Membership
Help
Wenzhou Xihe Electric Co.,LTD.
Wenzhou Xihe Electric Co.,LTD.
Fangpusun
Fangpusun Power Star
All the settings of the Fangpusun Power Star can be remote controlled. When a software with new functions is available, it can be loaded into the system, so the Fangpusun Power Star always stays up to date. Several Fangpusun Power Star can be connected in parallel or to form a three-phase system. That means that up to nine Fangpusun Power Star can work together.
Multifunction contacts
These potential-free contacts can be programmed for many different applications. They can react to any event outside or inside of the inverter (grid availability, battery voltage, fault message ...) They can also be programmed on a timer or can be switched on during particular times (at night, at the weekend ...). In this way, they can serve to start up a generator, to switch off less important loads, to signal a fault, to charge batteries depending on the situation, etc.
Smart-boost function
With the smart-boost function, the output of another source of alternating current, such as a power generator or a charger connection, can be increased; even when special loads are being used (inductive, asymmetric, with high switch-on current). It is also possible to combine the Fangpusun Power Star with almost all inverters which are already present in order to increase the available output.
Model | PSH-D3000-12 | PSH-D5000-24 | PSH-D6000-48 | PSH-D8000-48 |
Nominal battery voltage | 12V | 12V | 24V | 24V |
Input voltage range | 9.5-17VDC | 19-34VDC | 38-68VDC | 38-68VDC |
Continuous Power | 2500VA | 4500VA | 5000VA | 7000VA |
Power 30 min. | 3000VA | 5000VA | 6000VA | 8000VA |
Power 5 Sec. | 7.5KVA | 12KVA | 15KVA | 21KVA |
Max.efficiency | 93% | 94% | 96% | 96% |
Own consumption stand by | 1.4W | 1.8W | 2.2W | 2.4W |
Own consumption stand by | 14W | 18W | 22W | 30W |
Acoustic level without ventilation | 40dB | |||
Acoustic level with ventilation | 45dB | |||
Maximum load | Up to short-circuit | |||
Maximum asymmetric load | Up to Pcont. | |||
Load detection (stand-by) | 2 to 25 W | |||
Cos φ | 0.1-1 | |||
Output voltage | Pure sine wave 230Vac (±2%) / 120Vac (1) | |||
Output frequency | 45Hz-60Hz(1) ± 0.05% (crystal controlled) | |||
Harmonic distortion | <2% | |||
Overload and short-circuit protection | Automatic disconnection with 3 time restart attempt | |||
Overheat protection | Warning before shut-off - with automatic restart | |||
Battery charger | ||||
Charge Characteristic | 6 steps : Bulk-Absorption-Floating-Equalization-reduced floating-periodic absorption Number of steps,thresholds,end current and times completely adjustable with the RCC-02/03 | |||
Temperature compensation | With BTS-01 or BSP 500/1200 | |||
Maximum charging current | 160A | 140A | 100A | 120A |
Input voltage range | 150 to 265Vac / 50 to 140Vac (1) | |||
Input frequency | 45 to 65Hz | |||
Input current max . (transfer relay) / Output current max . | 50Aac / 56Aac | 50Aac / 80Aac | ||
Transfer time | < 15ms | |||
Protection index | IP 20 | |||
Operating temperature range | -20 to 55ºC | |||
Ventilation | Forced from 55ºC | |||
Warranty | 2 Years |