The vacuum circuit breaker adopts spring energy storage type operating mechanism , which can be operated by electric or manual.It can also be equipped with a permanent magnet actuator with a long service life of 60000 times, which is used in extremely frequent operation places.The vacuum circuit breaker is designed as a re encapsulated structure, which can be used either as a fixed installation unit or as a with draw-able installation unit together with the chassis.The vacuum circuit breaker is manufactured in accordance with the national standard GB1984-2003
1. Guide device must be provided for interrupter during operation. The coaxiality of the moving guide pole and the axis of the arc extinguishing chamber must meet the requirements. Torque on bellows is not allowed.
2. During installation, it is forbidden to knock or impact the interrupter shell with hard objects to avoid air leakage due to cracks.
3. Pay attention to make sure that the conducting pole is coaxial with the interrupter, and that the conducting pole is perpendicular to the end face of the fixed end.
4. Pay attention not to remove the interrupter repeatedly to avoid screw slipping. Do not torque the moving conducting rod, and do not overpressure the bellows, so as to avoid torque force and scratches and reduce the service life of the bellows.
5. During installation, the force applied on the surface of both ends shall not exceed the static pressure relief specified in the specification.

Technical Parameter
Item | Description | Unit | Data | |||
1 | Rated voltage | KV | 12 | |||
2 | Max. voltage | KV | 12 | |||
3 | Rated current | A | 630/1000/1250 | 1250/1600 /2000/2500 | 1250/1600 /2000/3150 | |
4 | Rated short circuit opening current | KA | 20/25 | 31.5 | 40 | |
5 | Rated short circuit closing current | KA | 50/63 | 80 | 100 | |
6 | Rated peak withstand current | KA | 50/63 | 80 | 100 | |
7 | 4s Rated short-time withstand current | KA | 20 | 31.5 | 40 | |
8 | Rated insulation level | Power frequency withstand voltage | KV | 42,fracture48 | ||
Impulse withstand voltage(peak) | 75,fracture85 | |||||
9 | Rated operating sequence | O-0.3s-C&O-180s-C&O | ||||
10 | Mechanical life endurance | Times | 10000 | |||
11 | Rated short-circuit opening current sequence | Times | 50 | |||
12 | Clearance between open contacts | mm | 11±1 | |||
13 | Super stroke (the compress length of contact spring) | mm | 3.5±0.5 | |||
14 | Different period among phases for breaking and closing | ms | ≤2 | |||
15 | Bounce time of contact close break | ms | ≤2 | |||
16 | Average break speed | m/s | 0.9~1.2 | |||
17 | Average closing speed | m/s | 0.5~0.8 | |||
18 | Opening time | Under max.operating voltage | s | ≤0.05 | ||
Under min.operating voltage | ≤0.08 | |||||
19 | Closing time | s | ≤0.1 | |||
20 | Resistance of each phase main loop | μΩ | 630A≤65;1250A≤60 | |||
21 | Contacts limit erosion | mm | 3 | |||