number of integrated Digital outputs | 6 | |
Output type | Relay, dry contact | |
Digital I/O mapping area | 128(64 inputs/64 outputs) | |
Analog I/O mapping area | 32(16 inputs/16 outputs) | |
Maximum number of expandable I/O modules | 0 | |
Maximum number of digital I/O | 14 | |
Maximum number of analog I/O | 0 | |
Pulse Catch inputs | 8 | |
High-speed counters Single phase counters | 4×50KHz,support HSC0、HSC3、HSC4、HSC5, do not support HSC1 and HSC2 | |
Digital Input Features | ||
Number of integrated digital input | 8 | |
Input type | Sink/Source | |
Rated voltage | 24V DC | |
Maximum continuous permissible voltage | 30V DC | |
Logical 1 Signal (minimum) Logical 0 Signal (Maximum ) | 14 VDC,2.5mA 5 VDC,1mA | |
Isolation( field side and logical circuit) Optical isolation(Galvanic) Isolation group | √
500V AC,1 minute refer to the Terminal Identification | |
Simultaneous Inputs | 8 | |
Maximum cable length Shielded Unshielded | 500 m(standard input)、50m(high-speed counter input) 300 m( standard input) | |
Digital Output Features | ||
Number of integrated digital output | 6 | |
Output type | Relay, dry contact | |
Maximum rated current of each output Surge Current | 2A 5A,4S@10% duty ratio | |
Lamp load(Max) | 30 WDC/200WAC | |
On- state resistance | 0.2 ohm | |
Simultaneous output | 6 | |
Two parallel outputs | × | |
Maximum cable length Shielded Unshielded | 500m(standard output) 150m(standard output) | |
Size Diagram:

Wiring Diagram
1.CTS7 112-1AD20-0X14

2.CTS7 112-1BD20-0X14

Definition of Communication Port
Connector | PIN | PORT0(RS485) |
![]() | 1 | Shell grounded |
2 | Logical | |
3 | RS-485 Signal B | |
4 | RTS(TTL) | |
| 5 | Logical | |
6 | +5V,100Ω resistances in series | |
7 | +24V | |
8 | RS-485 Signal A | |
9 | / | |
Shell | Shell grounded |