Welcome Customer !

Membership

XwbooInstrumentationTesting MachineOther Testing MachinesProtection Relay Test Set
  • $item.Title
  • $item.Title

Protection Relay Test Set

Wuhan Goldhome Hipot Electrical Co., Ltd.

Model
Nature of the Manufacturer
Manufacturer
Product Category
Other Testing Machines
Place of Origin
HuBei, WuHan
Output accuracyoutput:Six-phase current six-phase voltagePhase current output:0~30AAllowable operating value for long time of phase current:10AMaximum output power of phase current:400VAAllow time for maximum current output:10sOutput accuracy:0.2
Product overview

HMJBC-1200 six phase protection relay test set uses the latest generation of high-speed DSP digital signal processor as the core and adopts dual 12-bit D/C, high output precision and good waveform, stable performance.

Protection Relay Test Set is convenient to test the Automatic bus transfer equipment and the microcomputer differential protection device,and equipped with calibration procedures for various relays are targeted. The powerful functional test software can also provide a variety of verification and search methods for complete sets of microcomputer protection and automatic testing of automatic devices.

Test item contains Line protection, differential protection, impedance protection, low cycle, synchronization, automatic switching, etc. Various types of fault simulation programs can simulate and replay actual various types of faults, transient processes, system oscillations, and reclosing actions.


Rated parameter


Project

Plant parameter

Output

Six-phase current six-phase voltage

AC current

Output accuracy

0.2

Phase current output

0~30A

Allowable operating value for long time of phase current

10A

Maximum output power of phase current

400VA

Allow time for maximum current output

10s

DC Current Output

Output accuracy

0.5

Phase voltage output

0-±10A

Phase voltage/line voltage output power

80VA / 100VA

AC voltage output

output accuracy

0.2

Phase voltage output amplitude

0-120V

Output amplitude of line voltage

0-240V

Phase voltage/line voltage output power

80VA / 100VA

DC Voltage Output

Output accuracy

0.5

Phase voltage output amplitude

0-±160V

Output amplitude of line voltage

0-320V

Phase voltage/line voltage output power

70VA / 140VA

Frequency range

20~1000Hz

Harmonic order

1~20

Switching value

Switch input

10pairs

Remarks

idle contact: 1~20mA,24V
Potential Contact Access:“0”:0~ +6V; “1”:+11 V~ +250V

Switch output

8 pairs

Remarks

DC:220V/0.2A;AC:220V/0.5A

Time measurement

measuring range:0.1ms ~ 9999s
certainty of measurement:0.1mS

Dimensions and weights

dimension

No handle:360*425*215mm

weight

19kg

Running conditions

Power Supply Voltage

AC 220V±10%,50/60Hz

ambient temperature

-10℃ ~ +50℃


application of  protection relay test set


Main feature of Protection Relay Test Set


1.Output up to 6-phase voltage and 6-phase current, which can be combined to achieve conventional 4-phase voltage 3-phase current type, 6-phase voltage type, 6-phase current type, and 12-phase type output modes.

2.With High-performance embedded industrial control computer and 8.4" large-screen high-resolution color TFT LCD display,the protection relay test set can provide rich and intuitive information, including the current working status of the equipment, next-step work tips and various help information, etc.

3.The output end uses a high-fidelity, high-reliability modular linear power amplifier, with excellent performance. Will not produce high-frequency and intermediate-frequency interference to the test site, and ensure that the waveform is smooth and accurate throughout the whole process from large current to small current.

4.The output part is controlled by DSP, with fast calculation speed, strong real-time digital signal processing ability, and can control the conversion of high-resolution D/A. The output waveform has high precision, low distortion and good linearity. Adopting a large number of advanced technology and precision component materials, professional structural design, the device is small in size, light in weight, full-featured, easy to carry, convenient for on site test.

5.Protection Relay Test Set can complete various automatic, large-scale and complex calibration tasks.It can easily test and scan various protection settings, perform fault playback, store test data in real time, display vector graphics, and print reports online.

6.Protection Relay Test Set can complete various automated, large-scale and complex calibration tasks.It can easily test and scan various protection settings, playback fault, store test data in real time, display vector graphics, and print reports online.

7.With an independent 110V and 220V dedicated DC power output, convenient for on-site inspection and use.

8.The new generation of TP-60A protection relay test set is equipped with 10-channel open-in and 8-channel open-out, which is convenient for testing the Automatic bus transfer equipment.

9.Provide various automatic test software modules and GPS synchronization trigger test (optional), etc.


Attention(for one of the test function,more attention item please contact us


Microcomputer differential protection is a relatively complex protection, so you can't avoid coming across some problems during debugging. Generally the following points have significant influences on test result:

1、Setting equilibrium factor. Wrong equilibrium factor may lead to a large deviation between the curve tested and setting curve.

2、Selection of restraint formula. Wrong selection of restraint formula results in the testing curve and restraint coefficient calculated deviating from the setting value of protection, even completely wrong.

3、When doing the test by three-phase current, if compensating current does not be included, generally speaking ,if the first action point acts correctly, action points following it will act immediately after current is added. In this case, though the testing phase does not satisfy the condition of differential action, the differential current of compensating phase will exceed the setting value of differential action, so the protection will act quickly.


Harmonic Superposition Test

The ‘Harmonic Superposition’ Test unit can implement superposition output of each order harmonic component of 3 phase voltage and current, which is used for testing the working behavior of equipment of power system in all kinds of harmonic conditions. It is often used for verifying constraint coefficient of differential harmonic.

UA、UB、UC、IA、IB、IC can be overlapped DC and 2~20 order harmonic output.

Each component can be displayed and recorded according to amplitude, and it also can be displayed and recorded according to percentage of fundamental wave

You can select automatic variety or manual variety, and the amplitude and phase will all be changed.

It can measure action value, return value, action time and return time.

¢ Testing Parameters

Variable Option

Variable:Select the channel needed to change from the pulldown menu. In this diagram, A Phase voltage is selected to be variable.

Waveform: Represent harmonic change from DC to the 20th time harmonic.

Step Size of Amplitude Value:The step size here is also corresponding with ‘Harmonic Expressing Mode’. When ‘Express in amplitude value’ is selected, the step size can also be expressed by amplitude, and the unit is A or V; however, when selecting the ‘Express in percentage of fundamental wave’, step size is also the percentage.

Range and Time of Variation

Initial Value of Varitaion:The initial data of variation comes from the data of foregoing harmonic set, which could not be amended. If the initial value needs to be amended, you must do it on the page of harmonic data. The initial value here is expressed in the way of amplitude.

Upper Limit of Variety:It is the output upper limit value of variable, which can ensure the output value not to be very large and avoid ruining the tester.

Variation Time:Variation time stands for the interval of each step variation, and it is normally set to be slightly larger than the setting action time of protection.

Anti-Oscillating of Contacts: The default value is 5ms. When doing the relay test, you should set longer Anti-Oscillating time according to requirement.

Expressing Method of Harmonic

You can select ‘Express in the mode of amplitude’, and also can select ‘Express in percentage of fundamental wave’ to express data of harmonic component of each phase. When ‘Express in percentage of fundamental wave’ is selected, the data of each order harmonic on the page of ‘harmonic’ will be displayed the percentage related to the amplitude of fundamental wave. The step size of amplitude of variable will also be expressed in the percentage of fundamental wave. For example, when the ‘Express in amplitude value’ is selected, amplitude of the second order harmonic of certain phase voltage is 2V and the amplitude of fundamental wave is 10V, then the second order harmonic displayed is 20% when selecting ‘Express in percentage of fundamental wave’.

Set Digital Quantity

The page of digital quantity is used for defining the action of which channel is effective. It defaults that digital quantity of all seven channels A、B、C、R、a、b、c are effective. When doing the test, you can define the digital quantity of which channel is effective (tick ‘√’ means effective). Relation of each is ‘or’.

Way of Variation

Here Manual Operation and Automation (automatically increase and decrease) two kinds of variation are available for implementing change to harmonic components of each phase during the test.


  Wuhan Goldhome Hi pot Electrical Co.,ltd(short for Goldhome Hi pot) was established in 2008, its predecessor was state-owned third industry enterprises, one of the earliest enterprises specially in develop, design and manufacture high voltage testing equipment in China.In 2016, merged with Wuhan Sang Electric Co., Ltd. , we realize advantageous compartmentalize and resources reorganization.Now it has become a high-tech enterprise integrating R&D, production, marketing installation and commissioning.1.our-historyOur FactoryGoldhome Hi pot is located in Huading Mould Industrial Park, Economic and Technical Development Zone, Wuhan City, Hubei Province, China, working area more than 4000 square meters.As a high-tech enterprise, we are supported by natural advantages from various research universities in Wuhan city. Goldhome Hi pot works closely with professors from State Grid Power Science Research Institute, Electrical Engineering Colleges of Wuhan University and other scientific research institutions, constantly improving technology and updating products . Now Goldhome Hi pot has more than 20 patented technologies, and many software Copyrights!2.our factory-1product and product applicationOur ProductOur advantage products included AC Resonant Test System, PD Free Test System, AC/DC Hi pot Tester, Primary Current Injection, VLF Hi pot Tester, transformer tester,impulse generator,Transformer oil tester,HV Switch gear Tester ,Insulation Tester,ground Resistance Tester,cable fault locator,relay test set,CT PT analyse,arr ester tester and sf6 gas analyzer,etc.Product ApplicationAll the performance indexes of above testing equipment can reach the leading level in China, widely used in power supply bureau, power plant, power construction, railway, petroleum, chemical industry, metallurgy, coal and other industries.In recent years,our factory continues to expand overseas markets, some competitive products are already exported to American and European countries, Africa, Middle East, etc , and well praised by customers.product applicationOur CertificateAll product process is strictly in accordance with international standards and power industry regulations. And the products are through the national, provincial power authorities testing, as well as CE certification! At present,0ur company has received ISO9001:2015 quality management system certification, ISO14001:2018 occupational health and safety management system certification, and ISO14001:2015 environmental management system certification,and also had got SGS certification.We has more than 20 patented technologies,such as The utility model patent of a frequency conversion series resonance test device,The utility model patent of Lightning impulse voltage testing equipment,The utility model patent of DC high voltage generator,The utility model patent of microcomputer relay protection tester,The utility model patent of High voltage switching characteristic tester., etc.4.certificateoverseas market & our serviceOverseas MarketOur products are sold to Europe, Asia, Africa, North and South America and Oceania, Middle East, etc.and are well received by customers.We had won the bids for the purchase of high-voltage no-partial discharge test equipment from the Polish state-owned insulator production plant, the Myanmar National Grid cable fault tester purchase project, and the high-voltage test equipment purchase project of a Russian power installation and test engineering company.We also sell to end customers, and a single device can also be sold. For example, there are power maintenance and installation companies in Indonesia, South Africa, Denmark, and South Korea, and universities and research institutions purchase and use our test equipment.At the same time, our sales targets also include agencies. At present, we already have cooperated with agents in Singapore, Israel, Mauritius , etc.We insist on providing customers with first-class products and first-class services with reliable product quality and perfect service team.5market-1Our service1.Strict factory testAll products will be assembled and test strictly accord with our product process standard. All qualified products will be issued factory release reports and certificate labels.Defect products or non-qualified products won’t be allowed to make deliver.2.Providing technical materialsDuring the product acceptance, we provide the related manual sheets, packing list,qualified certificate labels, factory test reports and other technical documents.3. Support technical guidanceWe also provide the training for the operators. Complete training includes the skilled operations of our equipment, maintenance and troubleshooting . it also ranges the commissioning and test of our products at site!After-sale service1.First-use responsibility systemAfter the product is delivered, the technician can guide the operation at site if the client requires, and be responsible for the first use of each part2.One year warrantyAll products warranty is 1year, life-time maintenance .During the warranty period, if any defects or damaged because of product’s quality, maintenance or replacement can be provided with free charge in order to let our client’s satisfied !3.TroubleshootingIf the troubleshooting is not difficult, and client can handle with it by themselves, we can offer the call-on line guide within 1 hour!If the troubleshooting is difficult to handle with for client, we can promise that the best solution can be provided within 24 hours!