Membership
Help
COTRUST TECHNOLOGIES CO., LTD.
COTRUST TECHNOLOGIES CO., LTD.
Order Data
| Order Data | Order NO. |
| CTSC-200 EM231, 4AI×TC, J/K/S/T/R/E/N,+/-80mV | CTS7 231-7PD32 |
| CTSC-200 EM231, 8AI×TC, J/K/S/T/R/E/N,+/-80mV | CTS7 231-7PF32 |
Performance Parameters
Specification | EM231, 4AI×TC | EM231, 8AI×TC |
Physical Features | ||
Dimensions(W×H×D) | 71.2×80×62mm | 71.2×80×62mm |
Power Loss(dissipation) | 1.7W | 1.7W |
| Power Consumption | ||
| From +5V(from I/O bus) | 87mA | |
| From L+ | 60 mA | |
| L+ voltage range,class 2 or DC sensor supply | 20.4~28.8V DC | |
| LED indicator | 24 VDC Power Supply Good: ON = no fault,OFF = no power ; SF: ON=module fault, Blink=input signal error, OFF=normal; | |
| Analog Input Features | ||
| Input type | Floating Thermocouple | |
| Input range | TC type(select one per module): S, T, R, E, N, K, J Voltage range: +/-80mV | |
| Number of analog input points | 4 points | 8 points |
| Isolation | ||
Field to Logic Field to 24V DC | 500V AC 500V AC 500V AC | |
Common mode input range | 120V AC | |
Common mode rejection | >120dB@120V AC | |
| Input resolution | ||
Temperature Voltage | 0.1℃/0.1℉ 15 bits plus sign | |
Measuring principle | Sigma-Delta | |
| Module update time for all channel | 425ms | 825ms |
| wire length to sensor, maximum | 100 m | |
| Wire loop resistance | 100Ω | |
| Suppression of interference | 85dB@ 50Hz/60Hz/400Hz | |
| Data word format | Voltage: -27648 to +27648 | |
| Input impedance | ≥1MΩ | |
| Maximum input voltage | 30V DC | |
| Input filter attenuation | -3dB@ 21kHz | |
| Basic error | 0.1% FS(Voltage) | |
| Repeatability | 0.05% FS | |
Cold junction error | ±1.5℃ | |
| 24V DC supply voltage range | 20.4 to 28.8 VDC | |
DIP Switches Configuration
The EM231 TC modules provide a convenient, isolated interface to seven thermocouple types: J, K, E, N, S, T, and R, which also allow the CTS7-200 PLC to connect low level analog signals of 80mV range. You should use the DIP switched to select the thermocouple type, open wire check, temperature scale, cold junction compensation and burnout direction. All thermocouples connect to a module must be of the same type.
The configuration DIP switches are located on the right bottom of the modules, as shown in the figure 1 and Figure 2, the EM231 4TC module has a 8-pin switches and the EM231 8TC module has a 6-pin switches.
For the DIP switch settings to take effect, you need to power cycle the PLC or the 24V power supply.
Figure 1 EM231 4AI×TC
Figure 2 EM231 8AI×TCSelecting the thermocouple type by setting DIP switch 1 to switch 8 as shown in Table 1 and Table 2 for the EM231 4TC Module, and Selecting the thermocouple type by setting DIP switch 1 to switch 6 as shown in Table 1 and Table 2 for the EM231 8TC Module.
For the EM231 4TC Module, DIP switch 4 is not used, it should be set to the off position. For the EM231 8TC Module, the open wire check is always enable.
Table 1 Selecting the Thermocouple Type
Thermocouple Type SW1 SW2 SW3 J (Default) 0 0 0 K 0 0 1 T 0 1 0 E 0 1 1 R 1 0 0 S 1 0 1 N 1 1 0 +/- 80mV 1 1 1 Table 2 Selecting the others
Feature EM231 4AI×TC EM231 8AI×TC position status position status Burnout Direction SW5 0: Upscale (+3276.7degrees)
1: Downscale (-3276.8degrees)SW4 0: Upscale (+3276.7degrees)
1: Downscale (-3276.8degrees)Open Wire Check SW6 0: enable,
1: disablealways enable Scale Select SW7 0:Celsius (℃),
1:Fahrenheit (℉)SW5 0:Celsius (℃),
1:Fahrenheit (℉)Cold Junction Enable SW8 0: enable
1:disableSW6 0: enable
1:disableSoftware Configuration
The EM231 8AI×TC module has different beginning input address in different slot and its address is not in AIW but in VW, you can calculate the address by the following formula,
x(VWx) = a × 64 + b × 2 (a is the slot no., and b is the point no.)
Table 2 Address for the EM231 8AI×TC
VWx Point 0 Point 1 Point 2 Point 3 Point 4 Point 5 Point 6 Point 7 Slot 0 VW0 VW2 VW4 VW6 VW8 VW10 VW12 VW14 Slot 1 VW64 VW66 VW68 VW70 VW72 VW74 VW76 VW78 Slot 2 VW128 VW130 VW132 VW134 VW136 VW138 VW140 VW142 Slot 3 VW192 VW194 VW196 VW198 VW200 VW202 VW204 VW206 Slot 4 VW256 VW258 VW260 VW262 VW264 VW266 VW268 VW270 Slot 5 VW320 VW322 VW324 VW326 VW328 VW330 VW332 VW334 Slot 6 VW384 VW386 VW388 VW390 VW392 VW394 VW396 VW398Notice: Because the offset address of Td2X text display is also in VW0, so If you need to use Td2X text display in your system, please don’t put the EM231 8AI×TC module in slot 0, or the td2X will not work normally. SIEMENS TD200 text displayer is same as TD2X.(SIEMENS is the trademark of SIEMENS AG.)
Size Diagram

Wiring Diagram