Membership
Help
WENZHOU JUNKE ELECTRIC CO., LTD.
WENZHOU JUNKE ELECTRIC CO., LTD.
Application
NO. | Items | Unit | Data | ||
FZN25-12D/T630-20 | FZRN25-12D/T125-31.5 | ||||
1 | Rated voltage | KV | 12 | ||
2 | Rated frequency | Hz | 50 | ||
3 | Rated Current | A | 630 | 200 | |
4 | Rated insulation level | 1 min power frequency withstanded insulation voltage | KV | Arc chamber between open contacts 30: To earth, phase to phase 42;Isolation between open contacts 48 | |
Lightning impulse withstand voltage | KV | To earth phase to phase 75: solation between open contact 85 | |||
5 | Rated short-time withstand current | KA | 20 | ||
6 | Rated short circuit duration | S | 4 | ||
7 | Rated peak withstand curent | KA | 50 | ||
8 | Rated active load breaking current | A | 630 | ||
9 | Rated closed-loop breaking current | A | 630 | ||
10 | Rated cable charging breaking current | A | 10 | ||
11 | Rated breaking no-load transformer capacity | KVA | 1600 | ||
12 | Rated short-circuit breaking current | KA | - | 31.5 | |
13 | Rated transfer current | A | 2000 | ||
14 | Fuse Type | SDLAJ-12 XPNT1-12 | |||
15 | IImpactor output energy | J | 1+0.5 | ||
16 | Rated short circuit dosing current | KA | 80 (expected peak) | ||
17 | Earthing switch rated short-fime withstand current | KA | 20 | ||
18 | Earthing switch rated short circuit duration | S | 2 | ||
19 | Earthing switch rated peak withstand current | KA | 50 | ||
20 | Auxiliary circuit rated voltage | V | ≈220V,≈110V | ||
21 | Mechanical life | Times | 1000 | ||