Membership
Help
CEEG Nanjing Transmission & Distribution Equipment Co., Ltd.
CEEG Nanjing Transmission & Distribution Equipment Co., Ltd.
KYN28-24kv indoor metal clad drawer type switchgear (hereinafter referredto as switchgear) is a complete set of power distribution device of 24 kV Three-Phase AC 50 / 60Hz single bus and single bus section system. It is mainly used for power transmission of power plants, small and medium-sizedgenerators, power distribution of industrial and mining enterprises and institutions, power receiving and transmission of secondary substation of power system, starting of large high-voltage motor, etc.
The switchgear has the interlocking function of preventing the circuitbreaker handcart from being pushed or pulled with load, preventing the circuit breaker from being opened or closed by mistake, preventing the circuit breaker from being closed when the grounding switch is in the closed position,preventing the circuit breaker from entering the live isolation room by mistake, and preventing the grounding switch from being closed by mistake when it is live. It can be equipped with VD4 Vacuum Circuit Breaker of ABB companyand VS1 vacuum circuit breaker developed and manufactured by Senyuan company.
Main technical parameters
Item | Unit | data | ||
Rated voltage | KV | 24 | ||
Rated insulation level | 1min power frequency withstand voltage | KV | 60/79 | |
Lightning impulse withstand voltage(full wave) | KV | 125/145 | ||
Rated frequency | Hz | 50/60 | ||
Main busbar rated current | A | 630、1250、1600、 2000、2500、3150 | ||
Branch busbar rated current | A | 630、800、1250 | ||
Operations of short-circuit breaking current interruption | Times | 30 | ||
Rated short-circuit breaking current rated dynamic current(peak) | KA | 25 | 31.5 | |
Rated short-circuit making current | KA | 63 | 80 | |
Rated short-time withstand current(4s) | KA | 63 | 80 | |
Rated single capacitor bank breaking current | A | 400 | ||
Rated operating sequence | O-0.3s-CO-180s-CO | |||
Rated operating voltage | AC220/110 DC220/110 | |||
Mechanical life | Times | 20000 | ||
Protection class | IP4X for Shell, IP2X for isolation room, IP2X when circuit breaker room’s door is opened. | |||