XwbooElectrical & ElectronicsIndustrial Control Systems & EquipmentPLCProfinet Slave Module(EM277PN)
  • $item.Title
  • $item.Title

Profinet Slave Module(EM277PN)

COTRUST TECHNOLOGIES CO., LTD.

Model
Nature of the Manufacturer
Other
Product Category
PLC
Place of Origin
,
Profinet Slave Module(EM277PN)
Product Description

① Profinet bus communication rate 100Mbps,the maximum communication distance up to 100m between two slave module(100BASE-TX).

② The topological structure support star,tree,linear,ring structure.

③ Each slave module allow to extend 8 I/O module(digital module,analog module,temperature module,PID module.but CAN module,

     motion control module,weighting  module are not include).

④ Support Siemens Profinet master station,Siemens S7-300,Siemens S7-1200,Siemens S7-1500.

⑤ Programming software TIA Portal V13 and above version.


6365075078755078132476536.jpg

Technical Spec

  

Physical Features

Dimension(W×H×D)

71×80×62 mm

Power Consumption

Rated voltage input

24V DC

Voltage range

20.4V~28.8V DC

Current input

0.8A

Bus power voltage

+5V DC

Bus power current

1.1A

Isolation

The external power supply is isolated from the system power supply

Power protection

provides reverse connection protection and surge absorption

LED Indicator

24V Indicator(Green)

ON = 24VDC power

OFF = 24VDC no power

SF Indicator(red)

ON = extend I/O Bus failure or PROFINET module failure

OFF = no fault

BF Indicator(red)

ON = PROFINET Bus communication failure (no connection to switch, no network detected)

Blinking=Hardware configuration is inconsistent

OFF = no fault

MT Indicator(yellow)

(maintenance indicator )

ON = Loss of synchronization

OFF =  no fault

P1R/P2Rport Indicator(green)

ON = There is a connection to the switch /PN master station

OFF = There is no a connection to the switch /PN master station

P1R/P2Rport Indicator(yellow)

ON = received data

OFF = no received data

 

Expansion I/O

Maximum support module

8(digital module、analog module、temperature module and PID module,other moudle is not included)

Protocol

CTSC-200 PLC 4MHZ Bus protocol

Maximum  IO each station

Analog IO up to 64AI/32AQ

Digital IO up to 256DI/256DQ

Topological structure

support star,tree,linear,ring structure.

PROFINET port

Communication port

1*dual RJ45 port

Data transmission rate

Ethernet speed rate 10Mbps

PROFINET speed rate100Mbps

Support Ethernet

ping、arp、(SNMP)/MIB-2、LLDP

Send

250us~4ms

The third part PROFINET master station

Support

Maximum distance

100m(100BASE-TX)

Topological structure

support star,tree,linear,ring structure.

Isolation

Communication port isolation

Hardware configuration function

File type

PROFINET GDS file XML format

The third part PN master station

Add CTS7 277-0PN32 then support 8pcs expansion model

digital module、analog module、temperature module and PID module,other moudle is not included


Installation

6364887005901074218465628.jpg

COTRUST Technologies Co., Ltd. founded in 2003, is dedicated to R&D, manufacturing and sales of industrial automation control products.Relying on high quality, high performance automation control products and solutions to create maximum value for customers, determined to become the world's leading industrial automation solutions supplier.As a high-tech enterprise, COTRUST provides a wide business coverage of intelligent equipment & robot, new energy vehicles, industrial Internet,smart factory. Main products include PLC, Motion control&servo drive, HMI, dedicated control system and automation software MagicWorks programming software (PLC/HMI/TUNER/OPC),the new launch MiCo remote solution, multi-robot cooperative control system widely used in customer solutions.COTRUST built a long-term partnerships with customers. To achieve this, COTRUST offers more than just products: working with COTRUST gives customers access to leading integrated manufacturing and R&D facilities, as well as highly skilled engineering and industry specialists.COTRUST invests 10% of revenues and 40% of employees in R&D, owned more than 30 trademark registration and 79 patents with certificates( including invention, utility models and appearance). Uses a uniquely rigorous engineering process that incorporates advanced design modelling,performance analysis and quality assurance techniques for improve production capacity continuously and promote sustainable development.On the basis of owning industrial automation technologies with proprietary intellectual property rights, COTRUST perseveres in industry marketing and providing total solution to customers in segment market and achieves growth of both enterprise value and customer value.