Membership
Help
COTRUST TECHNOLOGIES CO., LTD.
COTRUST TECHNOLOGIES CO., LTD.
Order data
Specification | Order No. |
CTSC-100 EM123 Digital I/O Module, 16DI/16DO, Relay output | CTS7 123-1PL10 |
Performance Parameters
Features | 16DI×24VDC,16DO×Relay |
Order No. | CTS7 123-1PL10 |
Physical Features | |
Dimension(W*H*D) | 138×80×62mm |
Power Consumption | 6W |
Input Features | |
Number of Inputs | 16 |
Input Type | Sink/Source |
Input Voltage | |
Rated Voltage | 24V DC |
The Maximum permissible Voltage | 30V DC |
Surge Voltage | 35V DC,0.5s |
Signal "1" | 14VDC,2.5mA |
Signal "0" | 5VDC,1mA |
Isolation | |
Optical Isolation | 500V AC, Duration: within 1 minute |
Number of Isolation points per group | 8 |
The longest Input Delay | 4.5 millisecond |
Sink Current | Max: 1mA AC |
Length of Cable | |
Unshielded | 300 m |
Shielded | 500 m |
Simultaneous Inputs | |
40℃ | 16 |
50℃ | 16 |
Output Features | |
Number of Outputs | 16 |
Type of Output | Relay-Dry contract |
Output Current | 0.75A |
Signal "1" Number of Output Groups Number of Outputs per group Simultaneous Outputs Maximum Current per group Lamp Load Contact Resistance Peak Current per point Surge Current(Max) | 2A 4 4 16 8A DC:30W,AC:200W 0.2Ω 7A,Electric shock closed External provide |
Isolation | |
Number of Isolation Points Per group Between coil and power supply Between coil and contact point Resistance | 4 × 1500V AC,duration: within 1 minute Min:100Ω |
Relay Features | |
Switch Delay Switch Frequency Mechanical Switch Frequency Contact point lifetime | 15mS 1HZ 10.000.000 100.000 |
Length of Cable | |
Unshielded | 150 m |
Shielded | 500 m |
Power Waste | |
+5V DC Consumption Current | 138 mA |
L+ | 9mA When Connect |
L+ Coil Voltage Range | 20.4-28.8VDC |
Size Diagram