Welcome Customer !

Membership

XwbooElectrical & ElectronicsWire & CableInstrumentation CablePower Station Thermocouple / Thermal Resistance
  • $item.Title
  • $item.Title

Power Station Thermocouple / Thermal Resistance

Anhui Hongye Instrumentation Cable Co., Ltd.

Model
Nature of the Manufacturer
Manufacturer
Product Category
Instrumentation Cable
Place of Origin
AnHui, ChuZhou
Power Station Thermocouple / Thermal Resistance
1.Application
Professionally designed for power stations, it can meet the temperature measurement needs of 300,000 and 600,000 kilowatt generating units and auxiliary equipment. Directly measure the temperature of liquid, vapor and gaseous media and solid surface in the range of -200 ° C ~ 800 ° C in various production processes.
2.Working principle
The electrode of a thermocouple consists of two different conductor materials. When there is a temperature difference between the measuring terminal and the reference terminal, a thermoelectric potential will be generated, and the working instrument will display the temperature value corresponding to the thermoelectric potential. Thermal resistance measures the temperature of a substance by changing its resistance as the temperature changes. When the resistance value changes, the working instrument displays the temperature value corresponding to the resistance value.
3.Main technical parameters
Product performance standards:
IEC584 IEC751 IEC1515 JB / T18622-1997 JB / T8623-1997 GB / T16839-1997
4.Measurement range and tolerance
TypeScale numberTolerance level
III
Tolerance valueTemperature measurement range °CTolerance valueTemperature measurement range °C
WRNK±1.5°C-40~+375±2.5 °C-40~+333
±0.004ltl375~1000±0.0075 ltl333~1200
WRMN±1.5°C-40~+375±2.5°C-40~+333
±0.004 ltl375~1000±0.0075 ltl333~1200
WREE±1.5°C-40~+375±1.5°C-40~+333
±0.004 ltl375~800±0.004 ltl333~900
WRFJ±1.5°C-40~+375±1.5°C-40~+333
±0.004 ltl375~750±0.004 ltl333~750
WRCT±1.5°C-40~+125±1°C-40~+133
±0.004 ltl125~350±0.0075 ltl133~350
5. Room temperature insulation resistance
Thermal resistance at ambient temperature is 15-35℃, relative humidity is not more than 80%, test voltage is 10-100V (DC) insulation resistance between electrode and outer tube> 100MΩ.
Thermocouple at ambient temperature of 20 ± 15℃, relative humidity not more than 80%, test voltage is 500 ± 50V (DC), insulation resistance between electrode and outer tube> 1000Ω.m
  At present, the main products produced and developed by the company are: bare copper stranded wires, computer cables, control cables, power cables, compensation cables, coaxial RF cables, high-temperature special cables, cross-linked cables, overhead cables, marine cables, fluoroplastic installation cables , Motor lead wires, instrument signal cables, pre-branched cables, various types of flame-retardant, fire-resistant, low-smoke halogen-free, intrinsically safe cables, rubber jackets, silicone rubber, polytetrafluoride and other high temperature special cables.