FN(R)18-12(D) series indoor high-voltage switch disconnector is applicable to AC three-phase power system with rated voltage of 12kV and rated frequency of 50Hz for opening and closing load current, closed-loop appliance, no-load transformer and cable charging current, closing short-circuit current, mainly used in ring network or terminal power supply of urban distribution station and industrial electrical equipment for short-circuit protection of control box. It is characterized by advanced design, simple operation, compact structure, small volume, full function, light weight, fast opening and closing speed, high reliability, etc.
The FN(R)18 is based on a modular principle.The basic unit consists of a frame with insulators and current carrying parts.Two types of operating mechanisms,snap action mechanism type K or stored energy mechanism type A, can be mounted on the frame.Fuse bases type,with or without fuse tripping mechanism,and an earthing switch type,suitable for both direct mounting and free standing components,complete the basic equipment of a switch disconnector.
A FN18 load break switch,which interrupts load current up to 1250A,and a small fault current circuit. The FN18 switch combines a fuse base with a current-limiting fuse to create a FNR18 switch,which can break large short-circuit current.It provides protection against a majority of fault types in a modern electric network.Both FN18/FNR18 are designed in accordance with the requirement of the following standards:IEC62271-105,GOST 7717-79,GOST1516.3-96 and CSA Standard No.C22.2,93.
FUNCTIONAL DESCRIPTION
To ensure correct operation for all relevant currents,the FN18/FNR18 ais equipped with a dual arc extinguishing system.As the current is being interrupted,the arc will be exposed to :
1:A current independent air blast which automatically starts at the correnct time during the interrupting process.
2:A current dependent gas blast which occurs when the walls of the arcing nozzles are exposed to the hot arc.


TYPE DESIGNATION

TECHNICAL DATA
Rated voltage | kV | 12kV | 24kV | ||||
Rated current | A | 400 | 630 | 1250 | 400 | 630 | 1250 |
Max.rated rated current | A | 400 | 630 | 1250 | 400 | 630 | 1150 |
Short circuit making capacity | kA peak | 67 | 67 | 67 | 50 | 50 | 50 |
Peak withstand current | kA peak | 82 | 82 | 82 | 82 | 82 | 82 |
Short time current 1sec. | kA | 31.5 | 31.5 | 31.5 | 25 | 25 | 31.5 |
Mainly active load breaking capacity | A | 400 | 630 | 1250 | 400 | 630 | 1250 |
Mainly capacitive breaking capacity | A | 150 | 150 | 150 | 80 | 80 | 80 |
Mainly inductive breaking capacity cosφ=0.15 | A | 16 | 16 | 16 | 16 | 16 | 16 |
Earth fault breaking capacity | A | 150 | 150 | 150 | 75 | 75 | 75 |
Capacitive breaking capacity | A | 90 | 90 | 90 | 31.5 | 31.5 | 31.5 |
Max. Breaking capacity in co-operation with fuses | A | 1600 | 1600 | 900 | 900 | ||
Max. Fuse size | A | 125 | 125 | 80 | 80 | ||
Power frequency withstand voltage | |||||||
-to earth and between poles | kV | 42 | 55 | ||||
-acrossisolating distance | kV | 45 | 70 | ||||
Impulse withstand voltage 1.2/50μs | |||||||
-to earth and between poles | kV | 75 | 125 | ||||
-across isolating distance | kV | 85 | 145 | ||||
Pole distance | mm | 150 and 170 | 235, 250 and 275 | ||||
Operating angle on the shaft | degree | 130 | |||||
Opening time | ms | 40-60 | |||||
OUTLINE AND DIMENSION OF INSTALLATION

FN18-12D/630 Air 12kV Air insulated LBS with earthing switch