Product description
By the perfect integration of stationary type and flexible expansion, SRM type SF6 gas-insulating compact close metal switchgear(Ring main unit) with the adoption of the modular design, is suitable for end-user or network node, meanwhile meets the requirement of all kinds of switching substations cabinet-type transformer substations and cable branch cabinets. It characters on its compact structure, safety and reliability, longevity and maintenance free.

Technical data
| No. | Item | Unit | Parameter | ||||
| 1 | Rated voltage | KV | 11 12 | 24 | 33 | 40.5 | |
| 2 | Rated current | A | 630/1250 | ||||
| 3 | Rated frequency | Hz | 50/60 | ||||
| 4 | 1min Power frequency withstand voltage | Phase to phase, phase to earth | kV | 42 | 55 | 80 | 95 |
| Fracture | 46 | 65 | 95 | 110 | |||
| 5 | Lightning impulse withstand voltage | Phase to phase, phase to earth | kV | 75 | 125/150 | 170 | 95 |
| Fracture | 85 | 150/160 | 185 | 215 | |||
| 6 | Short time withstand current | Main circuit | kA | 25/2s | |||
| Earthing circuit | |||||||
| 7 | Rated withstand current (peak) | kA | 63 | 50 | |||
| 8 | Rated transferring current | A | 1300-1700 | ||||
| 9 | Rated load circuitmarking current | A | 630 | ||||
| 10 | Rated cable(line) charging breaking current | A | Oct-50 | ||||
| 11 | No load transformer breaking current | A | 20 | ||||
| 12 | Cable charge breaking current in earthing fault | A | 100 | 80 | |||
| 13 | Rated short curcuitbreaking current (peak) | kA | 20 | ||||
| 14 | Rated short circuit making current (peak) | kA | 63 | 50 | |||
| 15 | Protection level | IP3X | |||||
| 16 | Load break switch life | times | 5000 | ||||
| 17 | Earthing switch life | times | 5000 | ||||
If you be interested contact us.
FAQ
1.Do your enclosure come with the assembly?
You can choose the empty box or the installation of electrical components, depending on your needs, we can provide.
2. Can I order the cover seperately from the bases?
Yes, you can order boxes and accessories separately, and you can also put forward your customized requirements.
3.How do I order customized enclosures?
The best way is you give us engineering drawings and equipment list, we will arrange engineers to serve you, if there is no drawings, we will also provide solutions for you.
4. What are leading times of orders?