Membership
Help
Zhejiang Volcano electrical technology Co., Ltd
Zhejiang Volcano electrical technology Co., Ltd
Environmental Conditions
1. Ambient temperature: not higher than +40 ºC, not less than -15 ºC (at -30 ºC to allow storage and transportation).
2. Altitude: not exceed 1000m.
3. Earthquake intensity: not more than 8 degree.
4. Wind pressure:≤700pa
5. No fire, explosion hazard, serious filthy, chemical corrosion, as well as places of intense vibration

Technical Specifications
| Number | Name | Unit | FN12-12D | FN12-12D(R)D |
| 1 | Rated voltage | KV | 12 | |
| 2 | Rated frequency | Hz | 50 | |
| 3 | Rated current | A | 630 | 125 |
| 4 | Lighting impulse resisting voltage | KV | To earthing.interphase 75 isolation break 85 | |
5 | 1min power frequency withstand voltage | KV | To earthing.interphase 42 isolation break 48 | |
6 | Rated heat-stability current | KA | 20(4S) | |
| 7 | Rated machine-stability current | KA | 50 | |
| 8 | Rated closing current(peak) | KA | 50 | 50 |
| 9 | Rated short-circuit breaking current (prospective value) | KA | 31.5 | |
| 10 | Max.critical breaking current | A2S | fuse box characterisitic curve | |
11 | Min.Breaking current | KA | fuse box characterisitic curve | |
12 | Rated transfer current | KA | 1.5 | |
| 13 | Max.breaking current(reference value) | KA | 1.8 | |
| 14 | Braking no-load transformer capcity | kva | 1250 | |
| 15 | Rated cable charging current | A | 10 | |
| 16 | Rated power load current breaking times | time | ≥100 | |
| 17 | Switch-off time of rated power load current switch on-and-off | S | >0.06 | |
| 18 | Rated transfer current | KA | 20(2S) | 20(2S) |
| 19 | Rated transfer current | KA | 50 | 50 |
| 20 | Motor operating power valtage | V | pay 110,220 direct current | |