Membership
Help
CEEG Nanjing Transmission & Distribution Equipment Co., Ltd.
CEEG Nanjing Transmission & Distribution Equipment Co., Ltd.
Helps to reduce solar plant total cost and promote efficiency, CEEG introduces “Inverter-Onto-Grid PV substation" below

This Inverter-Onto-Grid PV substation ( called all-in-one device) is a complete PV on-gird system of 50Hz 0.4-35KV three phase AC current, involving on-grid inverter; transformer, HV and LV switchgear, and enclosure. This all-in-one device has function of DC distribution, inverting, voltage step-up, monitoring and communication , and other function so forth. This all-in-one device is a perfect replacement of “inverter room & step-up kiosk ” and would be widely applied in distributed generation and centralized power generation. This all-in-one device could meets GB 17467、NB/T 32004、GB1094.11、GB 7251.1、GB 3906 standard.
Features:
1. Turn-key solution
a、All-in-one device of inverter, transformer , HV and LV switchgear. Free on-site installation
b、Container type enclosure, no special hanging device required, easy transportation and loading
2、strong Environment Adaptability
a、Anti-corrosion, high-intensive steel enclosure
b、Flame-proof, stable temperature function and thermal insulation.
c、Excellent Ventilation ability; sand and dust proof
3、High reliability and safety
a、Cast-resin dry-type transformer inside the substation is of anti-burn, anti-explosion and anti- fire
b、C2、E2、F1 Testing certified
4、Reduce total plant cost and promote feedback efficiency
Lower investment, higher feedback
Compared to traditional “inverter room & step-up kiosk ” 15% to 20% of lump sum investment will be saved.
Compared to traditional “inverter room & step-up kiosk ”, the numbers of foundations of this “all-in-one” device has reduced from two to one; meanwhile 50% installation time is saved. The connecting cable between inverter and step-up kiosk has been saved. Two switchgears have been saved between inverter and transformer as well
5 、Flexible design and could be made according to site condition from the customer
General Layout A


General Layout B


Datasheet
Performance | |||
Type | ZD-1000-OD/35 | ZD-2000-OD/35 | |
Incoming Data | |||
Max DC incoming power | 1123KW | 1123KW×2 | |
Max Array Trip Voltage | 1000Vdc | 1000Vdc | |
Incoming working voltage range | 750~1000Vdc | 750~1000Vdc | |
Max incoming current | 1130A*2 | 1439A×2 | |
Numbers of DC incoming branch | 10~20 lines | 20~30 lines | |
Outgoing Data | |||
Rated outgoing Power | 500+500KW | 1000KW×2 | |
Inverter outgoing voltage | 315Vac | 500Vac | |
Transformer outing voltage | 37KV | 37KV | |
Transformer outgoing current | 16.5A | 33A | |
System Characteristics | |||
Transformer Type | Two Windings | Dual outing windings | |
HV SWG | Voltage and current display; surge arrestor; earthing switch; protection fuse | Voltage and current display; surge arrestor; earthing switch; protection fuse | |
LV CT、PT and power meter | Optional | Optional | |
Transformer thermometer remote control | Optional | Optional | |
IP Grade | IP54 | IP54 | |