Welcome Customer !

Membership

XwbooInstrumentationTesting MachineOther Testing MachinesHigh-voltage Switch Tester Verification Device
  • $item.Title
  • $item.Title

High-voltage Switch Tester Verification Device

Wuhan Goldhome Hipot Electrical Co., Ltd.

Model
Nature of the Manufacturer
Manufacturer
Product Category
Other Testing Machines
Place of Origin
HuBei, WuHan
1. The High-voltage switch tester verification device can output 12-circuit breaks at the same time, and can simultaneously simulate the closing/opening of 12 high-voltage circuit breaker contact breaks.2. Simultaneously simulate the closing or opening time of high-voltage circuit breakers, which can be set arbitrarily within the range of 0.001-20000.000 ms, with a resolution of 1 μs,Accuracy: 0.001% reading ±0.005ms;3. The number of bounce pulses can be set arbitrarily within the range of 0-250, and the bounce fre......
I.Overview


HM6080C High-voltage switch tester verification device adopts ARM control and CPLD chip to generate high-precision, wide-range timing signals, and can simulate the action of high-voltage circuit breakers. It can be used to verify and detect the time reference of high-voltage circuit breaker dynamic characteristics tester. To verify the time measurement function of the high voltage switch tester. The High-voltage switch tester verification device can be used stand-alone or connected to a computer.

II、Main technical indicators and conditions of use


1. The High-voltage switch tester verification device can output 12-circuit breaks at the same time, and can simultaneously simulate the closing/opening of 12 high-voltage circuit breaker contact breaks.

2. Simultaneously simulate the closing or opening time of high-voltage circuit breakers, which can be set arbitrarily within the range of 0.001-20000.000 ms, with a resolution of 1 μs,

Accuracy: 0.001% reading ±0.005ms;

3. The number of bounce pulses can be set arbitrarily within the range of 0-250, and the bounce frequency is selectable from 1kHz, 2kHz, 4kHz, and 8kHz.

4. Support different periods of testing.

5. Support internal trigger, external trigger, active trigger, passive trigger.

6. Ambient temperature: 10-30 degrees Ambient humidity: less than 85%

III. Brief introduction of working principle


The circuit of the time calibration device is divided into: trigger circuit, high-speed presettable counter circuit, high-precision crystal oscillator circuit, single-chip control circuit, and output control circuit.

1. 12 circuit break time:

Analog high-voltage circuit breaker 12-way contact output, the first 6-way A1, B1, C1, A2, B2, C2 and the front black grounding jack share the same ground, the rear 6-way A3, B3, C3, A4, B4, C4 and the front end are black The grounding jack has a common ground, which is called a virtual ground. If you want to measure 12 channels at the same time, you must ensure that the two grounds are connected.

It supports setting different time for each fracture and different period setting.

2. Active input external trigger:

The trigger voltage is provided by the calibrated high-voltage switch tester, and the range of input trigger voltage is: DC10-250V.

3. Trigger within active output:

The calibration device provides a trigger voltage to trigger the calibrated high-voltage switch tester. The output voltage is about DC 110V.

4. Passive trigger terminal:

Mainly used to calibrate this device.

V. Specific instructions for use


1. Connect the ground wire (ground wire, fracture wire and control wire) of the test wire between the high-voltage switch tester and the verification device of the high-voltage switch tester. Then turn it on, in order to ensure the reliability of the instrument, turn it on and preheat for more than 5 minutes before performing the test.

2. Calibrate the specific setting and operation of the time parameters of the high-voltage switch tester:

Verification device setting: trigger mode: external trigger

Trigger type: active trigger

Pulse output: node output

Bounce frequency: 1K

The bounce frequency can be selected from 1K, 2K, 4K, 8K. The bounce frequency corresponds to the fineness of the bounce. The higher the frequency, the finer the bounce. The bounce interval of 1KHz is 1/1000=0.001S=1ms, and the bounce interval of 2KHz is 1/2000=0.0005S=0.5ms.

Operation method: enter [1, time bounce setting] in the main menu

Setting of the calibrated high-voltage switch tester: trigger mode: internal trigger

Output voltage: it is appropriate to adjust to between DC100-DC220V

Specific wiring: The red terminal of the verification device is connected to the closing + of the internal DC output power of the high voltage switch tester, the black terminal is connected to the negative of the internal DC output power of the high voltage switch tester, and the green is connected to the internal DC output power of the high voltage switch tester. Gate+.

Operation method: Enter [2, time bounce setting] in the main menu:

Press the up key to enter the position to be modified, such as the A1 closing time break, press the [OK] key, and then press the left and right keys to move the cursor left and right to the corresponding position, and press the up and down keys to modify the number. After modification, press the [OK] key to save the setting, and then press the up, down, left, and right keys to enter other places that need to be modified, and modify according to the above method. After the modification, move the cursor to the [Save] at the bottom of the screen 】, press 【OK】key to save.

Then move the cursor to [3. Time bounce calibration] on the main menu interface, and press the [OK] key to enter,

Press【OK】key to select closing check:

Press the right button to move the cursor to the start of verification:

Press【OK】to start the test:

Observe that the fracture status on the right end of the screen of the verification device will change. If it was opened before, then directly operate the calibrated high-voltage switch tester to perform the closing test (if it is closed. At this time, directly operate the calibrated high-voltage switch tester to perform the opening test), and the verification device operates (you will hear the bee Buzzer sound), wait for the end of the measurement, the tested high-voltage switch tester will display the corresponding waveform and time, synchronization, bounce and other data.

The above operation is to use the internal output power of the high voltage switch tester to trigger the verification device. The verification device is waiting, and the high-voltage switch tester outputs a signal to make the detection system work normally.

A Verification device setting: trigger mode: internal trigger

Trigger type: active trigger

Pulse output: node output

Setting of the calibrated high-voltage switch tester: trigger mode: external trigger

This is to use the verification device to trigger the high-voltage switch tester. The high-voltage switch tester is waiting, and the verification device outputs a signal to make the detection system work normally.

Specific wiring method: If the external trigger of the high-voltage switch tester has only two wires, just connect them regardless of positive and negative. If the external trigger of the high-voltage switch tester has four wires (2 for closing and 2 for opening), use the active output internal trigger mode to operate, and the wire needs to be turned down. That is, during closing verification, the two binding posts are respectively connected to the external closing trigger terminals (red and black jacks) triggered by the high-voltage switch tester; during opening verification, the two binding posts are respectively connected to the external triggering points of the high-voltage switch tester. Trigger terminals outside the gate (green and black jacks).

Refer to the previous article for specific operation methods.

According to the fracture status displayed on the verification device: if it is open, operate the high-voltage switch tester for closing test; if it is closed, operate the high-voltage switch tester for opening test. First operate the high-voltage switch tester to be in the waiting state for triggering, then move the cursor of the verification device to the [Start Calibration] on the right, and press the [OK] button to send a trigger command: the internal trigger signal changes from waiting to output, The calibration device drives the instrument to complete the action, and the corresponding waveform and time, synchronization, bounce and other data appear on the instrument interface.

5.3. Calibrate the specific settings and operations of the verification device of the high-voltage switch tester:

Set the verification device: trigger mode: internal trigger

Trigger type: passive trigger

Pulse output: TTL level output

Connect the positive + of the external 5V power supply to a 1K, 2W resistor in series, and then connect it to the detected fracture port, such as A1. The negative pole of the external 5V power supply-directly connected to the black grounding jack.

Use Agilent 53230A universal counter for time calibration, or use a high-precision oscilloscope to observe: Passive trigger negative-connect to the ground of the oscilloscope, probe 1 connects to passive trigger positive +, and probe 2 connects to the test device to be detected fracture, such as A1. See below:

Passive internal trigger is a falling edge trigger, a falling edge trigger when closing, and a rising edge trigger when opening.

Then follow the operation described in B above.


  Wuhan Goldhome Hi pot Electrical Co.,ltd(short for Goldhome Hi pot) was established in 2008, its predecessor was state-owned third industry enterprises, one of the earliest enterprises specially in develop, design and manufacture high voltage testing equipment in China.In 2016, merged with Wuhan Sang Electric Co., Ltd. , we realize advantageous compartmentalize and resources reorganization.Now it has become a high-tech enterprise integrating R&D, production, marketing installation and commissioning.1.our-historyOur FactoryGoldhome Hi pot is located in Huading Mould Industrial Park, Economic and Technical Development Zone, Wuhan City, Hubei Province, China, working area more than 4000 square meters.As a high-tech enterprise, we are supported by natural advantages from various research universities in Wuhan city. Goldhome Hi pot works closely with professors from State Grid Power Science Research Institute, Electrical Engineering Colleges of Wuhan University and other scientific research institutions, constantly improving technology and updating products . Now Goldhome Hi pot has more than 20 patented technologies, and many software Copyrights!2.our factory-1product and product applicationOur ProductOur advantage products included AC Resonant Test System, PD Free Test System, AC/DC Hi pot Tester, Primary Current Injection, VLF Hi pot Tester, transformer tester,impulse generator,Transformer oil tester,HV Switch gear Tester ,Insulation Tester,ground Resistance Tester,cable fault locator,relay test set,CT PT analyse,arr ester tester and sf6 gas analyzer,etc.Product ApplicationAll the performance indexes of above testing equipment can reach the leading level in China, widely used in power supply bureau, power plant, power construction, railway, petroleum, chemical industry, metallurgy, coal and other industries.In recent years,our factory continues to expand overseas markets, some competitive products are already exported to American and European countries, Africa, Middle East, etc , and well praised by customers.product applicationOur CertificateAll product process is strictly in accordance with international standards and power industry regulations. And the products are through the national, provincial power authorities testing, as well as CE certification! At present,0ur company has received ISO9001:2015 quality management system certification, ISO14001:2018 occupational health and safety management system certification, and ISO14001:2015 environmental management system certification,and also had got SGS certification.We has more than 20 patented technologies,such as The utility model patent of a frequency conversion series resonance test device,The utility model patent of Lightning impulse voltage testing equipment,The utility model patent of DC high voltage generator,The utility model patent of microcomputer relay protection tester,The utility model patent of High voltage switching characteristic tester., etc.4.certificateoverseas market & our serviceOverseas MarketOur products are sold to Europe, Asia, Africa, North and South America and Oceania, Middle East, etc.and are well received by customers.We had won the bids for the purchase of high-voltage no-partial discharge test equipment from the Polish state-owned insulator production plant, the Myanmar National Grid cable fault tester purchase project, and the high-voltage test equipment purchase project of a Russian power installation and test engineering company.We also sell to end customers, and a single device can also be sold. For example, there are power maintenance and installation companies in Indonesia, South Africa, Denmark, and South Korea, and universities and research institutions purchase and use our test equipment.At the same time, our sales targets also include agencies. At present, we already have cooperated with agents in Singapore, Israel, Mauritius , etc.We insist on providing customers with first-class products and first-class services with reliable product quality and perfect service team.5market-1Our service1.Strict factory testAll products will be assembled and test strictly accord with our product process standard. All qualified products will be issued factory release reports and certificate labels.Defect products or non-qualified products won’t be allowed to make deliver.2.Providing technical materialsDuring the product acceptance, we provide the related manual sheets, packing list,qualified certificate labels, factory test reports and other technical documents.3. Support technical guidanceWe also provide the training for the operators. Complete training includes the skilled operations of our equipment, maintenance and troubleshooting . it also ranges the commissioning and test of our products at site!After-sale service1.First-use responsibility systemAfter the product is delivered, the technician can guide the operation at site if the client requires, and be responsible for the first use of each part2.One year warrantyAll products warranty is 1year, life-time maintenance .During the warranty period, if any defects or damaged because of product’s quality, maintenance or replacement can be provided with free charge in order to let our client’s satisfied !3.TroubleshootingIf the troubleshooting is not difficult, and client can handle with it by themselves, we can offer the call-on line guide within 1 hour!If the troubleshooting is difficult to handle with for client, we can promise that the best solution can be provided within 24 hours!