Application:
M1moulded case circuit breaker with rated insulation voltage800V, applied in the power system of AC50(60)Hz, rated voltage 690V and below, rated current 1250A and below as the transfer not frequently. The circuit breaker has the protection devices of over load, short circuit and under voltage ,it can protect the circuit and power equipment from broken.
The mccb can be sorted to C type (basic),L type (standard),M type (high breaking), H type(higher breaking) according to its rated limit short circuit breaking capacity.
The mccb has the features small volume, breaking capacity high, electric arcing short ,anti-vibration. It is the ideal product for application in land and ship.
The installation can be vertical or level and the standard conforms to IEC60947-2 and GB14048.2
Technical Parameters:
Model | Rated | Poles | Rated | Rated | Electric | Rated | Rated | O performance | |
M1-63L | 6,10, | 2,3,4 | 800 | 400 | 0 | 25 | 18 | 6000 | 8500 |
M1-63M | 690v | 50 | 35 | ||||||
M1-100C | 10,16, | 25 | 18 | ||||||
M1-100L | 0(<=50) | 35 | 22 | ||||||
M1-100M | 50 | 35 | |||||||
M1-100H | 85 | 50 | |||||||
M1-225C | 100,125, | 400 | <=50 | 25 | 18 | 2000 | 7000 | ||
M1-225L | 690v | 35 | 22 | ||||||
M1-225M | 50 | 35 | |||||||
M1-225H | 85 | 50 | |||||||
M1-400C | 225,250, | 35 | 25 | 1000 | 4000 | ||||
M1-400L | 50 | 35 | |||||||
M1-400M | <=100 | 65 | 42 | ||||||
M1-630C | 400,500, | 35 | 25 | ||||||
M1-630L | 50 | 35 | |||||||
M1-630M | 65 | 42 | |||||||
M1-630H | 100 | 65 | |||||||
M1-800M | 630,700, | 75 | 50 | 1000 | 2500 | ||||
M1-800H | 100 | 65 | |||||||
M1-1250H | 800,1000, | <=120 | 100 | 65 | 1000 | 2000 | |||
Trip Mode And Parts:
Parts No. | Parts Name |
208,308 | Alarming contact |
210,310 | Shunt release |
220,320 | Auxiliary contact |
230,330 | Under voltage release |
240,340 | Shunt release ,auxiliary contact |
250,350 | Shunt release, under voltage release |
260,360 | Two group auxiliary contact |
Parts No. | Parts Name |
270,370 | Auxiliary contact, under voltage |
218,318 | Shunt release, alarming contact |
228,328 | Auxiliary contact, alarming contact |
238,338 | Under voltage release, alarming contact |
248,348 | Shunt release, auxiliary contact, alarming contact |
268,368 | Two group auxiliary contact, alarming contact |
278,378 | auxiliary contact, under voltage release, alarming contact |
Thermal Release With Inverse Time Lag:
Ui of release | Thermal breaking release (40for land,45°Cfor ship) | Electromagnetic release breaking current(A) | Remark | |
1.05In(cool station)no breaking time(h) | 1.30(thermal station) breaking time(h) | |||
10 | >=1 | <1 | 10In±20% | Power distribution |
63 | >=2 | <2 | ||
100 | >=2 | <2 | 5In±20%&10In±20% | Power distribution |
10 | 1.0In(cool) no breaking time(h) | 1.20In(thermal) breaking time(h) | 12In±20% | Motor protection |