● 100mmmeasurement range, particularly suitable for applications that are under highlevel of dust and require larger measurement range.
● Withadjustable guide, effectively improves measurement reliable for sloping solids.
● Withvery high signal-noise ratio, strong interference resistance.
● Intrinsic safety explosion protection certifiedinfrared handheld programmer for wireless remote set up.Measurable solids | Dielectric constant | DK>1.4 |
Antenna | Type | Horn antenna |
Material | 316L | |
Measurement parameters | Transmit frequency | 24.2~25.2GHz (FMCW) |
Measurement range | 100m | |
Blind limitation | 0.35m (count from the reference point) | |
Deviation | 0.25% of full measurement range or 25mm, whichever is larger. | |
Repeatability | ≤10mm | |
Power supply | DC | 24V DC +25/-20%, 6W |
AC | 120~230V AC,±15%, (50/60HZ), 6W | |
Signal output | Analog output | Optical isolation, 4~20mA |
Relay output | Max. 50V DC, 200mA, Rated 5W | |
Communication protocol | HART, PROFIBUS-PA | |
Fault protection | Programmable high, low or hold | |
Operation condition | Process pressure | Max. 0.5bar. |
Process temperature | -40~200℃ | |
Ambient temperature | -40~65℃ | |
Installation level | II | |
Pollution degree | IV | |
Approval | Ingress protection rating | IP67 |
Explosion proof | Flameproof Enclosure: EXd IIC T4 Intrinsic Safety: EXia IIC T4 | |
Materials | External housing | Aluminum coated withpolyester powder. |
Process fitting | 316L | |
Optional device | Dust cover | PTFE |
Purge device | 1/8” NPT |
● Level measurement mainly for industries such aschemical engineering, electric power, cement, environment protection and food processingetc.