Membership
Help
Zhejiang Volcano electrical technology Co., Ltd
Zhejiang Volcano electrical technology Co., Ltd
Introduction
KYN28A air-insulated metal-clad withdrawable switchgear 3-phase AC 50/60Hz. It is mainly used to receive and distribute 7.2~24kV network electrical and control protection and monitoring to line circuit.
The cabinet is equipped with VS1 , Vacuum circuit breaker, also can be equipped with imported VD4 vacuum circuit breaker and VC series vacuum contactor.
Technical Parameter of Switchgear
No | Name | Unit | Data | |||
1 | Rated voltage | kV | 12 | 15 | 24 | |
2 | Insuation level | Lightning impulse withstand | kV | 75/85 | 90/105 | 125/150 |
1min power frequency | kV | 42/48 | 48/55 | 55/65 | ||
3 | Rated frequency | Hz | 50/60 | |||
4 | Rated current | A | 630,1250,1600,2000,2500,3150, | |||
5 | 4s short time withstand current | kA | 20,25,31,31.5,40,50 | |||
6 | Rated peak withstand current | kA | 50,63,80,100,125 | |||
7 | Thickness | |||||
7.1 | Base frame | mm | 2.0 | |||
7.2 | Side panels | mm | 2.0 | |||
7.3 | Top cover(with provisions of louvers for | mm | 2.0 | |||
7.4 | Doors | mm | 2.0 | |||
8 | Live cable indicators for incoming & | Supply Live display | ||||
9 | Material | Steel sheet coated with | ||||
10 | Protection level | Enclosure IP4X,partition of | ||||
11 | Standard | IEC62271-200 | ||||

THE USE OF CONDITIONS
Air temperature: maximum temperature +40ºC.Minimum temperature -10ºC;
Altitude: ≤1000m;
Relative humidity: daily mean ≤95%, monthly mean ≤90%;
Surrounding air: not suitable for places with corrosion, serious pollution, flammable gas and violent vibration;
Earthquake strength: no more than 8 magnitude.