Membership
Help
Henan Senyuan Electric Co., Ltd.
Henan Senyuan Electric Co., Ltd.
GW4-40.5/126 disconnector is self-developed in accordance with the disconnector perfection requirements of China State Grid based on company’s original products. It is suitable to be used in the three-phase AC 50Hz outdoor power distribution system with the rated voltage of 40.5/126kV. Under the circumstance of on-load voltage and non-loaded current, the disconnector can connect, disconnect and isolate the electric circuit and equipment. Made up of base, post insulator and conductive parts, GW4-40.5/126 disconnector has three monopoles of door-type double post structure. Each monopole has two insulating supports parallel to each other and mounted vertically to the horizontal plane. The insulating posts are respectively installed in the bearing pedestal connected to the base, achieving opening and closing operation through a set of four-bar linkage. Fitted with the earthing switch on one side or both sides, the disconnector has four options, including earth-free, left earthing, right earthing, and double earthing.
♦ The contact spring adopts an external pressure type, so as to avoid accidents caused by the spring current-carrying failure.
♦ The conductive tube adopts the square aluminum alloy tube; the flexible connection is made from copper; the conductive contact surface is silver-plated; high mechanical strength and good through-current effect.
♦ The drive parts adopt stainless steel axle pin and composite axle sleeve with less friction and reliable drive.
♦ A reliable interlock device is arranged between the main earthing knife-switch and earthing knife-switch to prevent incorrect manipulation effectively.
♦ The mounting base is fully-sealed, which can effectively prevent water and dust. The bearing pedestal is provided with an oil filler hole and can be maintained without power cut, thus improving the reliability and convenience of the switch.
♦ Large steel parts are hot-dip galvanized with good appearance quality and strong anti-corrosion capability.
No. | Item | Unit | Parameter | ||||||
1 | Rated Voltage | kV | 40.5 | 126 | |||||
2 | Rated Frequency | Hz | 50 | ||||||
3 | Rated Current | A | 1250 | 2000 | 2500 | 4000 | |||
4 | Main Loop Resistance | μΩ | ≤200 | ≤150 | ≤100 | ≤85 | |||
5 | Temperature Rise | Test Current | A | 1.1-fold Rated Current | |||||
6 | Rated Power Frequency (1 min) Withstand Voltage | To Earth | kV | 95 | 230 | ||||
Isolating Fracture | 118 | 230+70 | |||||||
Rated Lightning Impulse Withstand Voltage (Peak)(1.2∕50ms) | To Earth | kV | 185 | 550 | |||||
Isolating Fracture | 215 | 550+100 | |||||||
7 | Rated Short-time Withstand Current & Duration | Disconnecting Switch | kA/s | 25/4 | 31.5/4 | 40/4 | 40/4 | ||
Earthing Switch | 25/4 | 31.5/4 | 40/4 | 40/4 | |||||
8 | Rated Peak Withstand Current | kA | 63 | 80 | 100 | 100 | |||
9 | Conversion Current Capacity of Opening & Closing Busbar | Conversion Current | A | 1600 | |||||
Conversion Voltage | V | 100 | |||||||
Breaking Times | Times | C-O 100 Times | |||||||
10 | Opening & Closing Small Capacitance Current | A | 1 | ||||||
11 | Opening & Closing Small Inductance Current | A | 0.5 | ||||||
12 | Induced Current Capacity of Opening and Closing Earthing Switch | Electromagnetic Induction | Inductive Current | A | 50 | ||||
Recovery Voltage | kV | 0.5 | |||||||
Breaking Times | Times | O、C 10 Times | |||||||
Electrostatic Induction | Capacitance Current | A | 0.4 | ||||||
Recovery Voltage | kV | 3 | |||||||
Breaking Times | Times | O、C 10 Times | |||||||
13 | Mechanical Stability | Times | 3000 | ||||||
14 | Short-duration Power Frequency Withstand Voltage for Auxiliary and Control Circuit | kV | 2 | ||||||
15 | Static Mechanical Load of Terminals | Horizontal Portrait | N | 800 | 1000,1250 | ||||
Horizontal Landscape | 500 | 750 | |||||||
Vertical | 750 | 1000 | |||||||
16 | Post Insulator | Creepage Distance | mm | ≥1256 | ≥3906 | ||||
Height | 550 | 1200 | |||||||