Order Data
| Order Data | Order No. |
| CTSC-200 EM231, 4AI×TC PID | CTS7 231-7TD32 |
| CTSC-200 EM231, 8AI×TC PID | CTS7 231-7TF32 |
Performance Parameters
Specification | EM231, 4TC×PID | EM231, 8TC×PID |
| Physical Features | ||
Dimensions(W×H×D) | 71.2×80×62mm | 71.2×80×62mm |
| Power Loss(dissipation) | 1.7W | 1.7W |
| Power Consumption | ||
| From +5V(from I/O bus) | 87mA | |
| From L+ | 60 mA | |
| L+ voltage range,class 2 or DC sensor supply | 20.4~28.8V DC | |
| LED indicator | 24 VDC Power Supply Good: ON = no fault,OFF = no power ; SF: ON=module fault, Blink=input signal error, OFF=normal; | |
| Analog Input Features | ||
| Input type | Floating Thermocouple | |
| Input range | TC type: K | |
| Number of analog input points | 4 points | 8 points |
| Isolation | ||
Field to Logic Field to 24V DC 24V DC to logic | 500V AC 500V AC 500V AC | |
| Common mode input range (input channel to input channel) | 120V AC | |
| Common mode rejection | >120dB@120V AC | |
| Input resolution | ||
Temperature Voltage | 0.1℃/0.1℉ 15 bits plus sign | |
| Measuring principle | Sigma-Delta | |
| Module update time for all channel | 425ms | 825ms |
| Wire length to sensor, maximum | 100 m | |
| Wire loop resistance | 100Ω | |
| Suppression of interference | 85dB@ 50Hz/60Hz/400Hz | |
| Data word format | Voltage: -27648 to +27648 | |
| Input impedance | ≥1MΩ | |
| Maximum input voltage | 30V DC | |
| Input filter attenuation | -3dB@ 21kHz | |
| Basic error | 0.1% FS(Voltage) | |
| Repeatability | 0.05% FS | |
| Cold junction error | ±1.5℃ | |
| 24V DC supply voltage range | 20.4 to 28.8 VDC | |
| Diagnostic program | LED:EXTF,SF | |
| PID Features | ||
| PID arithmetic | PID+FUZZY argument auto-tuning | |
| Sampling time | 1 second | |
| Minimum output pulse time | 10 ms | |
| PID type | P、PI、PD、PID | |
| PID output type | Analog or PWM | |
| PID output polarity | Bipolar or unipolar | |
Configuring PID Address
Calculating the PID address
| PID address | Formula | Note |
| Address for PID argument | A=(2048+S*256)+16*C | S is the installing slot no.of the module (0~6) C is the point no.( 0~7 for 8PID module and 0~3 for 4PID module |
| Address for PID positive pulse | X=(2048+S*256)+12 | |
| Address for PID negative pulse | Y=(2048+S*256)+13 |
PID argument output (Module to CPU)
| Description | Address | Setting Value | Actual Value |
| Actual temperature | VM A | -2000~13000 | -200~1300℃ |
| Status word | VM A+2 | data read | |
| PID analog output | VM A+4 | -32000~32000 | -32000~32000 |
PID argument input (CPU to module)
| Description | Address | Setting Value | Actual Value |
| Setting temperature | VM A+128 | -2000~13000 | -200~1300℃ |
| Control bytes | When VB A+130 is zero | When VB A+130 is 1 | |
| V( A+130).0 | PID disable, no output | PID enable | |
| V( A+130).1 | Integral is always active and Kp is not auto tuning | Integral is not active and Kp is auto tuning | |
| V( A+130).2 | Unipolar PID output, 0~32000 | Bipolar PID output, 32000~32000, with calefaction and cooling function | |
| V( A+130).3 | Unused | ||
| V( A+130).4 | Integral is active | Integral is not active | |
| V( A+130).5 | Differential is active | Differential is not active | |
| V( A+130).6 | Filteing for input | Not Filtering for input | |
| Pulse output cycle for PID | VW A+132 | 1~255 | 1~255 seconds |
| Kp | VW A+134 | 0~9999 | 0~999.9 |
| Ti (Integral time) | VW A+136 | 0~3600 | 0~3600 seconds |
| Td (differential time) | VW A+138 | 0~3600 | 0~3600 seconds |
Address for positive pulse output
| point 0 | V X.0 |
| point 1 | V X.1 |
| point 2 | V X.2 |
| point 3 | V X.3 |
| point 4 | V X.4 |
| point 5 | V X.5 |
| point 6 | V X.6 |
| point 7 | V X.7 |
Address for negative pulse output
| point 0 | V Y.0 |
| point 1 | V Y.1 |
| point 2 | V Y.2 |
| point 3 | V Y.3 |
| point 4 | V Y.4 |
| point 5 | V Y.5 |
| point 6 | V Y.6 |
| point 7 | V Y.7 |
Example
VB2546 //control byte (PID enable、auto-tuning、bipolar output)
| thermocouple type | SW3 | 0: Type J 1: Type K |
| Burnout direction | SW4 | 0: Upscale (+3276.7degrees) 1: Downscale (-3276.8degrees) |
| Temperature scale | SW5 | 0:Celsius (℃), 1:Fahrenheit (℉) |
| cold junction compensation | SW6 | 0: enable 1:disable |