YH Series Metal Oxide Surge Arrester
Part 1 Overview
The surge arrester is the basis for the insulation coordination of various types of electrical equipment (Transformers, reactors, capacitors, generators, motors, PTs, CTs, circuit breakers, contactors, etc.) in the power system. The protective performance of the surge arrester determines the inside and outside insulation performance (Short duration power frequency withstand voltage, lightning impulse withstand voltage and switching impact withstand voltage, etc.) of all electrical equipment in the power system.
Metal Oxide Surge Arrester (MOA) originates from the United States and Japan in 1980s and is promoted as a new generation of surge arresters and integrated with the most advanced technology than the conventional MOAs. After the full introduction of this technology into China in the mid-1980s and absorb of the technology, the performance of AC surge arresters produced by various professional factories is identical to those produced in the US, Japan, Western Europe and other countries. The products that truly met all the requirements of Chinese national standard can achieve all the requirements of IEC standard.
The core component of MOA, which is called MOV, is based on the application of zinc oxide-based multi-metal oxide powder agglomeration, which has excellent nonlinear volt-ampere characteristics, fast response to steep wave and has large flow capacity. The gapped MOV adopts a self-blowing gap and has a pressure-equalized irradiation structure, which reduces the dispersion of the discharge and has a small impact coefficient.
The application of composite insulated housing conforms to the development trend of miniaturization, safety, and maintenance-free. Compared with inorganic materials such as traditional ceramics and glass, polymer organic composite materials have the advantages of compact size, light weight, resistance to pollution & cleaning free, and explosion-proof and vibration-proof. It is the preferred lightning protection device in the medium and high voltage integrated and modular power transmission and transformation equipment.
Part 2 Product Designation
According to standard JB/T 8459-1996 "Surge Arrester Product Model Methodology", the metal oxide surge arrester’s product model methodology is fined as follows:

(1) When there is no H, it means that the porcelain bushing metal oxide surge arrester
With H indicates composite bushing metal oxide surge arrester
(2) Nominal discharge current kV
(3) Structural features: W: Gapless; C: Series gap; R: Parallel gap
(4) Application: S: For distribution; Z: For substation; R: For capacitor bank; X: For power line;
D: For generator & motor; F: For protection in hermetical electricals; T: For Railway; O: To be used in oil;
L: To be used in DC; G: GIS type
(5) Design Serial Number (To be defined by the manufacturer)
(6) Rated Voltage of Surge Arrester kV (r.m.s)
(7) Maximum residual voltage kV (Peak) at nominal discharge current
(8) Additional Features: W: Anti-pollution; G: To be used in plateau; K: Anti-seismic type; J: Surge Counter;
IM: Monitor; T: For hot & humid condition; L: Disconnector
Part 3 Conditions of Application
1. Indoor or outdoor;
2. Ambient temperature: -40 °C ~ +55 °C;
3. The altitude above sea level shall not exceed 3000m (Porcelain bushing surge arrester shall not exceed 1000m);
4. Power frequency: 48Hz ~ 62Hz;
5. Power frequency voltage applied between the surge arrester terminals for long duration shall not exceed the continuous operating voltage of the surge arrester;
6. Seismic intensity: ≤8 degrees;
7. Maximum wind speed: ≤35m/s.
Part 4 Basic Principal
This series of products are gapless metal oxide surge arresters. Due to the application of zinc oxide resistors as its core component, compared with the traditional silicon carbide surge arresters, it has superior volt-ampere characteristics and high flow capacity, which brings about fundamental changes in the surge arrester’s characteristics.
Under normal operating voltage, the current passing through the surge arrester is only of micro-ampere level and is in an insulating state; when subjected to overvoltage, due to the excellent non-linearity of the zinc oxide resistor, the current flowing through the surge arrester reaches thousands of amperes instantaneously, and the surge arrester is at its on-state, the overvoltage energy is released, and the overvoltage amplitude is limited to the allowable value by the residual voltage of the surge arrester, thereby effectively limiting the damage of the overvoltage to the power transmission and transformation equipment.
Part 5 Model Selection
Users can choose different models of surge arrester according to the object to be protected.
In order to meet the needs of the market, we can design various non-standard products according to the requirements of users.
Part 6 Inspection and Maintenance
First check that the appearance is intact.
Before to put the surge arresters into operation, the DC reference voltage U1mA value shall be measured. The value shall not be less than the value specified in GB 11032-2000 standard. The U1mA leakage current under measurement shall not exceed 50μA. It shall be measured once every four years after being put into operation to see if it meets the requirements. Gapless surge arresters are not allowed to carry out power frequency discharge voltage test.
Part 7 Standard
Product performance is in line with the requirements in GB 11032-2000, IEC 60099-4, IEEEE C62.11 standard.
Part 8 Installation
To Mount in an upright position, the lower electrode studs are attached to the bracket angles.
Please note:
(1) The lower electrode should be connected to the ground wire;
(2) The surge arrester cannot be used as an insulator;
(3) The upper end of the lead wire is preferably a soft copper wire;
(4) Do not disassemble the upper and lower stainless-steel end caps;
(5) Do not use too much force to disassemble and install. Please use a 6 -inch wrench for operation.
Part 9 Common Designations
1. Distribution type: Protection the switchgear, prefabricated type substation, power cable outlet, oil switch on pole of the corresponding voltage level and other power distribution equipment from atmospheric and operating over-voltage damage.
Model of Surge Arrester | System Rated Voltage | Rated Voltage of Surge Arrester | Arrester Continuous Operating Voltage of Surge Arrester
| DC Reference Voltage (U1mA) | Residual Voltage under Steep Wave Impulse Current | Residual Voltage under Lightning Impulse Current | Residual Voltage under Switching Impulse Current | Square Wave Flow Capacity (2ms) | High Current Impact Withstand
|
(r.m.s) kV | ≥ kV | ≤ kV | A | kA | |||||
HY5WS-5/17 | 3 | 5 | 4.0 | 8.0 | 19.6 | 17 | 14.5 | 100 | 65 |
HY5WS-5/16 | 3 | 5 | 4.0 | 8.0 | 18.8 | 16 | 13.5 | 100 | 65 |
HY5WS-10/30 | 6 | 10 | 8.0 | 16.0 | 34.5 | 30 | 25.5 | 100 | 65 |
HY5WS-10/28 | 6 | 10 | 8.0 | 16.0 | 32.5 | 28 | 24.5 | 100 | 65 |
HY5WS-17/50 | 10 | 17 | 13.6 | 25.0 | 57.5 | 50 | 38.5 | 100 | 65 |
HY5WS-17/47 | 10 | 17 | 13.6 | 25.0 | 54.5 | 47 | 36.5 | 100 | 65 |
HY5WS-51/134 | 35 | 51 | 40.8 | 76.0 | 154 | 134 | 114 | 400 | 65 |
HY5WS-51/130 | 35 | 51 | 40.8 | 75.0 | 150 | 130 | 112 | 400 | 65 |
HY5WS-51/125 | 35 | 51 | 40.8 | 73.0 | 145 | 125 | 110 | 400 | 65 |
HY5WS-52.7/134 | 35 | 52.7 | 42.2 | 77.0 | 154 | 134 | 114 | 400 | 65 |
HY5WS-52.7/130 | 35 | 52.7 | 42.2 | 76.0 | 150 | 130 | 113 | 400 | 65 |
HY5WS-52.7/125 | 35 | 52.7 | 42.2 | 73.0 | 145 | 125 | 110 | 400 | 65 |
HY5WS-54/134 | 35 | 54 | 43.2 | 77.0 | 154 | 124 | 114 | 400 | 65 |
HY5WS-54/130 | 35 | 54 | 43.2 | 76.0 | 150 | 130 | 113 | 400 | 65 |
HY5WS-54/125 | 35 | 54 | 43.2 | 74.0 | 145 | 125 | 110 | 400 | 65 |
HY5WS-84/208 | 63 | 84 | 67.2 | 122 | 245 | 208 | 178 | 600 | 100 |
HY5WS-84/221 | 63 | 84 | 67.2 | 125 | 254 | 221 | 188 | 600 | 100 |
HY5WS-90/224 | 63 | 90 | 72.5 | 130 | 258 | 224 | 188 | 600 | 100 |
HY5WS-94/233 | 63 | 94 | 75.2 | 133 | 268 | 233 | 195 | 600 | 100 |
HY5WS-96/250 | 110 | 96 | 76.8 | 145 | 287 | 250 | 213 | 600 | 100 |
HY5WS-100/260 | 110 | 100 | 80.0 | 151 | 299 | 260 | 221 | 600 | 100 |
HY5WS-102/265 | 110 | 102 | 81.6 | 154 | 305 | 265 | 226 | 600 | 100 |
HY5WS-108/281 | 110 | 108 | 86.4 | 163 | 323 | 281 | 239 | 600 | 100 |
HY5WS-116/302 | 110 | 116 | 92.8 | 175 | 347 | 302 | 256 | 600 | 100 |
HY5WS-192/500 | 220 | 192 | 153.6 | 290 | 558 | 500 | 424 | 800 | 100 |
HY5WS-200/520 | 220 | 200 | 160.0 | 302 | 582 | 520 | 442 | 800 | 100 |
HY5WS-204/530 | 220 | 204 | 163.2 | 308 | 588 | 530 | 452 | 800 | 100 |
HY5WS-216/562 | 220 | 216 | 172.8 | 326 | 628 | 562 | 478 | 800 | 100 |
HY5WS-228/593 | 220 | 228 | 182.4 | 344 | 663 | 593 | 504 | 800 | 100 |
1. Power station type: To protect the AC electrical equipment of power plants and substations from atmospheric over-voltage and over-voltage.
Model of Surge Arrester | System Rated Voltage | Rated Voltage of Surge Arrester | Arrester Continuous Operating Voltage of Surge Arrester
| DC Reference Voltage (U1mA) | Residual Voltage under Steep Wave Impulse Current | Residual Voltage under Lightning Impulse Current | Residual Voltage under Switching Impulse Current | Square Wave Flow Capacity (2ms) | High Current Impact Withstand
|
(r.m.s) kV | ≥ kV | ≤ kV | A | kA | |||||
HY5WZ-5/13.5 | 3 | 5 | 4.0 | 7.5 | 15.5 | 13.5 | 11.5 | 150 | 65 |
HY5WZ-10/27 | 6 | 10 | 8.0 | 15.0 | 31.0 | 27 | 23.0 | 150 | 65 |
HY5WZ-17/45 | 10 | 17 | 13.6 | 24.0 | 51.5 | 45 | 38.3 | 150 | 65 |
HY5WZ-17/44 | 10 | 17 | 13.6 | 24.0 | 50.5 | 44 | 37.5 | 150 | 65 |
HY5WZ-51/134 | 35 | 51 | 40.8 | 76.0 | 154 | 134 | 114 | 400 | 65 |
HY5WZ-51/130 | 35 | 51 | 40.8 | 75.0 | 150 | 130 | 112 | 400 | 65 |
HY5WZ-51/125 | 35 | 51 | 40.8 | 73.0 | 145 | 125 | 110 | 400 | 65 |
HY5WZ-52.7/134 | 35 | 52.7 | 42.2 | 77.0 | 154 | 134 | 114 | 400 | 65 |
HY5WZ-52.7/130 | 35 | 52.7 | 42.2 | 76.0 | 150 | 130 | 113 | 400 | 65 |
HY5WZ-52.7/125 | 35 | 52.7 | 42.2 | 73.0 | 145 | 125 | 110 | 400 | 65 |
HY5WZ-54/134 | 35 | 54 | 43.2 | 77.0 | 154 | 134 | 114 | 400 | 65 |
HY5WZ-54/130 | 35 | 54 | 43.2 | 76.0 | 150 | 130 | 113 | 400 | 65 |
HY5WZ-54/125 | 35 | 54 | 43.2 | 74.0 | 145 | 125 | 110 | 400 | 65 |
HY10WZ-51/134 | 35 | 51 | 40.8 | 75.0 | 154 | 134 | 114 | 400 | 100 |
HY10WZ-51/130 | 35 | 51 | 40.8 | 73.0 | 150 | 130 | 112 | 400 | 100 |
HY10WZ-51/125 | 35 | 51 | 40.8 | 74.0 | 144 | 125 | 110 | 600 | 100 |
HY10WZ-51/120 | 35 | 51 | 40.8 | 72.0 | 140 | 120 | 108 | 600 | 100 |
HY10WZ-52.7/134 | 35 | 52.7 | 42.2 | 75.0 | 154 | 134 | 114 | 400 | 100 |
HY10WZ-52.7/130 | 35 | 52.7 | 42.2 | 74.0 | 150 | 130 | 112 | 400 | 100 |
HY10WZ-52.7/125 | 35 | 52.7 | 42.2 | 72.5 | 144 | 125 | 110 | 600 | 100 |
HY10WZ-54/134 | 35 | 54 | 43.2 | 76.0 | 154 | 134 | 114 | 400 | 100 |
HY10WZ-54/130 | 35 | 54 | 43.2 | 75.0 | 144 | 130 | 112 | 600 | 100 |
HY10WZ-94/228 | 63 | 94 | 75.2 | 133 | 263 | 228 | 200 | 600 | 100 |
HY10WZ-96/250 | 110 | 96 | 76.8 | 146 | 280 | 250 | 212 | 600 | 100 |
HY10WZ-100/265 | 110 | 100 | 80.0 | 152 | 291 | 260 | 221 | 600 | 100 |
HY10WZ-102/265 | 110 | 102 | 81.6 | 155 | 297 | 265 | 225 | 600 | 100 |
HY10WZ-108/281 | 110 | 108 | 86.4 | 164 | 314 | 281 | 239 | 600 | 100 |
HY10WZ-116/302 | 110 | 116 | 92.8 | 176 | 338 | 302 | 257 | 600 | 100 |
HY10WZ-126/328 | 110 | 126 | 100.8 | 192 | 367 | 328 | 279 | 600 | 100 |
HY10WZ-192/500 | 220 | 192 | 153.6 | 292 | 560 | 500 | 424 | 800 | 100 |
HY10WZ-198/565 | 220 | 198 | 158.4 | 322 | 633 | 565 | 490 | 800 | 100 |
HY10WZ-200/520 | 220 | 200 | 160.0 | 304 | 582 | 520 | 442 | 800 | 100 |
HY10WZ-204/530 | 220 | 204 | 163.2 | 310 | 594 | 530 | 451 | 800 | 100 |
HY10WZ-216/562 | 220 | 216 | 172.8 | 328 | 628 | 562 | 477 | 800 | 100 |
2. Parallel capacitor type: To suppress over-voltage destruction aroused by switching operation of vacuum switch and less oil switch to the capacitor bank.
Model of Surge Arrester | System Rated Voltage | Rated Voltage of Surge Arrester | Arrester Continuous Operating Voltage of Surge Arrester
| DC Reference Voltage (U1mA) | Residual Voltage under Steep Wave Impulse Current | Residual Voltage under Lightning Impulse Current | Square Wave Flow Capacity (2ms) | High Current Impact Withstand
|
(r.m.s) kV | ≥ kV | ≤ kV | A | kA | ||||
HY5WR-5/13.5 | 3 | 5 | 4.0 | 7.2 | 10.5 | 11.5 | 400 | 65 |
HY5WR-10/27 | 6 | 10 | 8.0 | 14.4 | 27.0 | 21.0 | 400 | 65 |
HY5WR-17/44 | 10 | 17 | 13.6 | 24.0 | 44 | 35.0 | 400 | 100 |
HY5WR-17/42 | 42 | 34.0 | 600 | |||||
HY5WR-17/42 | 42 | 34.0 | 800 | |||||
HY5WR-17/41 | 41 | 34.0* | 1000 | |||||
HY5WR-17/40 | 40 | 34.0* | 1200 | 100 | ||||
HY5WR-48/134 | 35 | 48 | 38.4 | 72.5 | 134 | 105 | 400 | 65 |
HY5WR-48/130 | 130 | |||||||
HY5WR-48/125 | 125 | |||||||
HY5WR-48/125 | 35 | 48 | 38.4 | 72.0 | 125 | 102 | 600 | 100 |
HY5WR-48/120 | 71.0 | 120 | 102 | |||||
HY5WR-48/134 | 73.0 | 134 | 105 | |||||
HY10WR-48/134 | 73.0 | 134 | 105 | |||||
HY10WR-48/125 | 72.0 | 125 | 104 | |||||
HY5WR-48/125 | 35 | 48 | 38.4 | 73.0 | 125 | 104 | 800 | 100 |
HY5WR-48/120 | 120 | |||||||
HY5WR-48/134 | 134 | |||||||
HY10WR-48/134 | 134 | |||||||
HY10WR-48/125 | 125 | |||||||
HY5WR-48/134 | 35 | 48 | 38.4 | 74.0 | 134 | 105 | 1000 | 100 |
HY5WR-48/125 | 74.0 | 125 | 105 | |||||
HY5WR-48/120 | 73.0 | 120 | 102 | |||||
HY10WR-48/134 | 35 | 48 | 38.4 | 73.0 | 134 | 105* | 1000 | 100 |
HY10WR-48/125 | 71.0 | 125 | 103* | |||||
HY10WR-48/120 | 70.0 | 120 | 100* | |||||
Note: * is residual voltage under 1kA switching impulse current.
3. Rotary motor type: To Limit the over-voltage generated when the vacuum switch or the less oil switch switches the rotary motor, and protects the rotary motor from over-voltage damage.
Model of Surge Arrester | System Rated Voltage | Rated Voltage of Surge Arrester | Arrester Continuous Operating Voltage of Surge Arrester
| DC Reference Voltage (U1mA) | Residual Voltage under Steep Wave Impulse Current | Residual Voltage under Lightning Impulse Current | Residual Voltage under Switching Impulse Current | Square Wave Flow Capacity (2ms) | High Current Impact Withstand
|
(r.m.s) kV | ≥ kV | ≤ kV | A | kA | |||||
HY5WD-4/9.5 | 3.15 | 4 | 3.2 | 5.7 | 10.7 | 9.5 | 7.6 | 400 | 65 |
HY5WD-8/18.7 | 6.3 | 8 | 6.3 | 11.3 | 21.0 | 18.7 | 15.0 | 400 | 65 |
HY5WD-13.5/31 | 10.5 | 13.5 | 10.5 | 18.9 | 34.7 | 31.0 | 25.0 | 400 | 65 |
HY5WD-17.5/40 | 13.8 | 17.5 | 13.8 | 24.8 | 44.8 | 40.0 | 32.0 | 400 | 65 |
HY5WD-20/45 | 15.8 | 20 | 15.8 | 28.4 | 50.4 | 45.0 | 36.0 | 400 | 65 |
HY5WD-21/48 | 20.0 | 21 | 16.8 | 29.0 | 54.6 | 48.0 | 44.0 | 1200 | 100 |
HY5WD-23/51 | 18.0 | 23 | 18.0 | 32.0 | 57.2 | 51.0 | 40.8 | 400 | 65 |
HY5WD-25/56.2 | 20.0 | 25 | 20.0 | 35.4 | 62.9 | 56.2 | 45.0 | 400 | 65 |
HY2.5WD-4/9.5* | 3.15 | 4 | 3.2 | 5.7 | 10.7 | 9.5 | 7.6 | 200 | 65 |
HY2.5WD-8/19* | 6.3 | 8 | 6.3 | 11.3 | 21.0 | 19.0 | 15.0 | 200 | 65 |
HY2.5WD-13.5/31* | 10.5 | 13.5 | 10.5 | 18.9 | 34.7 | 31.0 | 25.0 | 200 | 65 |
HY1.5WD-2.4/6** | 3.15 | 2.4 | 1.9 | 3.4 | 6.0 | 200 | 65 | ||
HY1.5WD-5/12** | 6.3 | 5 | 4.0 | 7.1 | 12.0 | 200 | 65 | ||
HY1.5WD-8/19** | 10.5 | 8 | 6.4 | 11.3 | 19.0 | 200 | 65 | ||
Note: * is for application of motor; ** is for application of motor neutral point; rest is for application of generator.
4. Electrified railway type: To protect various electrical equipment, catenaries, and electric locomotives of electrified railways from damage caused by atmospheric over-voltages and operation over-voltages.
Model of Surge Arrester | System Rated Voltage | Rated Voltage of Surge Arrester | Arrester Continuous Operating Voltage of Surge Arrester
| DC Reference Voltage (U1mA) | Residual Voltage under Steep Wave Impulse Current | Residual Voltage under Lightning Impulse Current | Residual Voltage under Switching Impulse Current | Square Wave Flow Capacity (2ms) | High Current Impact Withstand
|
(r.m.s) kV | ≥ kV | ≤ kV | A | kA | |||||
HY5WT-42/120 | 27.5 | 42 | 34.0 | 67 | 138 | 120 | 98 | 400 | 65 |
HY5WT-41/115 | 27.5 | 41 | 32.8 | 67 | 133 | 115 | 94 | 400 | 65 |
HY5WT-84/240 | 55.0 | 84 | 68.0 | 134 | 276 | 240 | 196 | 400 | 65 |
HY5WT-82/230 | 55.0 | 82 | 65.6 | 134 | 266 | 230 | 188 | 400 | 65 |
HY10WT-42/120 | 27.5 | 42 | 34.0 | 66 | 138 | 120 | 98 | 400 | 100 |
HY10WT-41/115 | 27.5 | 41 | 32.8 | 66 | 133 | 115 | 94 | 400 | 100 |
HY10WT-84/240 | 55.0 | 84 | 68.0 | 132 | 276 | 240 | 196 | 400 | 100 |
HY10WT-82/230 | 55.0 | 82 | 65.6 | 132 | 266 | 230 | 188 | 400 | 100 |
5. Transformer neutral type: To protect the transformer neutral point of the corresponding voltage class from atmospheric over-voltage and operating over-voltage damage.
Model of Surge Arrester | System Rated Voltage | Rated Voltage of Surge Arrester | Arrester Continuous Operating Voltage of Surge Arrester
| DC Reference Voltage (U1mA) | Residual Voltage under Steep Wave Impulse Current | Residual Voltage under Lightning Impulse Current | Square Wave Flow Capacity (2ms) | High Current Impact Withstand
|
(r.m.s) kV | ≥ kV | ≤ kV | A | kA | ||||
HY1.5W-55/132 | 110 | 55 | 44.0 | 79 | 132 | 126 | 400 | 65 |
HY1.5W-60/144 | 110 | 60 | 48.0 | 86 | 144 | 135 | 400 | 65 |
HY1.5W-72/186 | 110 | 72 | 58.0 | 103 | 186 | 174 | 400 | 65 |
HY1.5W-73/200 | 110 | 73 | 58.4 | 105 | 200 | 165 | 400 | 65 |
HY1.5W-96/260 | 500 | 96 | 76.8 | 137 | 260 | 243 | 600 | 100 |
HY1.5W-102/260 | 500 | 102 | 80.0 | 158 | 260 | 243 | 600 | 100 |
HY1.5W-144/320 | 220 | 144 | 115.8 | 205 | 320 | 299 | 600 | 100 |
HY1.5W-146/320 | 220 | 146 | 116.8 | 208 | 320 | 304 | 600 | 100 |
HY1.5W-207/440 | 330 | 207 | 165.6 | 292 | 440 | 410 | 600 | 100 |
HY1.5W-210/440 | 330 | 210 | 168.0 | 296 | 440 | 399 | 600 | 100 |
HY1.5W-132/320* | 500 | 132 | 105.6 | 187 | 320 | 272 | 800 | 100 |